11.4  Fault indications

[SC1]

Short circuit in OUT1�

[SC2]

Short circuit in OUT2�

[SC]

Short circuit in both outputs�

[OL]

Detection zone of volumetric flow or temperature exceeded�

Measured value between 120 % and 130 % of the final value of the measuring 

range�

[UL]

Below the temperature detection zone: measured value below -10°C (14 °F)�

[Err]

• 

Unit faulty / malfunction�

• 

Measured value greater than 130 % of the final value of the measuring range�

[SEnS] Sensor indicates incorrect measurement� Possible cause: accumulated gas and 

air in the medium or unit�

For more detailed diagnostics / fault assessment:

 

Briefly press [Set]�

 

> The latest measured values are displayed�

[IOE]

Flow sensor faulty

[Loc]

Setting pushbuttons locked, parameter change rejected�

12  Technical data

Technical data and scale drawing at www�ifm�com�

Summary of Contents for efector300 SU9004

Page 1: ...Operating instructions Ultrasonic flow rate sensor SU9004 80222195 00 11 2014 UK ...

Page 2: ...pes 11 6 Electrical connection 12 7 Operating and display elements 13 8 Menu 14 8 1 Menu structure 14 8 2 Explanation of the menu 15 9 Set up 16 10 Parameter setting 16 10 1 Parameter setting in general 17 10 1 1 Change from menu level 1 to menu level 2 17 10 1 2 Locking unlocking 18 10 1 3 Timeout 18 10 2 Scaling of the analogue value for temperature 18 10 3 Scaling of the analogue value for volu...

Page 3: ...0 4 8 Select the medium to be monitored 20 10 5 Service functions 20 10 5 1 Read min max values for volumetric flow 20 10 5 2 Read the min max values for the temperature 20 10 5 3 Reset all parameters to factory setting 20 11 Operation 21 11 1 Read the process value 21 11 2 Change the display unit in the Run mode 21 11 3 Read the set parameters 21 11 4 Fault indications 22 12 Technical data 22 13 ...

Page 4: ...ions Reaction result Designation of keys buttons or indications Cross reference Important note Non compliance may result in malfunction or interference 1 1 Warning signs used CAUTION Warning of personal injury Slight reversible injuries may result ...

Page 5: ...Technical data The responsibility whether the measurement devices are suitable for the respective application lies with the operator The manufacturer assumes no liability for consequences of misuse by the operator Improper installation and use of the devices result in a loss of the warranty claims For medium temperatures above 50 C 122 F some parts of the housing can heat up to over 65 C 149 F Mor...

Page 6: ... of group 2 fluids in accordance with the sound engineering practice The unit monitors liquid media It detects the two process categories volumetric flow and medium temperature Application area Water Glycol solutions Low viscosity oils viscosity 7 40 mm s at 40 C 7 40 cSt at 104 F High viscosity oils viscosity 30 68 mm s at 40 C 30 68 cSt at 104 F Selection of the medium to be monitored 10 4 8 ...

Page 7: ...ted by the electronics An analogue signal which is proportional to the volumetric flow 4 20 mA is provided on output 2 4 4 4 3 Temperature monitoring An analogue signal which is proportional to the temperature 4 20 mA is pro vided on output 1 4 4 4 4 Analogue function Example of volumetric flow monitoring Factory setting Measuring range scaled I mA 20 4 0 MEW Q I mA 20 4 0 MEW AEP ASP Q MEW Final ...

Page 8: ... calibration allows changing the gradient of the curve of measured values 10 4 5 It influences the display and the outputs 140 MEW 100 MEW 60 MEW MEW Q A V1 V0 V2 A operating value for display and output signals Q flow MEW final value of the measuring range V0 curve of measured values with factory setting V1 V2 curve of measured values after calibration The change in the gradient is indicated in p...

Page 9: ... avoids disturbance by air bubbles Install the unit so that the measuring pipe is completely filled Arrange for inlet and outlet pipe lengths Disturbances caused by bends valves reductions etc are compensated for It applies in particular No shut off and control devices are allowed directly in front of the unit S disturbance D pipe diameter F flow direction Install in front of or in a rising pipe F...

Page 10: ...ation positions F F Directly in front of a falling pipe In a falling pipe F F At the highest point of the pipe system Directly in front of the spout of the pipe F F On the suction side of a pump Flow rate direction horizontal unit vertical connector upwards F flow direction ...

Page 11: ... to the marked flow direction To mount the adapters on the process connection of the sensor use suitable lubricants 3 Screw the adapter B with the threads D until it is hand tight 4 Tighten the two adapters in opposite direction tightening torque 30 Nm After installation air bubbles in the system can affect the measurement Corrective measures Rinse the system after installation for ventilation rin...

Page 12: ...tion of electrical equipment must be adhered to Voltage supply according to EN 50178 SELV PELV Disconnect power Connect the unit as follows BK black BN brown BU blue WH white L L OUT1 OUT2 4 2 4 2 1 3 4 2 1 3 Colours to DIN EN 60947 5 2 Pin 1 L Pin 3 L Pin 4 OUT1 Analogue signal for temperature Pin 2 OUT2 Analogue signal for volumetric flow ...

Page 13: ...edium temperature in F LED 7 LED 8 not used 9 Alphanumeric display 4 digits Indication of the current volumetric flow if SELd FLOW is set Indication of the current medium temperature if SELd TEMP is set Indication of the parameters and parameter values 10 Mode Enter button Selection of the parameters and acknowledgement of the parameter values 11 Set button Setting of the parameter values scrollin...

Page 14: ...14 8 Menu 8 1 Menu structure Mode Enter Set l min C F C F gpm gph m3 h ...

Page 15: ...of the curve of measured values for volumetric flow CAr Reset calibration data FOU1 Status of output 1 in case of a device fault FOU2 Status of output 2 in case of a device fault dAP Measured value damping damping constant for volumetric flow in seconds diS Update rate and orientation of the display Uni F Standard unit of measurement for volumetric flow litres minute lmin cubic metres hour m3 h ga...

Page 16: ...rameter setting Parameters can be set before installation and set up of the unit or during opera tion If you change parameters during operation this will influence the function of the plant Ensure that there will be no malfunctions in your plant During parameter setting the unit remains in the operating mode Run mode It continues to monitor with the existing parameter until the parameter setting h...

Page 17: ...cing the value Let the display move to the maximum setting value Then the cycle starts again at the minimum setting value 3 Acknowledge parameter value Briefly press Mode Enter The parameter is displayed again The new setting value is saved Set other parameters Start again with step 1 Finish parameter setting and change to the process value display wait for 15 s or press Mode Enter several times u...

Page 18: ...ton is pressed for 15 s during parameter setting the unit returns to the operating mode with unchanged parameter 10 2 Scaling of the analogue value for temperature Select ASP1 and set the value at which 4 mA is provided Select AEP1 and set the value at which 20 mA is provided 10 3 Scaling of the analogue value for volumetric flow Select ASP2 and set the value at which 4 mA is provided Select AEP2 ...

Page 19: ...r d1 d2 d3 rotated by 180 OFF the display is switched off in the operating mode 10 4 4 Calibrate the curve of measured values for volumetric flow Select CGA and set a percentage between 60 and 140 100 factory setting 10 4 5 Reset calibration data Select CAr Press and hold Set until is displayed Briefly press Mode Enter The values are reset to the factory setting CGA 100 10 4 6 Set the measured val...

Page 20: ... as soon as the unit operates under normal operating conditions for the first time 10 5 2 Read the min max values for the temperature Select HI T or Lo T briefly press Set HI T max value LO T min value Delete memory Select HI T or LO T Press and hold Set until is displayed Briefly press Mode Enter It makes sense to delete the memories as soon as the unit operates under normal operating conditions ...

Page 21: ...lay unit in the Run mode Briefly press Set in the Run mode Press the button to move to the next dis play unit The display changes according to the preset l min m3 h C F or gpm gph C F The unit displays the current process value in the selected display unit for ap prox 15 s the corresponding LED is lit 11 3 Read the set parameters Briefly press Mode Enter to scroll the parameters Briefly press Set ...

Page 22: ... measured value below 10 C 14 F Err Unit faulty malfunction Measured value greater than 130 of the final value of the measuring range SEnS Sensor indicates incorrect measurement Possible cause accumulated gas and air in the medium or unit For more detailed diagnostics fault assessment Briefly press Set The latest measured values are displayed IOE Flow sensor faulty Loc Setting pushbuttons locked p...

Page 23: ...3 UK 13 Factory setting Factory setting User setting ASP1 10 0 AEP1 80 0 ASP2 0 0 AEP2 200 0 CGA 100 FOU1 OFF FOU2 OFF dAP 0 6 diS d2 Uni F Lmin Uni T C SELd FLOW MEDI H2O More information at www ifm com ...

Reviews: