After mounting, wiring and setting check whether the unit operates
correctly.
When the supply voltage is applied, all LEDs light and go off one after
the other.* The unit is then ready for operation.
*During this time the output is switched according to the programming: relay
energised with the NO function and de-energised with the NC function.
Recommended maintenance
Check the sensor tip for build-up from time to time. Clean it with a
soft cloth. If necessary, build-up which adheres firmly (e.g. lime) can
be removed with a common vinegar cleansing agent.
Technical data
ENGLISH
29
Installation and set-up / Operation / Maintenance
Nominal voltage [V] . . . . . . . . . . . . . . . . . . . . . 90 ... 240 AC (45....65 Hz)
Voltage tolerance [%] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -5 / +10
Operating voltage [V] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 ... 265 AC
Power consumption [VA] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.5
Switching power of relay . . . . . . . . . . . . . . . . . . . . 3A (250V AC / 30V DC)
Number of switching cycles: . . . . . . . . . . . . . . . . . . 20 million mechanically
Switching cycles with 3 A load: . . . . . . . . . . . . . . . . . . . 100.000 electrically
Relay type: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . contact closed at work
Liquids
Medium temperature [°C] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -25 ... +80
Setting range [cm/s] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 ... 300
Greatest sensitivity [cm/s] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 ... 60
Max. temperature gradient of medium [K/min] . . . . . . . . . . . . . . . . . . . 300
Gases
Medium temperature [°C] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -25 ... +80
Setting range [cm/s] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200 ... 3000
Greatest sensitivity [cm/s] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200 ... 800
Response time [s] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 ... 10
Power-on delay time [s] . . . . . . . . . . . . . . . . . . . . . . . 15, optically indicated
Pressure rating [bar] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Operating temperature [°C] . . . . . . . . . . . . . . . . . . . . . . . . . . . . -25 ... +80
Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP 67 / II
Shock resistance [g]. . . . . . . . . . . . . . . . . . . . 50 (DIN / IEC 68-2-27, 11 ms)
Vibration resistance [g] . . . . . . . . . . . . . . 20 (DIN / IEC 68-2-6, 55-2000 Hz)
Housing material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PBT-GF-20
Sensor material . . . . . . . . . . . . . . . . . . . . . . . . . . . stainless steel (316S12);
O-ring: FPM 8x1.5 gr 80° Shore A