8 Settings
Before the first set-up the basic teach empty state must be carried out
8.1 Carry out the basic teach empty state
The basic teach empty state sets the unit to the empty tank and the installation
conditions (eg the set installation length) Previous settings are deleted
► Empty the tank until the medium is at least 20 mm below the end of the probe
► Press [OUT OFF], keep it pressed for min 2 s / max 6 s
> The yellow LED flashes slowly When the button is released, it goes out
The unit is then ready for operation and set as NO unit (output ON when the
level has been reached)
If the unit is to be set as NC unit:
► After emptying the tank press [OUT ON] instead of [OUT OFF] After releasing
the pushbutton, the yellow LED lights continuously
8.2 Carry out the basic teach full state
The empty adjustment is sufficient for media with a low dielectric constant (eg
oils) For aqueous media the sensitivity must be optimised by a full adjustment
The full adjustment does not change the settings of the empty adjustment
► Fill the tank until the active zone of the unit is covered
> If the unit is set as NO unit (→ 8.1), the yellow LED lights, if it is set as NC unit,
it goes out
► If the unit is set as NO unit: press [OUT ON] and keep it pressed for at least
6 s
> The yellow LED flashes slowly, after 6 s it flashes quickly After releasing the
pushbutton, it lights continuously
If the unit is set as NC unit: After filling the tank press [OUT OFF] instead of
[OUT ON] After releasing the pushbutton, the yellow LED goes out