7.2.8 Setting of the error behaviour of the analogue output
► → 4.5.2 Setting of the analogue value in case of diagnosis [FOU2], table
2
7.2.9 Setting of the characteristics of the redundancy switching
►
Select [drEd
]
and set the value:
-
For 2-wire operation (Ub- not connected): → 4.5.1 Availability groups in
2-wire operation [drEd], table 1
-
For 3-wire operation (Ub- connected): → 4.6.1 Availability groups in
3-wire operation [drEd], table 3
7.2.10 Setting of the delay of the drift detection
►
Select [ddr] and set the value between 0�5 and 300 minutes�
By means of this function short exceeding of the drift thresholds can be
filtered out (e�g� in case of large temperature gradients)�
•
ddr value = time for which a drift value must be above the warning/alarm
threshold ([drW], [drA]) in order to activate the diagnostic output�
7.2.11 Set switching logic for OUT1
►
Select [P-n] and set [PnP] or [nPn]�
7.2.12 Setting of the standard unit of measurement for temperature
►
Select [Uni] and set the unit of measurement:
[°C] or [°F]�
7.2.13 Read error number
With the user interface of the program ifm Container:
►
Read [Fnr]�
7.2.14 Reset all parameters to factory setting
►
Select [rES]�
►
Execute the command [Reset to factory setting]
We recommend making note of your own settings in the table before carry-
ing out a reset (→ 12 Factory setting).
7.2.15 Settings for communication operation
For communication mode, no parameter setting is necessary� Using pin 4 (data
channel), data can be read in and out at any time�