17
UK
9.4.6 Setting the damping of the measured values for volumetric flow
► Select [dAP] and the damping constant in seconds (t value 63 %)�
9.4.7 Setting the error behaviour of OUT1 / OUT2
► Select [FOU1] and determine the value:
-[On] = the analogue signal goes to the upper end stop value�
-[OFF] = the analogue signal goes to the lower end stop value�
► Select [FOU2] and determine the value:
-[On] = the analogue signal goes to the upper end stop value�
-[OFF] = the analogue signal goes to the lower end stop value�
9.4.8 Selection of the medium to be monitored
► Select [MEDI] and determine the required medium:
-[H2O] = Water�
-[GLYC] = Glycol solutions�
-[OIL] = Oils��
9.5 Service-Funktionen
9.5.1 Reading the min./max. values for volumetric flow
► Select [HI�F] or [LO�F] and press [Set] briefly�
[HI�F] = maximum value, [LO�F] = minimum value�
Delete memory:
► Select [HI�F] or [LO�F]�
► Press [Set] and keep it pressed until [----] is displayed�
► Press [Mode/Enter] briefly�
It makes sense to delete the memories as soon as the unit works under
normal operating conditions for the first time�
9.5.2 Reading the min./max. values for temperature
► Select [HI�T] or [LO�T] and press [Set] briefly�
[HI�T] = maximum value, [LO�T] = minimum value�
Speicher löschen:
► Select [HI�T] or [LO�T]�
► Press [Set] and keep it pressed until [----] is displayed�
► Press [Mode/Enter] briefly�
It makes sense to delete the memories as soon as the unit works under
normal operating conditions for the first time�