22

9.3.2  Settings for quantity monitoring using the preset meter 

 

Select [OU1] and set [ImP]�

 

Select [ImPS] and set the volumetric flow quantity at which output 1 

switches (→ 9.7).

 

Select [ImPR] and set [no]: pulse repetition is not active� The output 

switches ON if the value set in [ImPS] is reached� It remains switched 

until the meter is reset�

9.3.3  Settings for meter reset controlled by the program

 

Select [rTO] and continue with a) or b)�

a) Reset the meter manually: press [Set] until [rES�T] is displayed� 

Press [Mode/Enter] briefly�

b) Enter the value for time-controlled reset: Press [Set] until the re-

quested value is displayed (intervals from 1 hour to 8 weeks)�

 

Press [Mode/Enter] briefly�

9.3.4  Switch off the meter reset

 

Select [rTO] and set [OFF]� The meter is only reset after overflow  

(= factory setting)�

9.3.5  Settings for meter reset by an external signal 

 

Select [OU2] and then [InD]�

 

Select [Din2] and set the reset signal: 

 -[Hi] = reset for high signal, 

 -[Lo] = reset for low signal, 

 -[+EDG] = reset for rising edge, 

 -[-EDG] = reset for falling edge�

9.4  Settings for temperature monitoring
9.4.1  Settings for limit value monitoring with OUT2

 

Select [SEL2] and set [TEMP]�

 

Select [OU2] and set the switching function: 

 -[Hno] = hysteresis function/normally open,  

 -[Hnc] = hysteresis function/normally closed,  

 -[Fno] = window function/normally open,  

 -[Fnc] = window function/normally closed�

 

Select [SP2] and set the value at which the output switches�

 

Select [rP2] and set the value at which the output switches back�

Summary of Contents for efector 300 SM0505

Page 1: ...Operating instructions Magnetic inductive flow sensor SM0505 704976 00 04 2011 UK...

Page 2: ...emperature monitoring analogue function 8 4 8 Start up delay dSt 10 5 Installation 11 5 1 Installation location 11 5 2 Installation in pipes 14 5 3 Protection against high medium temperatures 14 6 Ele...

Page 3: ...uration of the standard display 23 9 5 3 Activate deactivate empty pipe detection 23 9 5 4 Setting the output logic 23 9 5 5 Setting the start up delay 23 9 5 6 Setting the damping of the measured val...

Page 4: ...Ensure that the product is suitable for your application without any restrictions Improper or non intended use may lead to malfunctions of the unit or to unwanted effects in your application That is...

Page 5: ...al for volumetric flow limit value 9 2 2 or switching signal for temperature limit value 9 4 1 or analogue signal for volumetric flow 9 2 3 or analogue signal for temperature 9 4 2 OUT2 pin 2 cannot o...

Page 6: ...n meter subtracts Counting pulses are only provided as the sum increases After subtraction consumded quantity decreases pulses are not provided again before the consumded quantity has exceeded the for...

Page 7: ...rTO OFF If the quantity x is reached output 1 switches and remains switched until the meter is reset 4 4 Monitoring of temperatures A switching signal for temperature limit values can be provided on o...

Page 8: ...the distance between SPx and rPx SPx maximum value rPx minimum value 1 2 HY hysteresis FE window examples for volumetric flow monitoring When set to the window function the set and reset points have...

Page 9: ...between 0 and 10 V It is also indicated Volumetric flow above the measuring range output signal 10 V Current output 4 20 mA example volumetric flow monitoring Factory setting Measuring range scaled ME...

Page 10: ...re 3 options The volumetric flow quantity increases quickly and reaches the switch point good range within dSt outputs remain active The volumetric flow quantity increases slowly and does not reach th...

Page 11: ...ches again 0 5 of VMR dSt starts output becomes active 7 dSt elapsed Q has not reached good range output is reset 8 Q reaches good range output becomes active 5 Installation 5 1 Installation location...

Page 12: ...g pipe F flow direction Avoid the following installation locations Directly in front of a falling pipe In a falling pipe F flow direction At the highest point of the pipe system Directly in front of t...

Page 13: ...the pipe system The pipes are always completely filled On the suction side of a pump F flow direction If installed in an ungrounded pipe system e g plastic pipes the unit must be grounded Ground brac...

Page 14: ...hten the two adapters in opposite direction tightening torque 30 Nm After installation air bubbles in the system can affect the measurement Help Rinse the system after installation for ventilation rin...

Page 15: ...Pin1 Ub Pin3 Ub Pin4 OUT1 Switching signal limit values for volumetric flow Switching signal quantity meter reached preset value Pulses 1 pulse every time the defined volumetric flow is reached Pin2 O...

Page 16: ...ty before the last reset in 103 cubic metres LED 5 current medium temperature in C LED 7 LED 8 switching state of the corresponding output 9 Alphanumeric display 4 digits Indication of the current vol...

Page 17: ...M S M S M S M S M S M S M S M S M S M S M S M M S M M S S S M M M S M S M M S M M M M M S M S M M S M M S M S M M l min S m3 h S l S S C S 15s 15s 15s 15s M m3 l m3 Mode Enter Set l or m3 current mete...

Page 18: ...ow or temperature AEP Analogue end value for volumetric flow or temperature DIn2 Configuration of the input pin 2 for meter reset EF Extended functions opening of menu level 2 HI Maximum value memory...

Page 19: ...eter flashes for 5 s After 5 s The setting value is changed incremental by press ing briefly or scrolling by holding pressed Numerical values are incremented continuously If the value is to be reduce...

Page 20: ...ode Enter Set for 10 s Loc is displayed During operation Loc is briefly displayed if you try to change parameter values Press Mode Enter Set for 10 s uLoc is displayed When delivered unlocked Time out...

Page 21: ...unction normally closed Select SP2 and set the value at which the output switches Select rP2 and set the value at which the output switches back 9 2 3 Scaling of the analogue value for volumetric flow...

Page 22: ...als from 1 hour to 8 weeks Press Mode Enter briefly 9 3 4 Switch off the meter reset Select rTO and set OFF The meter is only reset after overflow factory setting 9 3 5 Settings for meter reset by an...

Page 23: ...onfiguration of the standard display Select SELd and determine the standard process category FLOW display shows the current volumetric flow value in the stand ard unit of measurement TOTL display indi...

Page 24: ...ut 2 switches irrespective of the error as defined with the parameters The analogue signal corresponds to the measured value 9 6 Service functions 9 6 1 Reading the min max values for volumetric flow...

Page 25: ...3 2 Press Mode Enter until ImPS is displayed Press Set and keep it pressed The current numerical value flashes for 5 s then one of the 4 digits becomes active digit flashes can be changed Set the req...

Page 26: ...the right flashes becomes active 8 1 2 3 no pushbutton pressed after 3 s 8 1 2 3 after 3 s 8 1 2 3 after 3 s 8 1 2 3 If the fourth digit flashes unchanged for 3 s digit 1 becomes ac tive again if the...

Page 27: ...another 15 s the parameter is displayed again then the unit returns to the Run mode 10 2 Changing the display unit in the Run mode Press Set briefly in the Run mode Press the pushbutton to move to the...

Page 28: ...medium temperatures over 50 C some parts of the housing can heat up to over 65 C In this case do not touch the unit Protect the housing against contact with flammable substances and uninten tional con...

Page 29: ...ble Max load current output 500 Min load for voltage output k 2 Pulse value 0 01 l 100 000 m Pulse length s min 0 0025 max 2 Power on delay time s 5 Flow monitoring Measuring range l min m h 0 2 100 0...

Page 30: ...20 DIN IEC 68 2 27 11ms Vibration resistance g 5 DIN IEC 68 2 6 55 2000 Hz EMC IEC 1000 4 2 ESD 4 8 KV IEC 1000 4 3 HF radiated 10 V m IEC 1000 4 4 Burst 2 KV IEC 1000 4 5 Surge 0 5 1 KV IEC 1000 4 6...

Page 31: ...PS 0 1 ImPR YES OU1 Hno OU2 I SP2 FLOW 40 00 rP2 FLOW 39 50 SP2 TEMP 20 0 rP2 TEMP 19 6 ASP FLOW 0 0 AEP FLOW 100 0 ASP TEMP 20 0 AEP TEMP 80 0 DIn2 EDG FOU1 OFF FOU2 OFF dSt 0 P n PnP dAP 0 6 rTo OFF...