Short-circuit and overload protection of the sensor supply
●
Protection rating IP 65/67
14 Technical data
General data
Housing material
Pocan
Weight [kg]
0�48
Ambient temperature (operation) [°C]
-25 ���60
Ambient temperature (storage/transport) [°C]
-25���85
Permissible humidity (operation) [%]
5���95
Air pressure (operation) [kPa]
70���106 kPa (up to 3000 m above
sea level)
Air pressure (storage/transport) [kPa]
70���106 kPa (up to 3000 m above
sea level)
Protection rating
IP 65 / IP 67
Protection class
III, IEC 61140, EN 61140, VDE
0140-1
Connection data
Connection type
M12 connector
Profibus DP interface
Number
2
Connection type
M12 connectors, B-coded
Designation connection point
copper cable
Number of poles
5
Transmission speed
9�6 Kbits/s���12 Mbits/s (automatic
baud rate detection)
Transmission physics
Profibus DP-compliant copper
cable
Profibus DP
Equipment type
Profibus slave
Profibus protocols
DP V1
Supply of the module electronics and sensors
Connection type
M12 connector (T-coded)
Number of poles
4
Designation
U
S
Supply voltage [V]
24 DC
Nominal supply voltage range [V]
18���31�2 V DC (including all tole-
rances, including ripple)
Typical current consumption [mA]
170 mA ±15 % (at 24 V DC)