9

UK

Display

Description

Type

Instructions

4 no  

connection

No IO-Link 

connection between 

the master and the 

device was found

Error

• If the device is only connected 

to a power supply, this status is 

normal.

• If parameter IO-Link = OFF:

 

► Check the cable connections 

and the function of the connec-

ted IO-Link participants 

 

► If necessary, re-establish the 

communication

5 invalid 

Invalid flag of the 

process data (PDV) 

is set. Indicated in the 

process value line

Error

The process value of the connec-

ted device is marked as invalid.

 

► Check the connected device. 

6 unsupported 

device of 

vendor <xxx>

No process data 

description for the 

device available.

Error

The connected device is not in the 

device catalogue.

unknown ifm 

device try 

catalogue 

update

Device catalogue no longer up to 

date.

 

► Device catalogue update: De-

vice catalogue download for ifm 

devices at www.ifm.com.

7 invalid 

process data 

description

The process data 

description does not 

match the communi-

cation content.

Error

Process data recognition error.

 

► Restart the communication with 

the connected device, e.g. by 

disconnecting and reconnecting 

the device.

Summary of Contents for E30430

Page 1: ...Operating instructions IO Link INLINE DISPLAY 1 44 E30430 80235800 00 02 2017 UK ...

Page 2: ...vice life The product must be suitable for the corresponding applications and environ mental conditions without any restrictions Only use the product for its intended purpose 2 Functions and features If the operating instructions or the technical data are not adhered to personal injury and or damage to property may occur The manufacturer assumes no liability or warranty for any consequences cau se...

Page 3: ...or indicating process values and the corres ponding information from a connected IO Link sensor The parameters of the connected sensor cannot be set via the INLINE DISPLAY 3 1 2 Example of a system integration 1 IO Link sensor 2 IO Link INLINE DISPLAY 3 IO Link master ...

Page 4: ...5 Electrical connection The camera must be connected by a qualified electrician The national and international regulations for the installation of electrical equipment must be adhered to Voltage supply according to EN 50178 SELV PELV Disconnect power Connect the unit as follows 4 3 2 1 BK black BN brown BU blue WH white BN WH BK BU 4 1 3 2 OUT2 L L OUT1 Colours to DIN EN 60947 5 2 Pin 1 L Pin 3 L ...

Page 5: ...ay Indication of current process values Indication of the parameters and parameter values 4 Buttons up and down Select parameters Change parameter values hold button pressed Switch between process value display and status display in the normal operating mode RUN mode Locking Unlocking buttons pressed simultaneously 10 seconds 5 Button Enter Change from the RUN mode to the main menu Change to the s...

Page 6: ...PLAY with the computer using the USB IO Link master E30390 Activate the device mode in the device menu Open LR DEVICE and transfer the current version of the Catalogue update IODD to the device Depending on the size the update of the display may take several minutes Usual ly the update takes about 1 minute 8 Menu Process value display RUN mode EF IO L DIS_ rES Info DIS diS S diS B diS U diS R PDis...

Page 7: ... that can be displayed Explanation extended functions EF rES Restore factory settings Info Device information IO L IO Link communication ON OFF OFF normal operation as passive display ON parameter setting or update of the device catalogue via the IODD tool e g LR DEVICE www ifm com When the device is started this point is reset to OFF DIS Opening of the lower menu level Explanation display setting...

Page 8: ...usly until the RUN mode is reached 10 Troubleshooting Display Description Type Instructions 1 ERROR Faulty units malfunction Error Replace device 2 off Supply voltage too low Error Assure a voltage supply with a sufficiently available current 18 30 V DC 3 PARA Parameter setting outside the valid range Error 1 Save the parameter settings 2 Restore the factory settings 3 Enter parameters again PARA ...

Page 9: ... Error The process value of the connec ted device is marked as invalid Check the connected device 6 unsupported device of vendor xxx No process data description for the device available Error The connected device is not in the device catalogue unknown ifm device try catalogue update Device catalogue no longer up to date Device catalogue update De vice catalogue download for ifm devices at www ifm ...

Page 10: ...rameter setting via IO Link communicati on is active Warning Wait until the parameter setting via the remote participant is finished 10 S Loc Setting buttons locked via parameter software Parameter change rejected Warning Unlock the setting buttons via the parameter setting software 11 no process data available No process data is available Warning The device is in the pre operate mode Wait until t...

Reviews: