8 Programming
WARNING
If programming takes place during operation, dangerous contact voltage may
occur� Therefore ensure that programming is done by a qualified electrician�
Parameter changes during operation, especially changes to the switching
function and the switch points can lead to malfunction in the plant�
Therefore disconnect it during the change and then check the function�
Programming consists of 6 steps:
1� Change from the RUN mode to the parameter range 1 or 2 or 3 [Enter/►]
2� Selection of the requested parameter (FOx, SOx, NCx, etc�)
[▲] / [▼]
3� Change to the PRG mode
[Enter/►]
4� Setting or changing the parameter value
[▲] / [▼]
5� Acknowledgement of the set parameter value
[Enter/►] > 3 s
6� Return to the RUN mode
[Enter/►] > 3 s
8.1 Programming example DT1 (Delay Time, output 1)
Operation
Display
Change from the RUN mode to the parameter range (here 1)
► Briefly press [Enter/►] once.
> The 1st parameter range is displayed�
CH1
RUN
0.0
DT1
CH1
RUN
15.0
DT1
CH1
RUN
1665
RPM
CH1
RUN
1
CH1
RUN PRG
0.0
DT1
CH1
RUN PRG
15.0
DT1
Selection of the requested parameter (here DT1)
► Press the [▼] button until the parameter DT1 is displayed with
the currently set value (here default value 0�0)�
CH1
RUN
0.0
DT1
CH1
RUN
15.0
DT1
CH1
RUN
1665
RPM
CH1
RUN
1
CH1
RUN PRG
0.0
DT1
CH1
RUN PRG
15.0
DT1
Change to the PRG mode
► Briefly press [Enter/►] once.
> The unit is in the adjustment mode�
> PRG indicator visible, parameter abbreviation flashes�