![IFM Electronic CR0401 Installation Instructions Manual Download Page 12](http://html1.mh-extra.com/html/ifm-electronic/cr0401/cr0401_installation-instructions-manual_3896226012.webp)
BasicController / BasicController
plus
12
5 Electrical connection
5.1 General electrical connection
The supply cables, CAN interfaces and input/outputs are connected via 6�3 x 0�8
mm blade male terminals on the front of the device�
Wiring (→ 8 Technical data)
A
B
C
D
E
F
N2
P/N1
1: Inputs
2: Outputs
3: Supply and CAN interfaces
Connector area (here e�g� CR0403)
Connector Connection
CR0401
CR0403
CR0411
Number of
poles
A
Inputs
IN0���3
IN0���3
IN0���3
8
B
IN4���7
IN4���7
IN4���7
C
IN8���11
IN8���11
–
D
Outputs
–
OUT0���3
OUT0���3
E
OUT0���3
OUT4���7
OUT4���7
F
OUT4���7
OUT8���11
–
P/N1
CAN interface 1 and supply
6
N2
CAN interface 2 (e�g� for BasicDisplay CR0451 or CR0452)
4
– = not connected
NOTE
Wrong connection may cause damage to the device�
► Observe the safety instructions (→ 2.3 Electrical connection).
► Basically all supply and signal cables must be laid separately�
► Lay supply and signal cables away from the device using the shortest possible
route�
► All connected cables must be provided with a strain relief at least 100 mm
behind the cable entry�
► Protect unused terminals with unpopulated sockets if no cover is used�