device manual AS-i DP - Gateway
6 Reference
6.1 Display messages
In the AS-i DP Gateway display error messages are displayed in two different ways:
1. AS-i
system
error:
The messages are displayed instead of the start image. There is no interruption in the menu
handling, a flashing exclamation mark is displayed in the middle of the bottom line in the
display instead (only if the configuration mode has been disabled)
2. Handling and internal system errors:
The message superposes the menu representation and must be confirmed by pressing the
right button.
6.1.1 AS-i system error (code E10 ...
E30 )
E10
slave profile incorrect
The slave was detected in the system but not activated by the master.
-> The cause is that the slave profile does not correspond with the projected one and that the master is in the
“Protected Mode”.
N.B.:
In the slave Info menu the projected and the detected slave profile can be checked.
E11
slave not present
The slave was found in the projection but it was not detected on the AS-i line.
LPS not identical with LDS.
E12
slave not projected
The slave was found on the AS-i line but not in the projection.
LDS not identical with LPS.
E13
Periphery fault detected
The master recognises that there is a periphery fault on at least one slave.
E14
Safety slave alert
>> error message not activated at present <<
E15
Analog protocol failure
>> error message not activated at present <<
E20
ASI Power Fail
The master is in the “Protected Mode” and detects that the AS-i voltage supply is not greater than 28 V.
This
message is only generated if at least one slave is projected, i.e. the LPS has to be unequal to 0.
E21
No slave detected
The master is in the “Projected Mode” and detects that no slave is connected to the AS-i line.
This message is
only generated if at least one slave is projected, i.e. the LPS has to be unequal to 0.