SmartPLC SafeLine AC4S with fieldbus interfaces
77
>
8.3.2
Safe AS-i slaves: Provide diagnostic information
43082
To control the provision of the internal diagnostic information of a logical device the following function
blocks are available:
Function block
Description
Reference
CtrlASi_InSlave
Provide diagnostic information of a safe AS-i input slave
→
CtrlASi_InSlave
(
CtrlASi_OutSlave
Provide diagnostic information of an AS-i control slave for
safe outputs
→
CtrlASi_OutSlave
(
→ S.
The safe AS-i slave that is to be controlled by means of the FB must be inserted in the device
tree.
>
8.3.3
Safe AS-i slaves: Transmit help signals HSI_1 and HSI_2 to safe AS-i
output modules
43086
To transmit help signals HSI_1 und HSI_2 to the logical device of a safe AS-i control slave the
following function block is available:
Function block
Description
Reference
CtrlASi_OutSlave
Transmit help signals HS1 and HS2 to AS-i control slave
for safe outputs
→
CtrlASi_OutSlave
(
→ S.
The safe AS-i control slave that is to be controlled by means of the FB must be inserted in the
device tree.
A transmission of the two help signals HSI_1 and HSI_2 once started cannot be interrupted.
Remarks about the status of the signal transmission are provided at the FB output
DiagCode
.
>
8.3.4
Local I/O interface: Reset logical device
43103
To reset a logical device of a safe sensor at the local I/O interface from the locked error state the
following function block is available:
Function block
Description
Reference
CtrlLocalInputs
Reset 2-channel peripheral at the local I/O interface that
is in the locked error state.
→
CtrlLocalInputs
(
→ S.
The safe device that is to be controlled by means of the FB must be inserted in the device
tree.
>