iFLOW HVAC INC.
www.iflowhvac.com
15
Display
Description
Explanation
EXAMPLE OF LAST 10 ERROR CODES
Parameter Settings Mode
How to Parameters settings:
Push the mode button until the screen reads
03 SEt
. Press enter
to confirm the Parameters mode. The screen will show the first
parameter 01. Use the up and down buttons to choose which
parameter to be changed from number 01‐28 and press enter. The
3 characters on the righthand side will indicate the value. Use the
up and down buttons to change the range of the value and press
venter to confirm and mode to exit.
Error Mode
How to access Error codes:
Push the mode button until the screen reads
02 Err
. Press enter to
confirm the Error code mode. Use the up and down buttons to see
the last 10 errors which will be numbered 01 to 10, with 01 being
the most recent. The 3 numbers on the righthand side will indicate
which error code is present. If more than 10 errors occur, the oldest
error will be deleted from the memory.
Item
Display
Range
Default
Fan Min. Speed (Heat)
5 - 40
30
Fan Max. Speed (Heat)
40 -100
60
Pump Min. Speed (Heat)
40 - 60
45
Pump Max. Speed (Heat)
60 - 100
70
Blower Motor Speed
@ G Mode
5 - 30
10
Y1 Blower Motor Speed
20 - 65
55
Determines the Y1 cooling mode of the blower motor operation after
a call for cool occurs.
Y2 Blower Motor Speed
65 - 90
80
Determines the Y2 cooling mode of the blower motor operation after
a call for cool occurs.
Lowest Outdoor
Temperature
0˚F - 32˚F
5˚F
Min. HeatLoss
6 - 30 KBTU/h
20K
Max. HeatLoss
15 - 100
KBTU/h
60/70/90
Determines the desired maximum BTUH output that is required.