Advanced Setup Table
31
FD = Factory Default Setting
Step# Description
Pg# Range
FD
TO ENTER MENUS ..... BUTTON PRESS
Setup Steps ................. MODE & OVERRIDE for 5 sec.
Time Schedule ............ MODE & UP for 2 seconds
Emergency Heat ......... UP & OVERRIDE for 2 seconds
TO ENTER MENUS .....BUTTON PRESS
Lockout Buttons ..........MODE, UP & DOWN for 2 sec.
Calibration ....................MODE & DOWN for 2 sec., then MODE
Wireless Setup ...........OVERRIDE for 5 Seconds
1
CLOCK
12A - 12A
12P
2
WEEKDAY
Monday - Sunday
Monday
3
SHOW CLOCK
On, Off
On
4
PROG
On, Off
On
5
BACKLIGHT
On, Off
Off
6
NIGHTLT
On, Off
Off
7
NIGHTLT START
12A - 12A
8:00P
8
NIGHTLT STOP
12A - 12A
6:00A
9
NUMBER OF WATER PIPES
4 PIPE, 2 PIPE
4 PIPE
10
2 PIPE SUBMODE (only if prior step = 2)
Heat Only, Cool Only
Auto Change
Auto Change, Total Elec
Auto Change, Aux Heat
Auto Change
11
1ST STAGE DEADBAND
1 - 6 degrees
2
12
MINIMUM HEAT/COOL SPREAD
0 - 6 degrees
2
(unless 2 pipe single mode)
13
SETPOINT LIMITS
On, Off
Off
14
MAX HEAT SETPOINT
35 - 99 degrees
82
15
MIN COOL SETPOINT
35 - 99 degrees
66
16
MAX OVRRIDE TIME IN HOURS
0 - 4 hrs
4
17
DISPLAY F/C
F, C
F
18
CONTINUOUS FAN, ON (low) or OFF (auto)
On, Off
Off
19
CARRIER FAN TYPE, ON (carrier) or OFF
On, Off
Off
20
WIRED SENSOR TYPE
control, monitor
control
21
CONTROL TO TEMP SOURCE
thermostat, sensor
thermostat
22
PRE-OCC FAN PURGE TIME
off - 3 hrs
off
23
HOT WATER VALVE TYPE
n.o / n.c.
n.c.
24
CHILLED WATER VALVE TYPE
n.o / n.c.
n.c.
25
DRY CONTACT POLARTY
n.o / n.c.
n.c.
26
DRY CONTACT USE
occupied, condensate,
condensate
fdd, holiday
27
SKYPORT
On, Off
On
28
API
On, Off
Off
29
TIME API
On, Off
Off