134
Figure 105. Configuration Mode MENU Screen
D.
Exit Configuration Mode as follows.
At top center of screen, touch home icon. DEVICE SELECT screen is displayed.
At top right of screen, touch Retrieve BAM button.
At top center of screen, touch Menu icon. Configuration Mode MENU Screen is dis-
played.
At bottom right of screen, touch More … button. Configuration Mode More Settings
screen is displayed.
Figure 106. Configuration Mode More Settings Screen
Touch Save List button. (If the button grays out, wait until it returns to normal again.)
Touch Reboot to GUI button.
E.
Wait for SAM Control center to reboot.
F.
Perform pressure sensor calibration. See section 5.2, Akron Brass Swing-Out™
Valve Calibrations (page 173).
G.
If SAM system is equipped with optional flowmeters, perform flowmeter calibra-
tion. See section 5.3, Flowmeter Calibration Procedures (page 178).