Safety Relays from IDEM           SCR-7 

H04 

Ver. A 

E61-329-00 

Note:  The items listed under “Electrical connection” must be observed during commissioning. 

Commissioning 
Procedure 

1. Wiring emergency stop circuit: 

Wire  the  emergency  stop  circuit  according  to  the  required 
Performance Level determined (see Fig. 1 to Fig. 5).  

2. Wiring start circuit: 

Wire the start circuit according to Fig. 6 or Fig. 7 to set the 
starting behavior. 

Warning: 

If  “Automatic  start”  is  set,  bear  in  mind  that  the  safety 
contacts  will  switch  immediately  after  the  power  supply  is 
connected.  If  “Monitored  manual  start”  is  set,  the  start 
button must be opened after wiring.  

3. Wiring feedback loop: 

If  your  application  provides  for  external  contactors  or  ex-
pansion modules, connect them to the device according to 
Fig. 8 or Fig. 9. 

4. Wiring power supply: 

Connect the power supply to terminals A1 and A2 (Fig. 10).   

Warning: Wiring only in de-energized state. 

5. Starting the device: 

 

Switch on the operating voltage.  

Warning: 

If  the  “Automatic  start”  starting  behavior  is  set,  the  safety 
contacts will close immediately. 

If the “Monitored manual start” starting behavior is set, close 
the start button to close the safety contacts. 

LEDs K1 and K2 are lit. 

6. Triggering safety function: 

Open  the  emergency  stop  circuit  by  actuating  the  connec-
ted safety switch. The safety contacts open immediately. 

7. Reactivation: 

Close  the  emergency  stop  circuit.  If  “Automatic  start”  is 
selected, the safety contacts will close immediately. 

If the “Monitored manual start” starting behavior is set, close 
the start button to close the safety contacts. 

Fig. 6: 

Monitored manual start. 
It is monitored that the start 
button was opened before the 
emergency stop button closes. 
(Prerequisite: operating voltage 
must not be interrupted.) 

Fig. 7: 

Automatic start. 
Max permitted delay during 
closing of the safety switches on 
S12 and S13: 

S12 before S13: 300 ms 

S13 before S12: any 

Warning: 
Safety contacts switch 
immediately when the 
power supply is connected. 

Depending on the application or the result of the risk assessment according to EN ISO 13849-1, the de-
vice must be wired as shown in Fig. 1 to Fig. 11.  

Applications 

Fig. 3: 

Single-channel emergency stop 
circuit with earth fault monitor-
ing. 

(category 1, up to PL c) 

Fig. 2: 

Two-channel emergency stop 
circuit with earth fault monitoring. 

(category 3, up to PL d) 

Fig. 1: 

Two-channel emergency stop 
circuit with short circuit and earth 
fault monitoring. 

(category 4, up to PL e) 

Fig. 4: 

Two-channel sliding guard 
monitoring with short circuit and 
earth fault monitoring. 

(category 4, up to PL e) 

Emergency Stop 
Circuit 

Starting Behavior 

Fig. 5: 

Two-channel emergency stop 
with pnp-outputs/OSSD-outputs 

with short circuit monitoring. 

(category 4, up to PL e) 

Fig. 8: 

Feedback loop for monitored manual 
start: 
The feedback loop monitors contactors 
or the expansion modules . 

Feedback Loop 

Fig. 9: 

Feedback loop for automatic start: 
The feedback loop monitors contac-
tors or the expansion modules . 

Power supply  

and  

Safety contacts 

Fig. 10: 

Power supply A1 and A2. 

 
(Power supply according to techn. 
Data ) 

Fig. 11: 

Connecting load to safety contacts. 

 

(Figure shows example.  
Voltage „+V“ according to techn. 
Data) 

Warning:  

In  order  to  activate  earth  fault  monitoring,  the  PE  must  be 
connected only to the power supply unit in accordance with 
EN60204-1. 

 

Corresponded to the application, the starting circuit have to 
be wired according to Fig. 6 or Fig. 7.

 