IDEM SAFETY SWITCHES SCR-2H User Information Download Page 3

User Information

  

Safety Relay s from IDEM           SCR-3 

Safety Relay s from IDEM           SCR-2H 

H02 

Ver. A 

E61-328-00 

Maintenance 

What to Do in  
Case of a Fault? 

Once  per  month,  the  device  must  be  checked  for  proper 
function  and  for  signs  of  tampering  and  bypassing  of  the 
safety  function  (to  do  this,  check  the  wiring  of  the  device 
and activate the emergency stop function. Check the delay 
time).

 

The  device  is  otherwise  maintenance 
free, provided that it was installed proper-
ly.

 

Note:

 

Additional data can be requested from the manufacturer for 
applications that deviate from these conditions. 

Safety  
Characteristics  
According to 
EN ISO 13849-1 

The device is certified according to EN ISO 13849-1 up to a 
Performance Level of PL e. 

Techn. Data 

Corresponds to the standards 

EN574, EN60204-1, EN ISO 13849-1, EN 62061 

Operating voltage 

 

AC 230 V, AC 115 V, AC/DC 24 V  

Rated supply frequency 

 

AC: 50-60 Hz 

Permissible deviation 

 

+/- 10 % 

Power consumption 

 

DC 24 V 

AC 230 V

 

 

 

approx.  1.5 W  approx. 3.7 VA 

Control voltage at S12-S12 and at S22-S23 

DC 24 V 

Control current  (both switches) 

approx. 2 x 40 mA 

Release time for the safety relays after release of a button  

< 20 ms 

Response delay after actuation of the buttons  

< 20 ms 

Syncronization time  

 

< 0.5 s 

Safety contact configuration    

2 NO contacts 

Max. switching voltage 

 

AC 250 V 

Safety contact breaking capacity  

AC:  

250 V, 2000 VA, 8 A for ohmic load 

(6 switching cycles/ min)

 

 

 

 

250 V, 3 A for AC-15 

 

 

DC:   24 V, 192 W, 8 A for ohmic load 

(6 switching cycles/ min)

   

 

 

 

24 V, 3 A for DC-13 

Max. total current through all contacts:  

12 A 

Minimum contact load  

 

24 V, 20 mA 

Min. Contact fuses 

 

10 A gG 

Max. line cross section 

 

0.14 - 2.5 mm

2

 

Max. length of control line 

 

1000 m with 0.75 mm

2

 

Contact material 

 

AgSNO

2

 

Contact service life 

 

mech. approx. 1 x 10

7

 

Test voltage 

 

2.5 kV (control voltage/contacts) 

Rated impulse withstand voltage, leakage path/air gap 

4 kV  (DIN VDE 0110-1) 

Rated insulation voltage 

 

250 V 

Degree of protection 

 

IP20 

Temperature range 

 

DC 24 V: 

-15 °C to +60 °C 

 

 

AC 230/115 V:  -15 °C to +40 °C 

Weight  

 

ca. 230 g  

Mounting 

 

DIN rail according to EN 60715 TH35 

Safety characteristics according to EN ISO 13849-1 for all variants of SCR-2H 

Load (DC-13; 24 V) 

<= 0.1 A 

<= 1 A 

<= 3 A 

T10d 

[years] 

20 

20 

20 

Category

 

PL 

PFHd 

[1/h] 

1.2E-08 

1.2E-08 

1.2E-08 

nop

 [cycle / year]  

<= 400,000 

<= 100,000 

<= 22,500 

What to Do in  
Case of a Fault? 

If  the  fault  still  exists,  perform  the  steps  listed  under 
“Commissioning Procedure”. 

If  these  steps  do  not  remedy  the  fault  either,  return  the 
device to the manufacturer for examination. 

Opening  the  device  is  impermissible  and  will  void  the 
warranty.  

Device does not switch on: 

• 

Check whether the 2-hand button of correct function. 

• 

Check whether the wiring. 

• 

Check the supply voltage on A1 and A2 

• 

Is the feedback loop closed? 

 

 

 

 

 