Maintenance
What to Do in
Case of a Fault?
Once per month, the device must be checked for proper
function and for signs of tampering and bypassing of the
safety function (to do this, check the wiring of the device
and activate the emergency stop function. Check the delay
time).
The device is otherwise maintenance
free, provided that it was installed proper-
ly.
Note:
Additional data can be requested from the manufacturer for
applications that deviate from these conditions.
Safety
Characteristics
According to
EN ISO 13849-1
The device is certified according to EN ISO 13849-1 up to a
Performance Level of PL e.
Techn. Data
Corresponds to the standards
EN574, EN60204-1, EN ISO 13849-1, EN 62061
Operating voltage
AC 230 V, AC 115 V, AC/DC 24 V
Rated supply frequency
AC: 50-60 Hz
Permissible deviation
+/- 10 %
Power consumption
DC 24 V
AC 230 V
approx. 1.5 W approx. 3.7 VA
Control voltage at S12-S12 and at S22-S23
DC 24 V
Control current (both switches)
approx. 2 x 40 mA
Release time for the safety relays after release of a button
< 20 ms
Response delay after actuation of the buttons
< 20 ms
Syncronization time
< 0.5 s
Safety contact configuration
2 NO contacts
Max. switching voltage
AC 250 V
Safety contact breaking capacity
AC:
250 V, 2000 VA, 8 A for ohmic load
(6 switching cycles/ min)
250 V, 3 A for AC-15
DC: 24 V, 192 W, 8 A for ohmic load
(6 switching cycles/ min)
24 V, 3 A for DC-13
Max. total current through all contacts:
12 A
Minimum contact load
24 V, 20 mA
Min. Contact fuses
10 A gG
Max. line cross section
0.14 - 2.5 mm
2
Max. length of control line
1000 m with 0.75 mm
2
Contact material
AgSNO
2
Contact service life
mech. approx. 1 x 10
7
Test voltage
2.5 kV (control voltage/contacts)
Rated impulse withstand voltage, leakage path/air gap
4 kV (DIN VDE 0110-1)
Rated insulation voltage
250 V
Degree of protection
IP20
Temperature range
DC 24 V:
-15 °C to +60 °C
AC 230/115 V: -15 °C to +40 °C
Weight
ca. 230 g
Mounting
DIN rail according to EN 60715 TH35
Safety characteristics according to EN ISO 13849-1 for all variants of SCR-2H
Load (DC-13; 24 V)
<= 0.1 A
<= 1 A
<= 3 A
T10d
[years]
20
20
20
Category
4
4
4
PL
e
e
e
PFHd
[1/h]
1.2E-08
1.2E-08
1.2E-08
nop
[cycle / year]
<= 400,000
<= 100,000
<= 22,500
What to Do in
Case of a Fault?
If the fault still exists, perform the steps listed under
“Commissioning Procedure”.
If these steps do not remedy the fault either, return the
device to the manufacturer for examination.
Opening the device is impermissible and will void the
warranty.
Device does not switch on:
•
Check whether the 2-hand button of correct function.
•
Check whether the wiring.
•
Check the supply voltage on A1 and A2
•
Is the feedback loop closed?