Remote I/O Communication Memory Refresh Image
Data communication between the remote I/O master and the remote I/O slaves is conducted as shown in the diagram below.
Connection Status with Remote I/O Slaves
The connections status of each remote I/O slave can be confirmed by referring to the special internal relays and special data
registers of the SmartAXIS configured as the remote I/O master.
Remote I/O
Slave 2
I0 to I35
Q0 to Q21
Analog inputs
D8040 to D8047
Remote I/O
Slave 3
I0 to I35
Q0 to Q21
Analog inputs
D8040 to D8047
I0 to I35
Q0 to Q21
Analog inputs
D8040 to D8047
Connection 1
I40 to I75
Q40 to Q61
Analog inputs
D8149 to D8156
Connection 2
I80 to I115
Q80 to Q101
Analog inputs
D8158 to D8165
Connection 3
I120 to I155
Q120 to Q141
Analog inputs
D8167 to D8174
I0 to I35
Q0 to Q21
Analog inputs
D8040 to D8047
Remote I/O
master
Remote I/O
slave 1
Item
Connection port
Device
Description
Connection status
Connection 1
M8110
Indicates the connection status with the
corresponding slave.
OFF: Not connected, ON: Connected
Connection 2
M8111
Connection 3
M8112
IP address of the connected
slave
Connection 1
D8110 to D8113
Stores the IP address of the slave.
Connection 2
D8114 to D8117
Connection 3
D8118 to D8121
Port number of the connected
slave
Connection 1
D8130
Stores the connected port number of the slave.
Connection 2
D8131
Connection 3
D8132
Summary of Contents for SmartAXIS FT9Z-1A01
Page 1: ...FT9Y B1378 7...
Page 10: ...TABLE OF CONTENTS Preface 9 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 212: ...7 DEVICE ADDRESSES 7 16 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 230: ...8 INSTRUCTIONS FUNCTION BLOCKS REFERENCE 8 18 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 344: ...13 SCRIPTS 13 36 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 386: ...APPENDIX Appendix 16 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 Japanese Font JIS X0201...
Page 393: ......