Frequency Measurement
This section describes frequency measurement, which measures the frequency of pulses input to an external input. Frequency
measurement is a function that measures the frequency of pulses input to an external input.
These input pulses are processed with dedicated hardware device in SmartAXIS, so frequencies can be measured with no relation
to the scan time. Groups that do not use frequency measurement can be used as normal inputs, high-speed counters, catch input,
and interrupt input. The measurement results are stored in special data registers and they are updated with each scan.
Function Specification
The SmartAXIS external inputs are used by switching between normal input, high-speed counters, catch input, interrupt input, and
frequency measurement. To use frequency measurement, specify the relevant group as
Frequency Measurement
in the
WindLDR
Function Area Settings
.
The frequency measurement results are stored in the following special data registers (Read-only):
Notes:
If the input pulse cycle is longer than the scan time, the measurement results are updated at pulse cycle + 1 scan time.
The data registers for the upper word and the lower word of the measurement value change according to the 32-bit data storage method
specified. For details, see "32-bit Data Storage Setting" on page 5-62.
Applicable Models
The AC power type does not support frequency measurement. In situations where the frequency measurement function is required, use the
DC power type.
Of the DC power types, only the the 24-, 40-, and 48-I/O types can use external inputs I6 and I7 for frequency measurement. The 12-I/O
type cannot use external inputs I6 and I7 as the frequency measurement function.
Group
1
2
3
4
5
6
External input
I0
I2
I3
I5
I6
I7
Frequency measurement
value (32 bits)
Upper word
D8050
D8056
D8062
D8068
D8134
D8140
Lower word
D8051
D8057
D8063
D8069
D8135
D8141
Frequency measurement range
1 Hz to 100 kHz
200 Hz to 100 kHz
Measurement error
Less than ±1%
(Truncated after the decimal point)
Calculation cycle
Each scan time
Summary of Contents for SmartAXIS FT9Z-1A01
Page 1: ...FT9Y B1378 7...
Page 10: ...TABLE OF CONTENTS Preface 9 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 212: ...7 DEVICE ADDRESSES 7 16 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 230: ...8 INSTRUCTIONS FUNCTION BLOCKS REFERENCE 8 18 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 344: ...13 SCRIPTS 13 36 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 386: ...APPENDIX Appendix 16 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 Japanese Font JIS X0201...
Page 393: ......