FT1A S
MART
A
XIS
U
SER
’
S
M
ANUAL
FT9Y-B1382
3-11
3: D
EVICE
A
DDRESSES
D8000 Quantity of Inputs
The total of input points provided on the CPU module is stored to D8000.
D8001 Quantity of Outputs
The total of output points provided on the CPU module is stored to D8001.
D8002 CPU Module Type Information
Information about the CPU module type is stored to D8002.
D8003 Memory Cartridge Information
When an optional memory cartridge is installed on the CPU module cartridge connector, information about the user program stored
on the memory cartridge is stored to D8003.
D8005 General Error Code
SmartAxis general error information is stored to D8005. When a general error occurs, the bit corresponding to the error occurred
turns on.
The general error and user program execution error can be cleared by writing “1” to the most significant bit of D8005 using a user
program.
For details on Pro/Lite general error codes, see Chapter 13 “Troubleshooting” in the FT1A Series Pro/Lite User's Manual. For details
on Touch general error codes, see Chapter ## “Troubleshooting” - “##.# Troubleshooting” in the FT1A Series Touch User's
Manual.
D8006 User Program Execution Error Code
SmartAxis user program execution error information is stored to D8006. When a user program execution error occurs, the error
code corresponding to the error occurred is stored to D8006.
For details on Pro/Lite user program execution error codes, see Chapter 13 “Troubleshooting” in the FT1A Series Pro/Lite User's
Manual. For details on Touch user program execution error codes, see Chapter ## “Troubleshooting” - “##.# Troubleshooting” in
the FT1A Series Touch User's Manual.
D8008-D8021 Calendar/Clock Data
D8008 through D8021 are used for reading calendar/clock data from the internal clock and for writing calendar/clock data to the
internal clock.
D8022-D8025 Scan Time Data
D8022 through D8025 are special data registers for checking the scan time and configuring the constant scan time.
For details on the SmartAxis Pro/Lite scan time, see Chapter 5 “Special Functions” – “Constant Scan Time” in the FT1A Series Pro/
Lite User's Manual. For details on the SmartAxis Touch scan time, see Chapter # “Project Settings” – “#.## Functions” – “Constant
Scan Time” in the FT1A Series Touch User's Manual.
D8026 Communication Mode Information (Port 2 and Port 3)
Communication mode information of port 2 and port 3 is stored to D8026.
0:
SmartAxis Pro/Lite 12-I/O type
1:
SmartAxis Pro/Lite 24-I/O type
2:
SmartAxis Pro/Lite 40-I/O type
3:
SmartAxis Pro/Lite 48-I/O type
4:
SmartAxis Touch
0:
SmartAxis Pro/Lite 12-I/O type
1:
SmartAxis Pro/Lite 24-I/O type
2:
SmartAxis Pro/Lite 40-I/O type
3:
SmartAxis Pro/Lite 48-I/O type
255:
The memory cartridge does not store any user program.
0:
Maintenance Communication
1:
User Communication
2:
Modbus RTU Master
3:
Modbus RTU Slave
Bit
0 0 0
0
Port 3
4
7
8
0
0
0
0
15
Bit
0
Port 2
D8026
Bit
Bit
Bit
Summary of Contents for microsmart pentra
Page 1: ...FT1A SERIES FC9Y B1382 Ladder Programming Manual ...
Page 6: ...Preface 5 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 104: ...7 DATA COMPARISON INSTRUCTIONS 7 10 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 122: ...8 BINARY ARITHMETIC INSTRUCTIONS 8 18 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 138: ...10 SHIFT ROTATE INSTRUCTIONS 10 12 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 162: ...11 DATA CONVERSION INSTRUCTIONS 11 24 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 188: ...12 CALENDAR COMPARISON INSTRUCTIONS 12 26 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 198: ...15 REFRESH INSTRUCTIONS 15 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 202: ...16 INTERRUPT CONTROL INSTRUCTIONS 16 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 266: ...20 DUAL TEACHING TIMER INSTRUCTIONS 20 4 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Page 318: ...25 USER COMMUNICATION INSTRUCTIONS 25 22 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...