HTOA (Hex to ASCII)
Applicable CPU Modules
Valid Devices
For the valid device address range, see pages 6-1 and 6-2
(Basic Vol.).
When T (timer) or C (counter) is used as S1 or S2, the timer/counter current value (TC or CC) is read out.
The quantity of digits to convert can be 1 through 4. Make sure that the quantity of digits designated by S2 is within the valid range. If the S2 data
is out of the valid range, a user program execution error will result, turning on special internal relay M8004 and the ERR LED on the CPU module.
When a user program execution error occurs, the execution of the instruction is canceled. The value of D1 is left unchanged and the next instruction
is executed. For user program execution errors, see Chapter 4 “User Program Execution Errors” on page 4-21.
Since the HTOA instruction is executed in each scan while input is on, a pulse input from a SOTU or SOTD instruction should be used as required.
Valid Data Types
S1
D1, D1+1, D1+2, D1+3
When input is on, the 16-bit binary data designated by S1 is read from the lowest digit
as many as the quantity of digits designated by S2, converted into ASCII data, and
stored to the destination starting with the device designated by D1.
The quantity of digits to convert can be 1 through 4.
HTOA(W)
S1
*****
S2
*****
D1
*****
FT1A-12
FT1A-24
FT1A-40
FT1A-48
FT1A-Touch
X
X
X
X
X
Device
Function
I
Q
M
R
T
C
D
Constant
Repeat
S1 (Source 1)
Binary data to convert
X
X
X
X
X
X
X
X
—
S2 (Source 2)
Quantity of digits to convert
X
X
X
X
X
X
X
1-4
—
D1 (Destination 1)
Destination to store conversion results
—
—
—
—
—
—
X
—
—
W (word)
X
When a bit device such as I (input), Q (output), M (internal relay), or R (shift register) is designated as the
source, 16 points (word data type) are used.
When a word device such as T (timer), C (counter), or D (data register) is designated as the source or
destination, 1 point (word data type) is used.
I (integer)
—
D (double word)
—
L (long)
—
F (float)
—
Summary of Contents for microsmart pentra
Page 1: ...FT1A SERIES FC9Y B1382 Ladder Programming Manual ...
Page 6: ...Preface 5 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 104: ...7 DATA COMPARISON INSTRUCTIONS 7 10 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 122: ...8 BINARY ARITHMETIC INSTRUCTIONS 8 18 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 138: ...10 SHIFT ROTATE INSTRUCTIONS 10 12 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 162: ...11 DATA CONVERSION INSTRUCTIONS 11 24 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 188: ...12 CALENDAR COMPARISON INSTRUCTIONS 12 26 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 198: ...15 REFRESH INSTRUCTIONS 15 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 202: ...16 INTERRUPT CONTROL INSTRUCTIONS 16 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 266: ...20 DUAL TEACHING TIMER INSTRUCTIONS 20 4 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Page 318: ...25 USER COMMUNICATION INSTRUCTIONS 25 22 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...