Compatibility table (FC4A/5A series -> FC6A Plus)
34
Special devices
The available special devices for replacing are shown in the table below..
Yes:
Compatible device that can be replaced automatically
Indirectly: Device that needs to be replaced manually
No:
Device that cannot be replaced
Special internal relay
Replaceability
Special
internal
relay
FC4A/5A series specifications
FC6A series specifications
Yes
M8000
Start Control
Same with FC4A/5A series.
Yes
M8001
1-s Clock Reset
Same with FC4A/5A series.
Yes
M8002
All Outputs OFF
Same with FC4A/5A series.
Yes
M8003
Carry (Cy) or Borrow (Bw)
Same with FC4A/5A series.
Yes
M8004
User Program Execution Error
Same with FC4A/5A series.
Yes
M8005
Communication Error
Same with FC4A/5A series.
Yes
M8006
Data Link Communication Prohibit Flag (Master Station)
Same with FC4A/5A series.
Yes
M8007
Data Link Communication Initialize Flag (Master Station)
Data Link Communication Stop Flag (Slave Station)
Same with FC4A/5A series.
Yes
M8010
Status LED
Same with FC4A/5A series.
No
M8011
HMI Write Prohibit Flag
It is not supported and cannot be used.
M8011 is defined as reserved.
No
M8012
HMI Operation Prohibit Flag
It is not supported and cannot be used.
M8012 is defined as reserved.
Yes
M8013
Calendar/Clock Data Write/Adjust Error Flag
Same with FC4A/5A series.
Yes
M8014
Calendar/Clock Data Read Error Flag
Same with FC4A/5A series.
No
M8015
Calendar/Clock Data Read Stop Flag
The CPU Module uses the built-in clock,
which cannot be stopped. M8015 is
defined as reserved.
Yes
M8016
Calendar Data Write Flag
Same with FC4A/5A series.
Yes
M8017
Clock Data Write Flag
Same with FC4A/5A series.
Yes
M8020
Calendar/Clock Data Write Flag
Same with FC4A/5A series.
Yes
M8021
Clock Data Adjust Flag
Same with FC4A/5A series.
Yes
M8022
User Communication Receive Instruction Cancel Flag
(Port 1)
Same with FC4A/5A series.
Yes
M8023
User Communication Receive Instruction Cancel Flag
(Port 2)
Same with FC4A/5A series.
Yes
M8024
BMOV/WSFT Executing Flag
Same with FC4A/5A series.
Yes
M8025
Maintain Outputs While CPU Stopped
Same with FC4A/5A series.
No
M8026
Expansion Data Register Data Writing Flag (Preset
Range 1)
Use the recipe function. M8026 is
defined as User Communication Receive
Instruction Cancel Flag (Port 3), and
M8027 as High-speed Counter (Group
1/10).
No
M8027
Expansion Data Register Data Writing Flag (Preset
Range 2)
Indirectly
M8030
High-speed Counter (X0-X2) Comparison Output Reset
There is no compatibility with the
high-speed counter.
Set and refer to the high-speed counter
(group 1/I0) near device allocation.
Indirectly
M8031
High-speed Counter (X0-X2) Gate Input
Indirectly
M8032
High-speed Counter (X0-X2) Reset Input/Preset Input
Indirectly
M8033
User Communication Receive Instruction Cancel Flag
(Port 3)
Use M8026.
Indirectly
M8034
High-speed Counter (X3) Comparison Output Reset
There is no compatibility with the
high-speed counter.
Set and refer to the high-speed counter
(group 3/I3) near device allocation.
Indirectly
M8035
High-speed Counter (X3) Gate Input
Indirectly
M8036
High-speed Counter (X3) Reset Input