Modbus RTU Slave Communication
Modbus slave communication can be configured by selecting Modbus RTU Slave for Port 1, Port 2 and Port 3 in the WindLDR
Function Area Settings
. When a Modbus RTU slave receives a request from the Modbus RTU master, the Modbus RTU slave
reads or writes data according to the request. The request is processed at the END processing of the user program.
Modbus RTU slaves do not reply to the Modbus RTU master for the broadcast requests.
Modbus RTU Slave Communication Specifications
*1 When timeout occurs, the FC6A Series MicroSmart discards the received data and waits for the first frame of the next valid communication.
*2 For communication at 19,200 bps or higher, the timeout between characters needs to be a minimum of 0.75 ms.
*3 For communication at 19,200 bps or higher, the timeout between frames needs to be a minimum of 1.75 ms.
Map of Slave Addresses for Modbus RTU Slaves
*1 Addresses generally used for Modbus communication. "Calculating Modbus Addresses for FC6A Series MicroSmart Devices" on page 6-9
shows
the method to calculate slave addresses from FC6A Series MicroSmart devices.
*2 These 4-digit addresses are used in the communication frame. To calculate the address used in communication frame, extract lower 5 digits of
the Modbus address, subtract 1 from the value, and convert the result into hexadecimal.
*3 Access within the device range for the FC6A Series MicroSmart type used.
Item
Description
Baud Rate (bps)
9,600, 19,200, 38,400, 57,600, 115,200
Data Bits
8 bits (fixed)
Stop bits
1, 2 bits
Parity
Odd, even, none
Slave Number
Constant
1 to 247
Data register
Set the special data register values between 1 and 247
Port 1: D8100
Port 2: D8102
Port 3: D8103
Timeout between Characters
1.5 characters minimum
Timeout between Frames
3.5 characters minimum
Modbus Device Name
Modbus Address
Map (Decimal)
Communication
Frame Address
FC6A Series MicroSmart Device
Applicable
Function Code
Coil
(000000 and above)
000001 - 000504
0000 - 01F7
Q0 - Q627
1, 5, 15
000701 - 000956
02BC - 03BB
R000 - R255
001001 - 003048
03E8 - 0BE7
M0000 - M2557
003049 - 007400
0BE8 - 1CE7
M2560 - M7997
009001 - 009256
2328 - 2427
M8000 - M8317
011001 - 017000
2AF8 - 4267
M10000 - M17497
Input Relay
(100000 and above)
100001 - 100504
0000 - 01F7
I0 - I627
2
101001 - 101256
03E8 - 04E7
T000 - T255 (timer contact)
101501 - 101756
05DC - 06DB
C000 - C255 (counter contact)
102001 - 102768
07D0 - 0ACF
T256 - T1023 (timer contact)
104001 - 104256
0FA0 - 109F
C256 - C511 (counter contact)
Input Register
(300000 and above)
300001 - 300256
0000 - 00FF
T000 - T255 (timer current value)
4
300501 - 300756
01F4 - 02F3
C000 - C255 (counter current value)
302001 - 302768
07D0 - 0ACF
T256 - T1023 (timer current value)
304001 - 304256
0AF0 - 10A0
C256 - C511 (counter current value)
Holding Register
(400000 and above)
400001 - 408000
0000 - 1F3F
D0000 - D7999
3,6,16
408001 - 408500
1F40 - 2133
D8000 - D8499
409001 - 409256
2328 - 2427
T000 - T255 (timer preset value)
3
409501 - 409756
251C - 261B
C000 - C255 (counter preset value)
410001 - 456000
2710 - DABF
D10000 - D55999
3,6,16
462001 - 462768
F230 - F52F
T256 - T1023 (timer preset value)
3
464001 - 464256
FA00 - FAFF
C256 - C511 (counter preset value)