4
Response SE -
User's
BOILER CONTROLS
Introduction
The
Response SE
is a wall mounted, room sealed, super
efficient condensing combination boiler, featuring full
sequence automatic spark ignition and fan assisted
combustion.
Due to the very high efficiency of the boiler, condensate is
produced from the flue gases and this is drained to a
suitable disposal point through the plastic waste pipe at
the left lower rear of the boiler. A condensate 'plume' will
also often be visible at the flue terminal.
The
Response SE
is a combination boiler providing both
central heating and instantaneous domestic hot water.
Gas safety (Installation & Use) Regulations 1994,
amendments 1996 or rules in force.
In your own interest, and that of safety, it is the law that this
boiler must be installed by a registered installer, in accordance
with all national and local regulations.
It is essential that the instructions in this
booklet are strictly followed, for safe and
economical operation of the boiler.
Electricity Supply
Connection must be made in a way that allows complete
isolation of the electrical supply such as a double pole
switch having a 3mm (1/8") contact separation in both
poles, or a plug and socket, serving only the boiler and
system controls. The means of isolation must be
accessible to the user after installation,
The fusing should be 3A.
Legend
A
Control door
B
Control panel
C
On/off switch
D
Central heating on/off switch
E
Central heating pressure gauge
IMPORTANT
•
THIS APPLIANCE MUST NOT BE OPERATED WITHOUT
THE CASING CORRECTLY FITTED.
•
If the boiler is installed in a compartment then the
compartment MUST NOT be used for storage purposes.
•
Clearances of 180mm above, 100mm below, 5mm at the
sides and 450mm at the front of the boiler casing must be
allowed for servicing.
•
If it is known or suspected that a fault exists on the boiler
then it MUST
NOT BE USED
until the fault has been
corrected by a registered installer.
To light the boiler
(see illustration below)
1.
Check that the electricity supply to the boiler is OFF.
2.
Open the controls access door .
3.
Set the on/off switch (C) and CH switch (D) to OFFand
ensure that all DHW taps are turned off.
4.
Switch ON the electricity supply to the boiler and check that
all external controls, e.g. programmer, room thermostat, etc.,
are ON.
If a programmer is fitted, refer to the separate instructions
provided.
5.
Set the on/off switch (C) to ON and CH switch (D) to the
desired position.
The boiler will first execute a self-check cycle then
commence the ignition sequence, first supplying heat to
preheat the domestic hot water and then to the central
heating, if required.
Summary of Contents for Response SE
Page 1: ......