13
Mexico Super 440 FF - 480 FF -
Installation
REAR FLUE OUTLET
INSTALLATION
15 LOCATING THE BOILER
A. If the flue assembly can be fitted from the outside,
proceed as follows:
1. Move the boiler into position ensuring that the flue
outlet is in line with the wall opening.
2. Insert the flue assembly ensuring that the flue slides
into the flue extension and the 3 sealing ring studs
locate into the boiler.
14 FITTING THE FLUE ASSEMBLY
A. Inside fitting.
If the flue assembly cannot be fitted from the outside, proceed as
follows:
1. Insert the flue assembly through the hole far enough to allow the
rubber seal to unfold completely and form an adequate seal on
the outside wall.
2. Ensure the notch is at the top. This will aid the location of the
studs into the boiler back panel.
3. Proceed to Frame 15, item B.
B. Outside fitting.
Proceed to Frame 15, item A.
1. Secure the flue to the boiler using the
three M5 wing nuts provided.
Note.
The sealing plate studs will locate in the
back panel one way only. This will ensure
that the terminal is correctly aligned.
16 CONNECTING THE FLUE TO THE BOILER
13 FITTING THE FOAM SEAL
1. To determine the position for the foam
seal measure the wall thickness and
mark it onto the flue, measuring from the
groove near the terminal.
2. Wrap the self-adhesive foam strip round
the flue, ensuring that the foam is on the
terminal side of the line. This seals the
gap between the flue and the wall.
B. If the flue assembly has been fitted from the inside
proceed as follows:
1. Move the boiler into position ensuring that the
flue slides into the flue extension tube and the 3
sealing ring studs locate into the boiler back panel.