background image

Exal

t

Venturi Replacement Kit

4

1. Touch simultaneously on the up and down soft

keys for 3 seconds to access the functions for the

installer. See Fig. 4.

Fig. 4:  CTRLMax Navigation Control 

2. Enter the installer access code “054” by using the

LEFT and RIGHT buttons to select a digit and the UP 

and DOWN buttons to change the digit.  Press the

CENTER button to enter the access code.

3. Press the RIGHT button to highlight the Manual

Operation icon then press the CENTER button.

Manual Operation

Released

Off

Off

Off

CH1

FAN

DHW

CH2

Manual Operation

Released

Off

Off

Off

CH1

FAN

DHW

CH2

Manual Operation

Released

Off

Off

Off

CH2

FAN

DHW

CH1

Manual Operation

Released

Off

Off

Off

DHW

FAN

CH1

CH2

Fig. 5:  CTRLMax Manual Operation

4. Press the CENTER button while the FAN icon is

highlighted to manually fire the burner and power 

the CH circulator. See Fig. 5

NOTICE

An adequate CH load must be present to dissipate the heat 

generated during the combustion test. If an adequate CH 

load is not available, an indirect water heater can be used to 

dissipate the heat by creating a DHW call which will enable 

the DHW circulator.

5. Press the RIGHT button to adjust the firing rate to

100% (high fire).  Hold down the  RIGHT button to 

rapidly increase the firing rate.

6. If the combustion levels during high fire are out-

side the recommended combustion settings (see

Table 1), adjust the THROTTLE SCREW (see Fig. 6)

using a flat-blade screwdriver as follows:

Counter-clockwise adjustment of the THROTTLE 
SCREW at High Fire (100% firing rate):

 O

2

 decreases and CO

 increases

Clockwise adjustment of the THROTTLE SCREW at 
High Fire (100% firing rate):

 O

2

  increases and CO

2

 decreases

7.

Once the combustion level is set at high fire, manu-

ally place the boiler into low fire mode by pressing

the LEFT button to adjust firing rate down to 1%

(low fire).

8.

If the combustion level (O

2

 or CO

2

) during low fire

is not are outside the recommended combustion

settings in Table 1 contact 

Ideal USA

 Technical

Support.

9.

Press the CENTER button while the fan icon is high-

lighted to shutdown the burner.

10.

 Press the LEFT or RIGHT button to highlight the

home screen icon to exit the service mode.

11.

 Replace the front panel and put the boiler back

into operation.