EZ Setup
DHW EZ Setup
Select DHW Demand
Thermostat
Sensor
DHW Storage Setpoint
140°F
68°F
168°F
DHW Priority Timeout
Off
Off
120 min.
EZ Setup Complete
DHW EZ setup is complete.
Additional changes can be made in
the Installer Menu if required.
Press OK to return to EZ Setup Menu
EZ Setup
DHW EZ Setup
Select DHW Demand
Thermostat
Sensor
DHW
Boiler Setpoint
168°F
96°F
188°F
58
CHAPTER
9
CHAPTER 9 - CTRLMAX OPERATION
9.8. Domestic Hot Water EZ Setup
- EXALT Solo Units
Select DHW Demand
prompts the installer to select how a DHW
Demand is generated.
When
Thermostat
is selected in Select DHW Demand, a domestic
hot water call from an aquastat or dry contact switch will enable the
EXALT with a fixed setpoint for a domestic hot water call. After Ther-
mostat is selected, the
DHW Boiler Setpoint
screen appears.
Default: Thermostat
DHW Boiler Setpoint
prompts to enter the fixed boiler setpoint
temperature during a domestic hot water call.
Touch the
or
soft keys to adjust the temperature setpoint
then touch
to store the setting. The
DHW Priority Timeout
screen then appears (see below).
Default: 168°F [75°C]
.
When
Sensor
is selected in Select DHW Demand, use of an (optional)
Indirect Water Heater Sensor is required. The EXALT monitors the DHW
storage temperature and generates a DHW call whenever the tem-
perature drops below the DHW storage setpoint by 6°F [3°C].
DHW Storage Setpoint
prompts to enter the DHW Storage Set-
point temperature.
Touch the
or
soft keys to adjust the temperature setpoint then
touch
to store the setting. The
DHW Priority Timeout
screen
then appears.
Default: 140°F [60°C]
.
The DHW Boiler Setpoint will automatically be set 28°F
[15°C] higher than the DHW Storage Setpoint setting
DHW Priority Timeout
prompts to enter an optional time limit that
a domestic hot water call has priority over central heating call.
Touch the
or
soft keys to adjust the timeout value, if required,
then touch
to store the setting and complete the DHW EZ Setup.
Defau
lt: Off
NOTICE
Domestic Hot Water EZ Setup allows the installer to quickly customize the Domestic Hot Water settings for the application
Summary of Contents for EXALT Solo 110
Page 2: ...INTENTIONALLY LEFT BLANK...
Page 16: ...INTENTIONALLY LEFT BLANK...
Page 24: ...INTENTIONALLY LEFT BLANK...
Page 48: ...INTENTIONALLY LEFT BLANK...
Page 56: ...INTENTIONALLY LEFT BLANK...
Page 78: ...INTENTIONALLY LEFT BLANK...
Page 88: ...INTENTIONALLY LEFT BLANK...
Page 92: ...INTENTIONALLY LEFT BLANK...
Page 94: ...INTENTIONALLY LEFT BLANK...
Page 112: ...INTENTIONALLY LEFT BLANK...
Page 125: ......
Page 126: ......
Page 127: ......