background image

          

 

        

 

 

       

SBS®

 

Connector

 

Assembly

 

Instruction

 

 

 

 

                                                   SBS

®

50                                                     SBS

®

75X                                     SBS

®

75G 

The following instructions are supplied as a reference. For installation by a qualified electrician in accordance with national and local 
electrical codes and the equipment manufacturer’s assembly instruction. The suitability of this type of termination must be evaluated by 
the Underwriter’s Laboratories, Inc. and Canadian Standard Association for the end use application. 

SBS

®

 crimp contacts are for use with stranded Copper (Cu) wire only. Crimp tools recommended by APP

®

 are required to achieve the 

designed performance of the connector. Use of solid wires, alternate conductor materials, or tools not recommended by Anderson can 
affect safety agency approvals of the connector and may produce unpredictable or health threatening results. 

Verify that you are using the appropriate power, ground and/or auxiliary contacts and recommended tooling from Tables A, B and C: 

 

Table A: Power Contacts Listed for Use with SBS

®

50, SBS

®

75X and SBS

®

75G Series 

Contact Part 
Number 

Wire Size 

Crimp Tool

1339G2 

#6 AWG - (16mm ²)

1309G4 hand tool 

or

1387G1 pneumatic tool + 1388G6 die + 1389G9 locator

1339G5 

#8 AWG - (10mm ²)

1309G4 hand tool 

or

1387G1 pneumatic tool + 1388G6 die + 1389G9 locator

1339G3 

#10 - 12 AWG - (2.5 - 6mm ²) 

1309G4 hand tool 

or

1387G1 pneumatic tool + 1388G7 die + 1389G9 locator

      

NOTE:

 

Use one of the following reducer bushings with contact # 1339G2 for smaller cable sizes. Electrical capability is derated with smaller wire sizes.  

 

 

 

 

Table B: Ground Contacts Listed for Use with SBS

®

75G Series 

 

Contact Part 
Number 

Wire Size 

Crimp Tool

1340G1 

#6AWG - (16mm ²) 

1309G4 hand tool or 1387G1 pneumatic tool + 1388G6 die + 1389G20 locator

1340G2 

#8AWG - (10mm ²) 

1309G4 hand tool or 1387G1 pneumatic tool + 1388G6 die + 1389G20 locator

1340G3 

#10 - 12 AWG - (2.5 - 6mm ²) 

1309G4 hand tool or 1387G1 pneumatic tool + 1388G7 die + 1389G20 locator

             

NOTE:

 

Use one of the following reducer bushings with contact #1340G1 for smaller cable sizes. Electrical capability is derated with smaller wire sizes.

  

 

 

 

 

 

Bushing 
Number 

Wire Size 

5912 

#8 AWG - (8.4mm ²) 

5910 

#12 - 10 AWG - (3.3 - 5.3mm ²) 

5913 

#16 - 14 AWG - (1.3 - 2.1mm ²) 

Bushing Number 

Wire Size 

5912 

#8 AWG - (8.4mm²) 

5910 

#12 - 10 AWG - (3.3 - 5.3mm²) 

5913 

#16 - 14 AWG - (1.3 - 2.1mm²) 

 

Reviews: