background image

2

6. Maintenance

-8-

   Battery Replacement :

(1) It is necessary to replace battery, when green

lamp is dull lit.

(2) Use a screwdriver to unscrew the screw on 

the back then open the case(Fig.2), remove
the battery and replace with new battery (type
006P, DC9V).

(3) Reinstall the case.

   Fuse Replacement :

(1) It is necessary to replace fuse, when lamp

indicator R or T show no connection, and
change R-S-T is the same.

(2) Use a screwdriver to unscrew the screws on

the back then open the case(Fig.2), remove 
the broken fuse and replace with new fuse
(200mA, 250V).

(3) Reinstall the case.

   Cleaning and Storage :

Periodically wipe the case with a damp cloth and 
detergent. Do not use abrasives or solvents.

WARNING

To avoid electrical shock or damage to the meter,

do not get water inside the case.

Summary of Contents for 61-521

Page 1: ...3 Phase Tester Motor Rotation Tester 61 521...

Page 2: ...L 2 OPEN PHASE INDICATOR 3 PHASE ROTATION INDICATOR 4 MOTOR TESTER POWER SWITCH 5 MOTOR TESTER POWER INDICATOR 6 MOTOR ROTATION INDICATOR 7 MOTOR ROTATION INPUT TERMINAL 2 3 PHASE TESTER MOTOR ROTATIO...

Page 3: ...Fig 2 Fig 1 61 521...

Page 4: ...rding to IEC Publication 348 Safety Requirements for Electronic Measuring Apparatus IEC 1010 En61010 and other safety standards Follow all warnings to ensure safe operation 1 Introduction 1 CAUTION RE...

Page 5: ...mental conditions 1 Indoor use 2 Installation Category lll 3 Pollution Degree 2 4 Altitude up to 2000 Meter 5 Relative Humidity 80 Max o 6 Ambient Temperature 0 40 C Observe the International Electric...

Page 6: ...rotation indication This model is ideal for installing conveyor lines pump systems and interconnected drivers Identifies 3 phase sequence and open phase check Battery operated Meets IEC 1010 EN61010 s...

Page 7: ...are on If so there is no open phase When any of the three lamps is not on there is open phase 4 Check the rotating direction of the rotation indicator 4 Measuring Methods 4 Open phase on terminal wher...

Page 8: ...input terminals by L1 L2 L3 and press the power button Fig1 The power indicator green lamp is lit If the clockwise or counter clockwise red indicator is lit before rotating the motor shaft it means v...

Page 9: ...r is lit it means there is a 3 phase motor connection to the power supply by L1 L2 L3 The 3 phase motor should be rotated clockwise 4 If you require the motor to rotate counter clockwise you should ch...

Page 10: ...ower Consumption Consumption current approx 14mA of motor rotation field of tester AC power consumption approx 7mA per phase rotation field of indicator Installation Category IEC 1010 600V Cat III Dim...

Page 11: ...ment 1 It is necessary to replace fuse when lamp indicator R or T show no connection and change R S T is the same 2 Use a screwdriver to unscrew the screws on the back then open the case Fig 2 remove...

Page 12: ...owing the purchase of the tester IDEAL INDUSTRIES INC will at its option replace or repair the defective unit subject to verification of the defect or malfunction Warranty limited solely to repair or...