General Specifications
LCD Display:
4000 count maximum reading
Bar Graph Display:
82 segment analog bar graph
Polarity Indication:
Automatic, negative indicated,
positive implied
Overrange Indication:
“OL” or “-OL”
Low Battery Indication:
“ ” when the battery
voltage drops below operating
voltage
Size (WxHxD):
88mm x 180mm x 33.5mm
(without holster)
94mm x 188mm x 40mm (with
holster)
Sampling:
2 times/sec LCD Display,
12 times/sec bar graph
Auto Power Off:
Approx. 30 min.
Operating Temperature:
0°C ~ 30°C (<80% RH),
30°C ~ 40°C (<75% RH),
40°C ~ 50°C (<45% RH)
Storage Temperature:
-20°C ~ 60°C (0~80% RH)
when battery removed from
meter
Temperature Coefficient:
0.15 x (specified accuracy) /
°C, <18°C or >28°C
Power Requirements:
9V NEDA 1604, 1EC bf 22,
J1S 006P
Battery Life:
300 hours (alkaline )
Installation Category:
IEC 1010, 1000V Cat. II,
600V Cat III
Environmental Conditions
Indoor Use
Maximum Altitude:
2000 Meter
Installation Category:
IEC 1010, 1000V Cat. II,
600V Cat. III
Pollution Degree:
2
17
Continuity Check
To Verify Continuity:
A continuity test ensures that all circuit connections are intact.
1. Plug the black test lead into the COM port and the red test
lead into the V
Ω
Hz port.
2. Set the rotary switch to the
Ω
position.
3. Press the blue button until is shown in the display.
4. Connect the test leads to the circuit to be measured. The
buzzer will sound if the resistance of the circuit measured is
lower than 30
Ω
.
Accessories
For AC Current Clamp (61-450):
1. Plug the black test lead into the COM port and the red test
lead into the V
Ω
Hz port.
2. Remove the probe tips from the end of the leads.
3. Attach the leads to the current clamp. (polarity will not effect
reading)
4. Set the rotary switch to the V position.
5. Push the blue button until
AC
is shown on the display.
6. Snap the jaw of the current clamp around one of the current
carrying conductors.
Hz
True RMS
Circuit Connection:
C
˜