13
3.5.12 Boiler Pump Operating Mode
The boiler pump can be controlled in one
for two ways.
Capacity control means that the pump speed
follows the burner capacity proportionally between
minimum capacity/minimum pump speed and
maximum capacity/maximum pump speed.
Temp. Diff. Control means that the pump
speed is controlled to maintain a fixed boiler
flow to return temperature differential.
Operating mode
Capacity control
Temp. Diff. Control
Operating mode
Capacity control
Temp. Diff. Control
3.5.13
Boiler Pump Overrun time
The boiler pump overrun time can be
adjusted if required.
Overrun
2minutes
Done
Overrun
2minutes
Done
3.5.14
Menu – Boiler – Flue offset
The flue offset parameter allows adjustment
of the boiler specific cascade flue setting.
The flue offset is an increase in the minimum
burner capacity to ensure that the cascade flue
pressure or an unpowered flue damper can
be overcome safely and avoid any risk of the
burner going out at the minimum boiler capacity.
When a multiline flue system is selected during
configuration this parameter is enabled, it has a
predetermined minimum already applied which
is required for the optional flue kit that can be
supplied for the boiler.
Flue offset
12%
Done
3.5.15
Menu – Boiler – Hours run
The hours run screen show the number of successful
burner starts and the number of full burner operating
hours for each boiler in the cascade:
Hours run
Boiler 1
Boiler 2
Hours run
Ignitions: 12
Burner: 2 hours
3.5.16
Menu – Boiler – Faults
The fault history, summary and detail, of each
boiler in the cascade can be interrogated,
this can also be reset:
Faults
Summary
Show detail
Reset
3.5.17
Menu – Boiler – Faults – Summary
On selecting which boiler you want to
interrogate, the system will read back the
fault summary and display:
Boiler 1
Fault 09 : Count 14
Fault 10 : Count 11
Fault 51 : Count 5
The list can be scrolled and any fault selected
will then show the specific fault description:
Fault 09
Outside thermistor defect
(open/short)
3.5.18
Menu – Boiler – Faults – Show
detail
On selecting which boiler you want to
interrogate, the system will then read back
the fault detail and display:
Boiler 1
09/09/2019, 09:13 Fault 07
09/09/2019, 09:13 Fault 01
04/09/2019, 09:13 Fault 23
The list can be scrolled to see the last 10
items in the fault history with date and time.
3.5.19
Menu – Boiler – Faults – Reset
By selecting the boiler which you want to
reset the fault information, you then the fault
summary and details for that specific boiler. It
may take some time for the fault information
to clear as this process is flagged for action
at the next available timeslot.
3.6
Menu – Plant
The plant menu has the following options,
there are other options but these are hidden
from the User/Installer:
Plant
Status
Operating mode
Settings
Plant
Status
Operating mode
Settings
Time clock
Plant
Operating mode
Settings
Time clock
Holiday programme
Plant
Settings
Time clock
Holiday programme
Plant
Time clock
Holiday programme
3.6.1
Menu – Plant - Status
The status sub menus give you access to
see the current real time values of the plant.
The status menu has the following options:
Status
Real time values
3.6.2
Menu – Plant – Status – Real
time values
The Real time values menu has the following
options:
Real time values
Demand inputs
Sensors
Outputs
Real time values
Inputs
Sensors
Outputs
Real time values
Sensors
Outputs