To shut Down the Boiler

1.  For short periods

  Set the external controls to OFF.  Wait 4 minutes and then 

isolate the mains supply to the boiler.

2.  For longer periods

  Set the external controls to OFF.  Switch the electricity supply 

to OFF.  For longer periods the entire system should be 

drained, including the domestic hot water supply.

To Relight the Boiler

Refill the system if it has been drained, taking care to ensure no 

air is in the boiler or system.
Repeat the procedure detailed in ‘To light the boiler’.

Frost Protection

The EVOMAX boiler has built into its control system the facility to 

protect the boiler only against freezing.  

Note

This may not protect remote parts of the system, in which case a 

separate frost thermostat should be fitted.

Boiler Overheat Thermostat

Boiler overheating is detected by electrical sensors connected to 

the boiler control module.  If the boiler overheats it will shut down 

and the display will show Overheat Lockout.  Press the reset 

button and the boiler will relight.  If the fault recurs turn off the 

boiler and consult a Gas Safe Registered Engineer or in IE an 

RGI engineer. 

Condensate Drain

This appliance is fitted with a siphonic condensate trap system 

that reduces the risk of the appliance condensate from freezing.  

However should the condensate pipe to this appliance freeze, 

please follow these instructions:

a.  If you do not feel competent to carry out the defrosting 

instructions below please call your local Gas Safe Registered 

installer for assistance.

b.  If you do feel competent to carry out the following instructions 

please do so with care when handling hot utensils.  Do not attempt 

to thaw pipework above ground level.

If this appliance develops a blockage in its condensate pipe, its 

condensate will build up to a point where it will make a gurgling 

noise prior to locking out displaying “Ignition Lockout” on the 

display.  If the appliance is reset it will make a gurgling noise prior 

to it locking out displaying “Ignition Lockout” on the display.

To unblock a frozen condensate pipe;

1.  Follow the routing of the plastic pipe from its exit point on the 

appliance, through its route to its termination point.

  Locate the frozen blockage.  It is likely that the pipe is frozen 

at the most exposed point external to the building or where 

there is some obstruction to flow.  This could be at the open 

end of the pipe, at a bend or elbow, or where there is a dip in 

the pipe in which condensate can collect.  The location of the 

blockage should be identified as closely as possible before 

taking further action.

2.  Apply a hot water bottle, microwaveable heat pack or a warm 

damp cloth to the frozen blockage area.  Several applications 

may have to be made before it fully defrosts.  Warm water 

can also be poured onto the pipe from a watering can or 

similar.  DO NOT use boiling water.

3.  Caution when using warm water as this may freeze and 

cause other localised hazards.

4.  Once the blockage is removed and the condensate can flow 

freely, reset the appliance. (Refer to “To Light the boiler”)

5.  If the appliance fails to ignite, call your Gas Safe Registered 

engineer.

Preventative solutions

During cold weather, set the boiler stat to maximum, (Must return 

to original setting once cold spell is over)

Place the heating on continuous and turn the room stat down to 

15ºC overnight or when unoccupied. (Return to normal after cold 

spell).

Escape of Gas

Should a gas leak or fault be suspected contact your local gas 

supplier without delay.

Do NOT search for gas leaks with a naked flame.

Cleaning

For normal cleaning simply dust with a dry cloth.

To remove stubborn marks and stains use a damp cloth and mild 

detergent.

DO NOT use abrasive cleaning materials.