background image

IF YOU WILL INSTALL THE UNIT ON THE 

GROUND OR ON A CONCRETE MOUNTING 

PLATFORM, DO THE FOLLOWING:

•  Mark the positions for four expansion bolts based 
  on dimensions in the Unit Mounting Dimensions chart.
•  Pre-drill holes for expansion bolts.
•  Clean concrete dust away from holes.
•  Place a nut on the end of each expansion bolt.
•  Hammer expansion bolts into the pre-drilled holes.
•  Remove the nuts from expansion bolts, and place 
  outdoor unit on bolts.
•  Put washer on each expansion bolt, then replace
  the nuts.
•  Using a wrench, tighten each nut until snug.
•  Ensure the unit is level.

STEP 4: CONNECT SIGNAL AND POWER 

CABLES

The outside unit’s terminal block is protected by

an electrical wiring cover on the side of the unit.

A comprehensive wiring diagram is printed on

the inside of the wiring cover.

BEFORE PERFORMING ELECTRICAL 

WORK, READ THESE REGULATIONS

•  All wiring must comply with local and national 
  electrical codes, and must be installed by a licensed 
 electrician.
•  All electrical connections must be made according 
  to the Electrical Connection Diagram located on the 
  side panels of the indoor and outdoor units.
•  If there is a serious safety issue with the power 
  supply, stop work immediately. Explain your reasoning 
  to the client, and refuse to install the unit until the 
  safety issue is properly resolved.
•  Power voltage should be within 90-100% of rated 
  voltage. Insufficient power supply can cause 
  electrical shock or fire.
•  If connecting power to fixed wiring, install a surge 
  protector (Ideal-Air

TM

 700522) and main power 

  switch with a capacity of 1.5 times the maximum 
  current of the unit.
•  If connecting power to fixed wiring, a switch or 
  circuit breaker that disconnects all poles and has a 
  contact separation of at least 3mm/.125" must be 
  incorporated in the fixed wiring. The qualified technician 
  must use an approved circuit breaker or switch.
•  Only connect the unit to an individual branch 
  circuit outlet. 

DO NOT

 connect another appliance 

  to that outlet.
•  Make sure to properly ground the air conditioner.
•  Every wire must be firmly connected. Loose wiring 
  can cause the terminal to overheat, resulting in 
  product malfunction and possible fire.
• 

DO NOT

 let wires touch or rest against refrigerant 

  tubing, the compressor, or any moving parts within 
  the unit.

Before installing a wall-mounted unit, make sure that 
the wall is made of solid brick, concrete, or of similarly 
strong material. 

The wall must be able to support 

at least four times the weight of the unit.

•  Mark the position of bracket holes based on
  dimensions in the Unit Mounting Dimensions chart.
•  Pre-drill the holes for the expansion bolts.
•  Clean dust and debris away from holes.
•  Place a washer and nut on the end of each
  expansion bolt.
•  Thread expansion bolts through holes in mounting 
  brackets, put mounting brackets in position, and 
  hammer expansion bolts into the wall.
•  Check that the mounting brackets are level.
•  Carefully lift unit and place its mounting feet
  on brackets.
•  Bolt the unit firmly to the brackets.

TO REDUCE VIBRATIONS OF 

WALL MOUNTED UNIT

If allowed, you can install the wall-mounted unit with 
rubber gaskets to reduce vibrations and noise.

WHEN DRILLING INTO CONCRETE, EYE

PROTECTION IS RECOMMENDED AT ALL

TIMES.

IF YOU WILL INSTALL THE UNIT ON A 

WALL-MOUNTED BRACKET, DO THE  

FOLLOWING:

 WARNING

 WARNING

CAUTION

bt

Summary of Contents for 700807

Page 1: ...ONER INSTALLATION MANUAL This manual only describes the installation of the indoor unit When installing the outdoor unit refer to the installation manual of outdoor unit 700807 700808 PRO MINI SPLIT I N D O O R W A L L M O U N T ...

Page 2: ...our purchase of Ideal Air s Pro Mini Split indoor wall mount unit We re proud to offer this product and believe it s the very best in its class 2 SAFETY PRECAUTIONS 3 ACCESSORIES 5 INSTALLATION SUMMARY INDOOR UNIT 6 UNIT PARTS 8 INDOOR UNIT INSTALLATION 9 OUTDOOR UNIT INSTALLATION 17 REFRIGERANT PIPING CONNECTION 21 AIR EVACUATION 23 ELECTRICAL AND GAS LEAK CHECKS 25 TEST RUN 25 DISPOSAL GUIDELINE...

Page 3: ...an cause water leakage electrical shock fire and can cause the unit to fail Install the unit in a firm location that can support the unit s weight If the chosen location cannot support the unit s weight or the installation is not done properly the unit may drop and cause serious injury and damage For all electrical work follow all local and national wiring standards regulations and the Installatio...

Page 4: ...AUTION NOTE ABOUT FLUORINATED GASES This air conditioning unit contains fluorinated gases For specific information on the type of gas and the amount please refer to the relevant label on the unit itself Installation service maintenance and repair of this unit must be performed by a certified technician Product uninstallation and recycling must be performed by a certified technician If the system h...

Page 5: ...and fire or equipment failure Name Shape Quantity 1 1 1 Clip anchor Mounting plate fixing screw ST3 9 X 25 Remote control Fixing screw for remote control holder ST2 9 x 10 Remote control holder Dry battery AAA LR03 Seal Drain joint Mounting plate 5 5 2 1 Optional Parts 2 1 1 User manual Installation manual Line sets sold separately Connecting pipe assembly Liquid side Gas side 6 35 1 4 9 52 3 8 9 ...

Page 6: ...ation Page 9 And Drill Wall Hole Page 10 1 Attach Mounting Plate Page 10 2 Prepare Refrigerant Piping Page 12 4 3b 12cm 4 75 2 3m 90 55 12cm 4 75 15cm 5 9 Determine Wall Hole Position Page 10 3a INSTALLATION SUMMARY INDOOR UNIT ...

Page 7: ...7 Mount Indoor Unit Page 16 STEP 8 Wrap Piping and Cable Page 15 1 2 3 Connect Drain Hose Page 13 Connect Signal Cable Page 14 5 6 7 8 ...

Page 8: ...ont Panel Outdoor Unit Power Cable Some Units Remote Holder Remote Control Some Units UNIT PARTS NOTE ON ILLUSTRATIONS Illustrations in this manual are for explanatory purposes The actual shape of your indoor unit may be slightly different The actual shape shall prevail FIG 2 1 ...

Page 9: ...rt the weight of the unit A location at least 1m 40 from all other electrical devices e g TV radio computer DO NOT INSTALL UNIT IN THE FOLLOWING LOCATIONS Near any source of heat steam or combustible gas Near flammable items such as curtains or clothing Near any obstacle that might block air circulation Near the doorway In a location subject to direct sunlight INSTALLATION INSTRUCTIONS INDOOR UNIT...

Page 10: ...m 2 5 core drill drill a hole in the wall Make sure that the hole is drilled at a slight downward angle so that the outdoor end of the hole is lower than the indoor end by about 5mm 7mm 0 2 0 275 This will ensure proper water drainage See FIG 3 2 Place the protective wall cuff in the hole This protects the edges of the hole and will help seal it when you finish the installation process When drilli...

Page 11: ...mm 1 55 Right rear wall hole 65mm 2 5 Model C 965mm 38 138mm 5 45 34mm 1 35 517 4mm 20 37 Indoor unit outline Left rear wall hole 65mm 2 5 219mm 8 6 553mm 21 77 300mm 11 8in 335mm 13 2 Right rear wall hole 65mm 2 5 Model D 1080mm 42 5 53 5mm 2 1 47mm 1 85 76mm 3 53 5mm 2 1 47mm 1 85 148 7mm 5 85 151mm 5 95 174 3mm 6 85 Indoor unit outline Left rear wall hole 65mm 2 5 172mm 6 8 362mm 14 25 Right re...

Page 12: ...WILL AFFECT THE UNIT S PERFORMANCE Use scissors to cut down the length of the insulating sleeve to reveal about 15cm 6 of the refrigerant piping This serves two purposes a To facilitate the Refrigerant Piping Connection process b To facilitate gas leak checks and enable you to check for dents If existing connective piping is already embedded in the wall proceed directly to the Connect Drain Hose s...

Page 13: ... a small amount of water into the drain pan to make sure that water flows from the unit smoothly PLUG THE UNUSED DRAIN HOLE To prevent unwanted leaks you must plug the unused drain hole with the rubber plug provided FIG 3 5 CORRECT Make sure there are no kinks or dent in drain hose to ensure proper drainage FIG 3 6 NOT CORRECT Kinks in the drain hose will create water traps FIG 3 7 NOT CORRECT Kin...

Page 14: ...nit to an individual branch circuit outlet DO NOT connect another appliance to that outlet Make sure to properly ground the air conditioner Every wire must be firmly connected Loose wiring can cause the terminal to overheat resulting in product malfunction and possible fire DO NOT let wires touch or rest against refrigerant tubing the compressor or any moving parts within the unit STEP 6 CONNECT S...

Page 15: ...the wire cover on the front of the unit and the plastic panel on the back STEP 7 WRAP PIPING AND CABLES Before passing the piping drain hose and the signal cable through the wall hole you must bundle them together to save space protect them and insulate them Bundle the drain hose refrigerant pipes and signal cable according to FIG 3 10 DRAIN HOSE MUST BE ON BOTTOM Make sure that the drain hose is ...

Page 16: ...edded in the wall do the following Hook the top of the indoor unit on the upper hook of the mounting plate Use a bracket or wedge to prop up the unit giving you enough room to connect the refrigerant piping signal cable and drain hose Refer to FIG 3 11 for an example Connect drain hose and refrigerant piping refer to Refrigerant Piping Connection section of this manual for instructions Keep pipe c...

Page 17: ...le to the direction of the wind If needed build a barrier in front of the unit to protect it from extremely heavy winds See FIG 4 2 and FIG 4 3 above INSTALLATION INSTRUCTIONS OUTDOOR UNIT IF THE UNIT IS FREQUENTLY EXPOSED TO HEAVY RAIN OR SNOW Build a shelter above the unit it to protect it from the rain or snow Be careful not to obstruct air flow around the unit IF THE UNIT IS FREQUENTLY EXPOSED...

Page 18: ...between their mounting feet Prepare the installation base of the unit according to the dimensions below FIG 4 4 WARNING W A B D Air inlet Air outlet Air inlet Outdoor Unit Dimensions mm in W x H x D Mounting Dimensions Distance A mm in Distance B mm in 681x434x285 26 8 x17 x11 2 460 18 10 292 11 49 700x550x270 27 5 x21 6 x10 62 450 17 7 260 10 24 780x540x250 30 7 x21 25 x9 85 549 21 6 276 10 85 84...

Page 19: ...f 1 5 times the maximum current of the unit If connecting power to fixed wiring a switch or circuit breaker that disconnects all poles and has a contact separation of at least 3mm 125 must be incorporated in the fixed wiring The qualified technician must use an approved circuit breaker or switch Only connect the unit to an individual branch circuit outlet DO NOT connect another appliance to that o...

Page 20: ... and place it to the side Match the wire colors labels with the labels on the terminal block and firmly screw the u lug of each wire to its corresponding terminal After checking to make sure every connection is secure loop the wires around to prevent rain water from flowing into the terminal Using the cable clamp fasten the cable to the unit Screw the cable clamp down tightly Insulate unused wires...

Page 21: ... of 5m 16 5 Refer to the table below for specifications on the maximum length and drop height of piping MAXIMUM LENGTH AND DROP HEIGHT OF REFRIGERANT PIPING PER UNIT MODEL DO NOT DEFORM PIPE WHILE CUTTING Be extra careful not to damage dent or deform the pipe while cutting This will drastically reduce the heating efficiency of the unit STEP 2 REMOVE BURRS Burrs can affect the air tight seal of ref...

Page 22: ... and even flaring STEP 4 CONNECT PIPES When connecting refrigerant pipes be careful not to use excessive torque or to deform the piping in any way You should first connect the low pressure pipe then the high pressure pipe MINIMUM BEND RADIUS When bending connective refrigerant piping the minimum bending radius is 10cm 4 See FIG 5 6 INSTRUCTIONS FOR CONNECTING PIPING TO INDOOR UNIT Align the center...

Page 23: ...nts shown in the table above WARNING TORQUE REQUIREMENTS Outer Diameter of Pipe mm Tightening Torque N cm Add Tightening Torque N m Ø 6 35 Ø 0 25 1 500 11lb ft 1 600 11 8lb ft Ø 9 52 Ø 0 375 2 500 18 4lb ft 2 600 19 18lb ft Ø 12 7 Ø 0 5 3 500 25 8lb ft 3 600 26 55lb ft Ø 16 Ø 0 63 4 500 33 19lb ft 4 700 34 67lb ft Valve cover FIG 5 9 FIG 5 10 AIR EVACUATION PREPARATIONS AND PRECAUTIONS Air and for...

Page 24: ...ing hexagonal wrench fully open both the high pressure and low pressure valves Tighten valve caps on all three valves service port high pressure low pressure by hand You may tighten it further using a torque wrench if needed OPEN VALVE STEMS GENTLY When opening valve stems turn the hexagonal wrench until it hits against the stopper DO NOT try to force the valve to open further WARNING NOTE ON ADDI...

Page 25: ...L CODES AND MUST BE INSTALLED BY A LICENSED ELECTRICIAN GAS LEAK CHECKS There are two different methods to check for gas leaks SOAP AND WATER METHOD Using a soft brush apply soapy water or liquid detergent to all pipe connection points on the indoor unit and outdoor unit The presence of bubbles indicates a leak LEAK DETECTOR METHOD If using leak detector refer to the device s operation manual for ...

Page 26: ...ient temperature is below 17 C In this instance you can use the MANUAL CONTROL button to test the COOL function Lift the front panel of the indoor unit and raise it until it clicks in place The MANUAL CONTROL button is located on the right hand side of the unit Press it 2 times to select the COOL function See FIG 8 1 Perform test run as normal This appliance contains refrigerant and other potentia...

Page 27: ... greater the number rating the more efficient the heating A 10 HSPF for example is a very good rating Humidifier Humidifiers use water to put humidity in the growing space Many plants we grow indoors are accustomed to growing outdoors in tropical areas where humidity is high Also certain parts of the country are drier than others so you will need to add humidity Line Set Insulated copper tubing us...

Page 28: ... answers to most common questions and a complete technical support library please visit www ideal air com All design and specifications herein are subject to change without notice for product improvement Contact Ideal AirTM for details updates and other information DO NOT return this product to the store where you purchased it ...

Reviews: