Keypad Output Format
Define the data format the reader will use to send keypad input data.
This configuration applies when sending PIN data over Wiegand only.
⦁
Keypad Output Format
:
-
ARK501 (Default)
-
26 Bit
-
4 Bit
-
4 Bit Parity
-
4 Bit Buffered
-
4 Bit Parity Buffered
-
36 Bit Output
Low Frequency Flags
The Low Frequency Flag TLV is used to enable reading of legacy HID low frequency formats, which may be
required for backward compatibility on older sites.
When enabled, the reader will interpret 125kHz HID cards using a legacy version of the HID format. When disabled,
the reader will read 125kHz HID cards using the standard HID format. This is the default.
There is currently no selection option to disable this programming once enabled. To disable low frequency flags,
apply a
Hex
TLV with hex code
160100
.
Custom Card Format Slots
Allows the entry of a custom format string which describes how to interpret data from the card being read.
Changing this setting has the potential to render the reader unusable.
⦁
Slot
: The custom card format slot where the custom format configuration will be stored.
⦁
Format
: Enter the required custom card format string.
The string must be in ASCII format, up to a maximum of 64 ASCII characters.
For example, %64r sets the format to 64 bit raw, so the reader will read the first 64 bits of data off the card.
ICT Card Reader | Configuration Guide
16