Connect the two form-C relay bus alarm outputs to an external 
monitoring  system  if  needed,  by  stripping  and  terminating  16-
28AWG alarm wiring in the Bus A and B Alarm 3-pin connector 
plugs,  and  installing  in  the  back  panel.  Each  Bus  Alarm  output 
will trigger for any fuse or breaker open on that bus. Note that 
unused output channels should have a fuse or breaker installed 
to avoid continuous activation of the alarm contact. 
 
Bus Alarm Connector: (Bus A or B) 

 

OPERATION 

Ensure the correct fuses or circuit breakers are installed in each 
channel location that will be used to power a load, and switch 
the  front  panel  channel  breakers  into  the  ON  position  (if 
equipped).  Close  the  main  Bus  A  and  B  input  disconnect 
devices, and the panel is ready to use. 
 
An  over  current  condition  on  any  output  channel  will  trip  the 
beaker  or  open  the  fuse  on  that  channel,  lighting  the  fuse  fail 
LED (on fuse units) and triggering the Bus Form-C alarm contact 
for the affected bus. 

 

SPECIFICATIONS 

Operating Voltage (either bus):  10VDC to 60VDC, or -10VDC to 

-60VDC 

Bus Current Rating: 

100A max, 80A cont. (Bus A, B) 

Output Current Rating: 

20A Continuous per output 
(limited by bus max rating) 

Fuse/Breaker Capacity: 

25A x 6 per bus 

Power Consumption: 

< 4 W  

Alarm Form-C Contacts: 

1 output per bus, 0.5A 65VDC 

Input Connector: 

4x Insulated M8 Stud, with 
slip-on insulating boot 

Output Connector: 

12 position cage clamp type 
per bus (10 – 22AWG) 

Alarm Connectors: 

Removable plug cage clamp 
type (16 – 28 AWG) 

Operating Temperature: 

-20°C to +60°C (Derate max 
bus current by 2% per degree 
C above 50°C) 

Weight: 

7 lbs (3.2kg) 

Warranty: 

2 years 

Dimensions: 

19.0” x 9.29” x 1.75” 
483mm x 236mm x 45mm 

LIMITED WARRANTY 

ICT  Ltd.  warrants  to  the  original  consumer  purchaser  that  this 
product  shall  be  in  good  working  order,  free  from  defects  in 
materials and workmanship, for a period of two (2) years from 
the  date  of  purchase.  Should  failure  occur  during  the  above 
stated time period, then ICT will, at its option, repair or replace 
this product at no additional charge except as set forth below. 
All  parts,  whether  for  repair  or  replacement,  will  be  furnished 
on an exchange basis. All exchange pieces become the property 
of  ICT.  This  limited  warranty  shall  not  apply  if  the  ICT  product 
has  been  damaged  by  unreasonable  use,  accident,  negligence, 
disaster, service, or modification by anyone other than the ICT 
factory. 
 
Limited  warranty  service  is  obtained  by  delivering  the  product 
during  the  above  stated  two  (2)  years  warranty  period  to  an 
authorized  ICT  dealer  or  ICT  factory  and  providing  proof  of 
purchase  date.  If  this  product  is  delivered  by  mail,  you  will 
insure the product or assume  risk of loss or damage in transit, 
and prepay shipping charges to the factory. 
 
Every  reasonable  effort  has  been  made  to  ensure  that  ICT 
product manuals and promotional materials accurately describe 
ICT  product  specifications  and  capabilities  at  the  time  of 
publication.  However,  because  of  ongoing  improvements  and 
updating of ICT products, ICT cannot guarantee the accuracy of 
printed  materials  after  the  date  of  publication  and  disclaims 
liability for changes, errors or omissions. 
 
If  this  ICT  product  is  not  in  good  working  order,  as  outlined  in 
the  above  warranty,  your  sole  remedy  shall  be  repair  or 
replacement as provided above. In no event will ICT be liable for 
any damages resulting from the use of or the inability to use the 
ICT  product,  even  if  an  ICT  employee  or  an  authorized  ICT 
dealer  has  been  advised  of  the  possibility  of  such  damages,  or 
for any claim by any other party. 
 
ICT reserves the right to make changes without further notice to 
any  products  or  documentation  for  improvement  of  reliability, 
function, or design. 
 
ICT Ltd. does not recommend use of its products in life support 
applications  wherein  a  failure  or  malfunction  of  the  product 
may directly or indirectly threaten life or cause injury. The user 
of ICT products, which are to be used in life support applications 
as  described  above,  assumes  all  risks  of  such  use  and 
indemnifies ICT against all damages. 

 

INNOVATIVE CIRCUIT TECHNOLOGY LTD. 

26921 Gloucester Way 

Langley, British Columbia, Canada   V4W 3Y3 

604.856.6303  

F

 604.856.6365   

www.ict-power.com 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Alarm Pin  

Function  

Alarm Output common (0.5A 65Vdc max) 

NC 

Alarm Output normally  closed for alarm  

NO 

Alarm Output normally  open for alarm  

Innovative Circuit 

Technology Ltd. 

 

Standard Dual Bus 

Distribution Panel Series 

INSTRUCTION MANUAL 

855-314-010 (Rev 1.5) 

 

Models: 

ICT200DF-12 

ICT200DB-12 

Reviews: