10.3.2 Modbus settings
10.3.2.1 Modbus RTU Setup
The Flow sensors
IVA 521
comes with a Modbus RTU Interface.
Before commissioning the sensor the communication
parameters
Modbus ID, Baudrate, Parity und Stop bit
must be set in order to ensure the communication with the Modbus master.
Settings
Modbus Setup
Default values out of factory:
Modbus ID:
1
Baud rate:
19200
Stop bit:
1
Parity:
even
Byte Order:
ABCD
Remark
: If the sensor is placed at the end of the Modbus system a termination is required. The sensors have an
internal switchable termination, therefore the 6 fastening screws from the lid are to be released and set
the internal DIP Sw
itch to “On”.
Alternatively, a 120R resistor can be installed in the plug between pin 2 and pin 4
.
It must be ensured that the connection plugs are still plugged and the gasket is installed correctly, see
also chapter 4.5.
For changes, e.g. the sensor ID,
first select by pressing key
„
“
the field
“
ID
”
and then key “
OK”
.
Select the desired position by pressing the
">"
and select with
"OK
" button.
Change values by pressing the
„
“
values
takeover by pressing
"OK".
Inputs for baud rate, stop bit and parity is
done analogue.
By means of the button "Byte Order" it is
possible to change the data format (Word
Order). Possible formats are "ABCD" (Little
Endian) and "CDAB" (Middle Endian)
Saving the changes by pressing
"Save",
therefore select it with key
„
“
and then
confirm it with
"OK".
To set back to default values please press
“Set to Default”