• Two designs

duct version 

(

I

LK)

wall mounting 

(

I

LW)

• Different

physical

outputs

humidity and temperature and all 
hx values 

1)

 

• Output signals

RS232 with ASCII protocol

RS485 with Modbus RTU protocol

• Special versions

sealing for increased  

requirements, e.g. condensation

sealing against vibrations

• Filter

protective basket ZE07 (IP 00)

filter with membrane ZE08 (IP30)
PTFE sintered filter ZE05 (IP65)

Product info sheet 

I

L Series digital

Humidity/-temperature sensors for digital data 

transfer RS485 / MODBUS-RTU or RS232 for 

use in heating, ventilation and air conditioning 

Measuring medium

air, pressureless, 

non-aggressive,  non-condensing  

Min. air speed  

 0.5 m/s

Operating temperature

-40...+80°C

Storage temperature

-40...+85°C

Degree of protection of measuring head 

with protective basket ZE07

IP00

with membrane filter ZE08

IP30

with PTFE sintered filter ZE05

IP65

Degree of protection housing

IP65

Material of housing

PC (light grey / white)

General data

 

Power supply, external

6...30  VDC

Max. transfer distance RS232/RS485

15m/1000 m

Consumption of electronics

< 1,0 mA

Directive about electromagnetic compatibility 2014/30/EU

DIN EN 61326-1 ............................................. issue 07/13

DIN EN 61326-2-3 .......................................... issue 07/13

Humidity

 

Sensing element

calibrated sensor chip calHT

Output range

0...100 %rh

Accuracy  

30...80 %rh 

at 10...40°C

±

3  %rh         

< 30 %rh or > 80 %rh 

at 10...40°C

±

5 %rh

Influence of temperature  < 10°C or > 40°C   typ. 

±

0.06 %rh/K

Technical data 

Temperatur

Sensing element

calibrated sensor chip calHT

Output ranges

-40...+85°C

Accuracy
       at 10...40°C 

±0.8 K

        <10°C and >40°C 

see diagramm

Electrical data

1) The accuracy of the calculated values depends on both the opera-
ting point in accordance with the hx diagram and on the primary values
measured. The hx processor operates in the range -30°C < T < +70°C,

5% rh<F<95% rh. Values outside this range are not calculated, the last

valid value is displayed. Normal atmospheric pressure of 1013.25 mbar 
is used when calculating the hx values.

I

LK

I

LW

Summary of Contents for IL Series

Page 1: ...ree of protection housing IP65 Material of housing PC light grey white General data Power supply external 6 30 VDC Max transfer distance RS232 RS485 15m 1000 m Consumption of electronics 1 0 mA Direct...

Page 2: ...d to check the accuracy of the sensors 84 rh at 25 C humidity standard to check the accuracy of the sensors 97 rh at 25 C ZE33 as designation F5 2 adapter for humidity standard ZE 31 1 Flange 20 045 f...

Page 3: ...ature C enthalpy kJ kg mixing ratio g kg absolute humidity g m and wet bulb temperature C K 4 Output signals RS232 ASCII protocol R RS485 MODBUS RTU protocol M 5 6 Operation conditions special version...

Page 4: ...Series Design Duct version Physical outputs active outputs Output signals MODBUS RTU Operation conditions special versions Sealing against vibrations Measured variable and output range 1 Measured vari...

Page 5: ...dity occur The sensor tube resp measuring head or measuring chamber should be exposed to the flow of air Avoid installation next to heaters doors or on outer walls Avoid places exposed to the sun Not...

Page 6: ...FLOAT32 Dew point temperature C 11 12 FLOAT32 Enthalpy kJ kg 13 14 FLOAT32 Mixing ratio g kg 15 16 FLOAT32 Absolute humidity g m 17 18 FLOAT32 Wet bulb temperature C 19 20 UINT16 Alarm code hx proces...

Page 7: ...sor The Modbus address can be modified at any time via write access to the address register reg no 205 Permissi ble slave addresses are within the 1 247 range Using address 0 as a slave address is not...

Page 8: ...rs in this impedance category 256 bus nodes are theoretically possible instead of 32 However due to the available address space in practice the number reduces to 247 The scanning interval should not e...

Page 9: ...ret the decimal result as a hexadecimal number 56 38hex 5 Compare the individual hexadecimal numbers with the transmitted ASCII characters of the checksum 38hex 3 8 VisualPMU Freeware for RS232 This s...

Reviews: