Configuring Network Settings 

1) 

Run the eSearch Utility. 

The eSearch Utility is located at:   

http://ftp.icpdas.com/pub/cd/6000cd/napdos/software/esearch/

 

 

2) 

Click the 

“Search Servers”

 to search your ET-2242U. 

3) 

Double-click your ET-2242U to configure the settings 

 

 

 

 

 

 

 

 

 

 

Factory Default Settings of ET-2242U: 

IP Address 

192.168.255.1 

Subnet Mask 

255.255.0.0 

Gateway 

192.168.0.1 

 

4) 

Contact your Network Administrator to obtain a correct network 

configuration (such as

 IP/Mask/Gateway

). 

Enter the network settings

 

and click 

“OK”

     

Note: The ET-2242U will use the new settings 2 

seconds later.

 

 
 
 
 
 
 
 

 

 

 

 

 

Summary of Contents for ET-2242U

Page 1: ...42U Quick Start v1 1 Mar 2018 What s in the box Related Information The package includes the following items ET 2242U Module x 1 Quick Start x1 This Document ET 2200 Series Product Page Documentation Firmware NS 205 MDR 20 24 Product Page optional ...

Page 2: ... your Windows firewall and Anti Virus firewall first else the Search Servers on Chapter 5 may not work Please contact with your system Administrator 2 Connect both the ET 2242U and your PC to the same sub network or the same Ethernet switch 3 Supply power 10 30 VDC to the ET 2242U 4 Verify that the PWR LED indicator on the ET 2242U is flashing Red OK ...

Page 3: ...ervice icpdas com P3 2 Pin Assignments Wiring Note Pin Assignments Wire Connections Readback as 1 ON State Digital Output Sink Source Readback as 0 OFF State DOx DO COM Load DOx DO COM Load DOx DO COM Load DOx DO COM Load ...

Page 4: ...est A tip for connecting the wire to the connector A tip for removing the wire from the connector 1 Use output LED to connect the DO COM pin Pin04 to the DO0 pin Pin06 2 Connect the External Power 24V to the DO0 pin Pin06 3 Connect the External Power GND to the DO COM Pin04 ...

Page 5: ... some registers is labeled with an E 1 0 cannot be write 1 can be write W 100 0x21 1 nDO Enables the PWM for all DO Channels 1 0 OFF 1 ON Default 0 R W 235 0xEB 1 nDO Sets the Power on value for all DO Channels 1 0 OFF 1 ON Default 0 R W F 267 0x10B 1 nDO Sets the Safe value for all DO Channels 1 0 OFF 1 ON Default 0 R W F R Read W Write F Settings are recorded in flash by default E After writing ...

Page 6: ...Search Servers to search your ET 2242U 3 Double click your ET 2242U to configure the settings Factory Default Settings of ET 2242U IP Address 192 168 255 1 Subnet Mask 255 255 0 0 Gateway 192 168 0 1 4 Contact your Network Administrator to obtain a correct network configuration such as IP Mask Gateway Enter the network settings and click OK Note The ET 2242U will use the new settings 2 seconds lat...

Page 7: ...he ET 2242U is working well with new configuration 2 Click the name of ET 2242U to select it 3 Click the Web button to log in to the web configuration pages Or enter the URL address of the ET 2242U in the address bar of the browser 4 Enter the password default Admin in the login password field and click Submit Use the default password Admin ...

Page 8: ...pdas com P8 5 In the Home page allows a simple test to be performed to verify the Digital Input and Output functionality 6 In the Digital I O section click the DO0 button to ON Red 7 Verify that the output LED status for high High ...

Reviews: