background image

516 01 3604 04

Specifications subject to change without notice.

19

Installing Weatherproof Cover

A  weatherproof while-in-use cover for  the factory-installed

convenience outlets is now required by UL standards. This

cover cannot be factory-mounted due its depth; it must be

installed at unit installation. For shipment, the convenience

outlet is covered with a blank cover plate.

The weatherproof cover kit is shipped in the unit’s control

box. The kit includes the hinged cover, a backing plate and

gasket.

DISCONNECT ALL POWER TO UNIT AND 

CONVENIENCE OUTLET.

Remove  the  blank  cover  plate  at  the  convenience  outlet;

discard the blank cover.

Loosen the two screws at the GFCI duplex outlet, until ap

-

proximately 

1

/

2

-in.  (13  mm)  under  screw  heads  are  ex

-

posed.  Press  the  gasket  over  the  screw  heads.  Slip  the

backing plate over the screw heads at the keyhole slots and

align with the gasket; tighten the two screws until snug (do

not over-tighten).

Mount  the  weatherproof  cover  to  the  backing  plate  as

shown in Fig. 32. Remove two slot fillers in the bottom of the

cover to permit service tool cords to exit the cover. Check

for full closing and latching.

Fig. 32 — Weatherproof Cover Installation

FACTORY-OPTION THRU-BASE CONNECTIONS
This  service  connection  kit  consists  of  a 

1

/

2

-in.  electrical

bulkhead connector and a 1

1

/

2

-in. electrical bulkhead con

-

nector, all factory-installed to the basepan cover plate. Re

-

move the cover plate from the shipping bracket and attach

to  basepan  with  8  screws  provided.  The 

1

/

2

-in.  bulkhead

connector  enables  the  low-voltage  control  wires  to  pass

through the basepan. The 1

1

/

2

-in. electrical bulkhead con

-

nector allows the high-voltage power wires to pass through

the basepan. See Fig. 33.

Check tightness of connector lock nuts before connecting

electrical conduits.

Field-supplied and field-installed liquidtight conduit connec

-

tors and conduit may be attached to the connectors on the

basepan. Pull correctly rated high voltage and low voltage

wires through appropriate conduits. Connect the power con

-

duit to the internal disconnect (if unit is so equipped) or to

the external disconnect (through unit side panel). Remove

one of the two knockouts located on the bottom left side of

the unit control box. Use this hole for the control conduit.

Fig. 33 — Thru-Base Connection Fittings

UNITS WITHOUT THRU-BASE CONNECTIONS
1. Install power wiring conduit through side panel open

-

ings. Install conduit between disconnect and control

box.

2. Install power lines to terminal connections as shown

in Fig. 26.

FIELD CONTROL WIRING
The RHH unit requires an external temperature control de

-

vice. This device can be a thermostat.
THERMOSTAT
Select  an  approved  accessory  2-stage  Cooling/Heating

thermostat. The RHH models do not require a thermostat

with an O function to control the reversing valve operation. If

using  an  electronic  thermostat,  configure  it  for  “non-heat

pump” operation. Install the accessory thermostat according

to installation instructions included with the accessory.

Locate the thermostat accessory on a solid wall in the con

-

ditioned  space  to  sense  average  temperature  in  accor

-

dance with the thermostat installation instructions.

If the thermostat contains a logic circuit requiring 24-v pow

-

er, use a thermostat cable or equivalent single leads of dif

-

ferent colors with minimum of seven leads. If the thermostat

does not require a 24-v source (no “C” connection required),

use a thermostat cable or equivalent with minimum of six

leads. See Fig. 34. Check the thermostat installation instruc

-

tions for additional features which might require additional

conductors in the cable.

For wire runs up to 50 ft. (15 m), use no. 18 AWG (American

Wire Gage) insulated wire [35°C (95°F) minimum]. For 50 to

75 ft. (15 to 23 m), use no. 16 AWG insulated wire [35°C

(95°F) minimum]. For over 75 ft. (23 m), use no. 14 AWG in

-

sulated wire [35°C (95°F) minimum]. Wire sizes larger than

no. 18 AWG cannot be directly connected to the thermostat

and will require a junction box and splice at the thermostat.

TOP

TO

P

TOP

WET  LOCATIO

NS

W

ET

  L

OC

AT

IO

NS

COVER - WHILE-IN-USE

WEATHERPROOF

BASEPLATE FOR

GFCI RECEPTACLE

GASKET

GFCI RECEPTACLE

NOT INCLUDED

LOW VOLTAGE
CONDUIT
CONNECTOR

HIGH VOLTAGE
CONDUIT
CONNECTOR

Summary of Contents for RHH120

Page 1: ...RING DIAGRAMS Economi er X Factory Option 27 SYSTEM COMPONENTS SPECIFICATIONS INPUTS OUTPUTS ENVIRONMENTAL ECONOMIZER MODULE WIRING DETAILS INTERFACE OVERVIEW ENTHALPY SETTINGS TWO SPEED FAN OPERATION...

Page 2: ...t DANGER ELECTRICAL SHOCK HAZARD Failure to follow this warning will result in personal injury or death Before performing service or maintenance operations on unit turn off main power switch to unit a...

Page 3: ...Enthalpy Sensor P 2 Position Damper w Barometric Relief U Ultra Low Leak Economizer w Barometric Relief OA Temp Sensor W Ultra Low Leak Economizer w Barometric Relief Enthalpy Sensor Outdoor Air Optio...

Page 4: ...4 Specifications subject to change without notice 516 01 3604 04 Fig 2 Unit Dimensional Drawing Size 120 Units...

Page 5: ...516 01 3604 04 Specifications subject to change without notice 5 Fig 2 Unit Dimensional Drawing Size 120 Units cont...

Page 6: ...clearances LOCATION DIMENSION CONDITION A 48 in 1219 mm 18 in 457 mm 18 in 457 mm 12 in 305 mm Unit disconnect is mounted on panel No disconnect convenience outlet option Recommended service clearance...

Page 7: ...o the check valve core s bottom O ring Install the fitting body and torque to 96 10 in lbs 10 9 1 Nm Do not exceed 106 in lbs 11 9 Nm when tightening INSTALLATION Jobsite Survey Complete the following...

Page 8: ...ing 8 Make electrical connections 9 Install other accessories FRAME MOUNTED INSTALLATION Frame mounted applications generally follow the sequence for a curb installation Adapt the sequence as required...

Page 9: ...516 01 3604 04 Specifications subject to change without notice 9 Fig 6 Roof Curb Details REV 50TM500827...

Page 10: ...t is ready to be rigged and no longer will be lift ed by a fork truck the wood protector under the basepan must be removed Remove 4 screws from each base rail Wood protector will drop to the ground Se...

Page 11: ...iscard the supply duct cover Install accessory CRDUCTCV001A00 to cover the vertical supply duct open ing Use the return duct cover removed from the unit end panel to cover the vertical return duct ope...

Page 12: ...own form and assembled to a metal support tray using plastic stretch wrap Located in the return air compartment the assembly s metal tray is at tached to the basepan and also attached to the damper us...

Page 13: ...e hood sides See Fig 17 and 18 Secure hood divider with 3 screws on each hood side The hood divider is also used as the bottom filter rack for the aluminum filter 5 Attach the post that separates the...

Page 14: ...must be used to route the main power from the condenser end of the unit to either the factory option disconnect the bottom of the control box or the single point box accessory One inch conduit is pro...

Page 15: ...1 4 in female spade connector from the 230 v connection and moving it to the 200 v 1 4 in male terminal on the prima ry side of the transformer Refer to unit label diagram for ad ditional information...

Page 16: ...m deviation is 4 v Determine percent of voltage imbalance This amount of phase imbalance is satisfactory as it is below the maxi mum allowable 2 Operation on improper line voltage or excessive phase i...

Page 17: ...socket re install 3 hex screws on the NFD enclosure 12 Re install the unit front panel Fig 29 Handle and Shaft Assembly for NFD CONVENIENCE OUTLETS Two types of convenience outlets are offered on RHH...

Page 18: ...the bottom of the dis connect box For the load side wiring to the factory option disconnect route the wires through the hole on the right side of the disconnect Be sure to create a drip loop at least...

Page 19: ...conduits Connect the power con duit to the internal disconnect if unit is so equipped or to the external disconnect through unit side panel Remove one of the two knockouts located on the bottom left...

Page 20: ...ng valve position Reversing valves are ener gized during the cooling stages and the defrost cycle and de energized during heating cycles Once energized at the start of a cooling stage the reversing va...

Page 21: ...DI 24 vac P2 4 CTB Y2 W1 Heat 1 DI 24 vac P2 7 CTB W1 W2 Heat 2 DI 24 vac P2 6 CTB W2 R Power 24 vac P3 1 CONTL BRD 8 C Common 24 vac P3 2 CONTL BRD 4 DFT 1 DI 24 vac DFT 1 to DFT 1 DFT 2 DI 24 vac D...

Page 22: ...he bottom left side of the control box after removing one of the two knockouts in the corner of the box Using a connector at the control box to protect the wire as it passes into the control box Pull...

Page 23: ...can be installed in the unit Use the wir ing procedure listed below for each heater as determined by the number of stages in the heater Single Stage Heaters Single stage heaters will have an orange a...

Page 24: ...ce 516 01 3604 04 Fig 41 Accessory Electric Heater Control Connections NOTE Optional Outdoor Temperature Control at One Heater Stage Move either heater wire to this terminal and connect outdoor temper...

Page 25: ...25 Specifications subject to change without notice 516 01 3604 04 Fig 42 Typical RHH Control Wiring Diagram...

Page 26: ...26 Specifications subject to change without notice 516 01 3604 04 Fig 43 Typical RHH Power Wiring Diagram 208 230 3 60 unit shown...

Page 27: ...module includes terminals for CO2 sensor Mixed Air sensor and an Outdoor Dry Bulb sensor Enthalpy and other options are available with bus sensors User Interface The interface provides status for norm...

Page 28: ...040839 001 Rev G HJW10 www energy ca gov Certified FDD Product California Title 24 Part 6 Table 8 Economizer Module Left Hand Terminal Blocks LABEL TYPE DESCRIPTION Top Left Terminal Block MAT MAT 20k...

Page 29: ...D display and a 4 button keypad on the front of the economizer controller Keypad Use the four navigation buttons see Fig 48 to scroll through the menus and menu items select menu items and to change p...

Page 30: ...ETUP ADVANCED SETUP CHECKOUT ALARMS NOTE Some parameters in the menus use the letters MA or MAT indicating a mixed air temperature sensor location before the cooling coil This unit application has the...

Page 31: ..._ F if not connected short or out of range DA TEMP _ _ _ F 0 F to 140 F 18 C to 60 C DISCHARGE AIR TEMPERATURE after Heating section Displays when Discharge Air sensor is connected and displays measu...

Page 32: ...2 8 V 2 to 10 Vdc DCV MAXIMUM DAMPER POSITION Displays only if a CO2 sensor is connected Used for Vbz ventilation max cfm setpoint Displays 2 to 10 V if 3 sensors RA OA and MA In AUTO mode dampers con...

Page 33: ...SET 45 F 35 F to 55 F 2 C to 13 C Incremented by 10 F SUPPLY AIR TEMPERATURE LOW LIMIT Temperature to achieve Freeze Protection close damper and alarm if temperature falls below setup value FREEZE POS...

Page 34: ...r has failed or become disconnected check wiring then replace sensor if the alarm continues CO2 SENS ERR N A N A CO2 SENSOR ERROR CO2 sensor has failed gone out of range or become disconnected check w...

Page 35: ...tion settings and checkout menu readings see Table 13 See Tables 14 21 for dry bulb and enthalpy sequence of operation With stage 3 delay STG3 DLY in Advanced setup menu second stage of mechanical coo...

Page 36: ...v On 0 v Off VENTMIN to VENTMAX Closed On On High 24 v On 24 v On VENTMIN to VENTMAX Closed Yes Off Off High 0 v Off 0 v Off VENTMIN to VENTMAX Closed On Off High 0 v Off 0 v Off VENTMIN to Full Open...

Page 37: ...O Y2 O OCCUPIED UNOCCUPIED None No Off Off Low 0 v Off 0 v Off MIN POS L Closed On Off Low 24 v On 0 v Off MIN POS L Closed On On High 24 v On 24 v On MIN POS H Closed Yes Off Off Low 0 v Off 0 v Off...

Page 38: ...y for differential enthalpy The high limit boundary is ES1 when there are no stages of mechanical cooling energized and HL high limit when a compressor stage is energized Table 21 Enthalpy Operation w...

Page 39: ...ly items that are configured are shown in the Checkout menu NOTE For information about menu navigation and use of the keypad see Interface Overview on page 29 To perform a Checkout test 1 Scroll to th...

Page 40: ...mpling inlet to the sampling tube on the basepan 2 SPEED INDOOR FAN MOTOR SYSTEM WITH VARI ABLE FREQUENCY DRIVE FACTORY INSTALLED OPTION For details on operating RHH 2 stage cooling units equipped wit...

Page 41: ...he belt span length by 1 64 For example if the belt span length is 32 inches 32 x 1 64 1 2 inch deflection BELT FORCE DEFLECTION METHOD Check the belt tension with a spring force belt force deflec tio...

Page 42: ...ners www hvacpartners com TORQUE ALL SHEAVE SET SCREWS TO 110 130 in lbs SET SCREW SET SCREW STRAIGHT EDGE BELT SPAN BELT DEFLECTION FORCE SEE TABLE 1 DEFLECTION BELT SPAN 64 TABLE 1 TABLE 2 BELT CROS...

Page 43: ...opeller for location in housing orifice and verify setscrew is tight Y N _____ Verify that fan sheaves are aligned and belts are properly tensioned Y N _____ Verify that scroll compressors are rotatin...

Page 44: ...L2 _____________ L3 _____________ TEMPERATURES Outdoor air Temperature _____________ F DB Dry Bulb Return air Temperature _____________ F DB _____________ F Wb Wet Bulb Cooling Supply Air Temperature...

Reviews: