32

Specifications subject to change without notice.

516 01 3604 04

STATUS 

(cont)

ACTUATOR

N/A

OK/Alarm (on 

Alarm menu)

Displays ERROR if voltage or torque is below actuator range.

EXH1 OUT

OFF

ON/OFF

EXHAUST STAGE 1 RELAY OUTPUT

Output of EXH1 terminal:

ON = relay closed

OFF = relay open

EXH2 OUT

OFF

ON/OFF

EXHAUST STAGE 2 RELAY OUTPUT

Output of AUX terminal; displays only if AUX = EXH2

ERV

OFF

ON/OFF

ENERGY RECOVERY VENTILATOR

Output of AUX terminal; displays only if AUX = ERV

MECH COOL ON

or

HEAT STAGES ON

0

0, 1, or 2

Displays stage of mechanical cooling that is active.
Displays the stage of heat pump heating that is active.

FAN SPEED

N/A

LOW or HIGH

SUPPLY FAN SPEED

Displays speed setting of fan on a 2-speed fan unit.

W (HEAT ON)

N/A

ON/OFF

HEAT DEMAND STATUS

Displays status of heat demand on a 2-speed fan unit.

SETPOINTS

MAT SET

53F

38°F to 65°F

(3°C to 18°C);

 increment by 1°F

SUPPLY AIR SETPOINT

Setpoint determines where the economizer will modulate the OA 

damper to maintain the mixed air temperature.

LOW T LOCK

32F

–45 to 80 F

(–43°C to 27°C);

increment by 1°F

COMPRESSOR LOW TEMPERATURE LOCKOUT

Setpoint determines outdoor temperature when the mechanical 

cooling cannot be turned on. Commonly referred to as the 

Compressor lockout.

DRYBLB SET

63F

48°F to 80°F

(9°C to 27°C);

increment by 1°F

OA DRY BULB TEMPERATURE CHANGEOVER SETPOINT

Setpoint determines where the economizer will assume outdoor air 

temperature is good for free cooling; e.g.; at 63°F unit will economize 

at 62°F and below and not economize at 64°F and above. There is a 

2°F deadband.

ENTH CURVE

ES3

ES1,ES2,ES3,ES4, 

or ES5

ENTHALPY CHANGEOVER CURVE

Enthalpy boundary “curves” for economizing using single enthalpy.

DCV SET

1100 ppm

500 to 2000ppm; 

increment by 100

DEMAND CONTROLLED VENTILATION

Displays only if CO

2

 sensor is connected. Setpoint for Demand 

Controlled Ventilation of space. Above the setpoint, the OA dampers 

will modulate open to bring in additional OA to maintain a space ppm 

level below the setpoint.

MIN POS

2.8 V

2 to 10 Vdc

VENTILATION MINIMUM POSITION

Displays ONLY if a CO

2

 sensor is NOT connected.

VENTMAX 

With 2-speed fan units 

VENTMAX L (low speed 

fan) and VENTMAX H 

(high speed fan) 

settings are required

2.8 V

2 to 10 Vdc

DCV MAXIMUM DAMPER POSITION

Displays only if a CO

2

 sensor is connected. Used for Vbz (ventilation 

max cfm) setpoint. Displays 2 to 10 V if <3 sensors (RA,OA, and 

MA). In AUTO mode dampers controlled by CFM.

100 to 9990 cfm; 

increment

by 10

If OA, MA, RA, and CO

2

 sensors are connected and DCV CAL 

ENABLE is set to AUTO mode, the OA dampers are controlled by 

CFM and displays from 100 to 9990 CFM.

2 to 10 Vdc

With 2-speed fan units VENT L (low speed fan) and MIN POS H (high 

speed fan) settings are required. Default for VENTMAX L is 3.2V and 

VENTMAX H is 2.8V

VENTMIN 

With 2-speed 

fan units VENTMIN L 

(low 

speed fan) and 

VENTMIN 

H (high speed fan) set

2.25 V

2 to 10 Vdc or 100 

to 9990 cfm 

increment by 10

DCV MINIMUM DAMPER POSITION

Displays only if a CO

sensor is connected. Used for Ba (ventilation 

min cfm) setpoint. Displays 2 to 10 V if <3 sensors (RA, OA, and MA). 

Va is only set if DCV is used. This is the ventilation for less than 

maximum occupancy of the space. In AUTO mode dampers 

controlled by CFM.

100 to 9990 cfm; 

increment

by 10

If OA, MA, RA, and CO

2

 sensors are connected and DCV CAL 

ENABLE is set to AUTO mode, the OA dampers are controlled by 

CFM and displays from 100 to 9990 CFM.

2 to 10 Vdc

With 2-speed fan units VENTMIN L (low speed fan) and MIN POS H 

(high speed fan) settings are required. Default for VENTMIN L is 3.2V 

and VENTMIN H is 2.8V

ERV OAT SP

††

32°F

0°F to 50°F

(–18°C to 10°C);

increment by 1°F

ENERGY RECOVERY VENTILATOR UNIT OUTDOOR AIR 

TEMPERATURE SETPOINT

Only when AUX1 O = ERV

EXH1 SET 

With 2-speed fan units 

Exh1 L (low speed fan) 

and Exh1 H (high speed 

fan) settings are 

required

50%

0 to 100%;

increment by 1

EXHAUST FAN STAGE 1 SETPOINT

Setpoint for OA damper position when exhaust fan 1 is powered by 

the economizer.

With 2-speed fan units Exh1 L (low speed fan) and Exh1 H (high 

speed fan) settings are required. Default for Exh1 L is 65% and Exh1 

H is 50%

EXH2 SET 

With 2-speed fan units 

Exh2 L (low speed fan) 

and Exh2 H (high speed 

fan) settings are 

required

75%

0 to 100%; 

increment by 1

EXHAUST FAN STAGE 2 SETPOINT

Setpoint for OA damper position when exhaust fan 2 is powered by 

the economizer. Only used when AUX1 O is set to EHX2.

With 2-speed fan units Exh2 L (low speed fan) and Exh2 H (high 

speed fan) settings are required. Default for Exh2 L is 80% and Exh2 

H is 75%

Table 12 — 

Menu Structure* (cont)

MENU

PARAMETER

PARAMETER 

DEFAULT 

VALUE

PARAMETER 

RANGE AND 

INCREMENT

NOTES

Summary of Contents for RHH120

Page 1: ...RING DIAGRAMS Economi er X Factory Option 27 SYSTEM COMPONENTS SPECIFICATIONS INPUTS OUTPUTS ENVIRONMENTAL ECONOMIZER MODULE WIRING DETAILS INTERFACE OVERVIEW ENTHALPY SETTINGS TWO SPEED FAN OPERATION...

Page 2: ...t DANGER ELECTRICAL SHOCK HAZARD Failure to follow this warning will result in personal injury or death Before performing service or maintenance operations on unit turn off main power switch to unit a...

Page 3: ...Enthalpy Sensor P 2 Position Damper w Barometric Relief U Ultra Low Leak Economizer w Barometric Relief OA Temp Sensor W Ultra Low Leak Economizer w Barometric Relief Enthalpy Sensor Outdoor Air Optio...

Page 4: ...4 Specifications subject to change without notice 516 01 3604 04 Fig 2 Unit Dimensional Drawing Size 120 Units...

Page 5: ...516 01 3604 04 Specifications subject to change without notice 5 Fig 2 Unit Dimensional Drawing Size 120 Units cont...

Page 6: ...clearances LOCATION DIMENSION CONDITION A 48 in 1219 mm 18 in 457 mm 18 in 457 mm 12 in 305 mm Unit disconnect is mounted on panel No disconnect convenience outlet option Recommended service clearance...

Page 7: ...o the check valve core s bottom O ring Install the fitting body and torque to 96 10 in lbs 10 9 1 Nm Do not exceed 106 in lbs 11 9 Nm when tightening INSTALLATION Jobsite Survey Complete the following...

Page 8: ...ing 8 Make electrical connections 9 Install other accessories FRAME MOUNTED INSTALLATION Frame mounted applications generally follow the sequence for a curb installation Adapt the sequence as required...

Page 9: ...516 01 3604 04 Specifications subject to change without notice 9 Fig 6 Roof Curb Details REV 50TM500827...

Page 10: ...t is ready to be rigged and no longer will be lift ed by a fork truck the wood protector under the basepan must be removed Remove 4 screws from each base rail Wood protector will drop to the ground Se...

Page 11: ...iscard the supply duct cover Install accessory CRDUCTCV001A00 to cover the vertical supply duct open ing Use the return duct cover removed from the unit end panel to cover the vertical return duct ope...

Page 12: ...own form and assembled to a metal support tray using plastic stretch wrap Located in the return air compartment the assembly s metal tray is at tached to the basepan and also attached to the damper us...

Page 13: ...e hood sides See Fig 17 and 18 Secure hood divider with 3 screws on each hood side The hood divider is also used as the bottom filter rack for the aluminum filter 5 Attach the post that separates the...

Page 14: ...must be used to route the main power from the condenser end of the unit to either the factory option disconnect the bottom of the control box or the single point box accessory One inch conduit is pro...

Page 15: ...1 4 in female spade connector from the 230 v connection and moving it to the 200 v 1 4 in male terminal on the prima ry side of the transformer Refer to unit label diagram for ad ditional information...

Page 16: ...m deviation is 4 v Determine percent of voltage imbalance This amount of phase imbalance is satisfactory as it is below the maxi mum allowable 2 Operation on improper line voltage or excessive phase i...

Page 17: ...socket re install 3 hex screws on the NFD enclosure 12 Re install the unit front panel Fig 29 Handle and Shaft Assembly for NFD CONVENIENCE OUTLETS Two types of convenience outlets are offered on RHH...

Page 18: ...the bottom of the dis connect box For the load side wiring to the factory option disconnect route the wires through the hole on the right side of the disconnect Be sure to create a drip loop at least...

Page 19: ...conduits Connect the power con duit to the internal disconnect if unit is so equipped or to the external disconnect through unit side panel Remove one of the two knockouts located on the bottom left...

Page 20: ...ng valve position Reversing valves are ener gized during the cooling stages and the defrost cycle and de energized during heating cycles Once energized at the start of a cooling stage the reversing va...

Page 21: ...DI 24 vac P2 4 CTB Y2 W1 Heat 1 DI 24 vac P2 7 CTB W1 W2 Heat 2 DI 24 vac P2 6 CTB W2 R Power 24 vac P3 1 CONTL BRD 8 C Common 24 vac P3 2 CONTL BRD 4 DFT 1 DI 24 vac DFT 1 to DFT 1 DFT 2 DI 24 vac D...

Page 22: ...he bottom left side of the control box after removing one of the two knockouts in the corner of the box Using a connector at the control box to protect the wire as it passes into the control box Pull...

Page 23: ...can be installed in the unit Use the wir ing procedure listed below for each heater as determined by the number of stages in the heater Single Stage Heaters Single stage heaters will have an orange a...

Page 24: ...ce 516 01 3604 04 Fig 41 Accessory Electric Heater Control Connections NOTE Optional Outdoor Temperature Control at One Heater Stage Move either heater wire to this terminal and connect outdoor temper...

Page 25: ...25 Specifications subject to change without notice 516 01 3604 04 Fig 42 Typical RHH Control Wiring Diagram...

Page 26: ...26 Specifications subject to change without notice 516 01 3604 04 Fig 43 Typical RHH Power Wiring Diagram 208 230 3 60 unit shown...

Page 27: ...module includes terminals for CO2 sensor Mixed Air sensor and an Outdoor Dry Bulb sensor Enthalpy and other options are available with bus sensors User Interface The interface provides status for norm...

Page 28: ...040839 001 Rev G HJW10 www energy ca gov Certified FDD Product California Title 24 Part 6 Table 8 Economizer Module Left Hand Terminal Blocks LABEL TYPE DESCRIPTION Top Left Terminal Block MAT MAT 20k...

Page 29: ...D display and a 4 button keypad on the front of the economizer controller Keypad Use the four navigation buttons see Fig 48 to scroll through the menus and menu items select menu items and to change p...

Page 30: ...ETUP ADVANCED SETUP CHECKOUT ALARMS NOTE Some parameters in the menus use the letters MA or MAT indicating a mixed air temperature sensor location before the cooling coil This unit application has the...

Page 31: ..._ F if not connected short or out of range DA TEMP _ _ _ F 0 F to 140 F 18 C to 60 C DISCHARGE AIR TEMPERATURE after Heating section Displays when Discharge Air sensor is connected and displays measu...

Page 32: ...2 8 V 2 to 10 Vdc DCV MAXIMUM DAMPER POSITION Displays only if a CO2 sensor is connected Used for Vbz ventilation max cfm setpoint Displays 2 to 10 V if 3 sensors RA OA and MA In AUTO mode dampers con...

Page 33: ...SET 45 F 35 F to 55 F 2 C to 13 C Incremented by 10 F SUPPLY AIR TEMPERATURE LOW LIMIT Temperature to achieve Freeze Protection close damper and alarm if temperature falls below setup value FREEZE POS...

Page 34: ...r has failed or become disconnected check wiring then replace sensor if the alarm continues CO2 SENS ERR N A N A CO2 SENSOR ERROR CO2 sensor has failed gone out of range or become disconnected check w...

Page 35: ...tion settings and checkout menu readings see Table 13 See Tables 14 21 for dry bulb and enthalpy sequence of operation With stage 3 delay STG3 DLY in Advanced setup menu second stage of mechanical coo...

Page 36: ...v On 0 v Off VENTMIN to VENTMAX Closed On On High 24 v On 24 v On VENTMIN to VENTMAX Closed Yes Off Off High 0 v Off 0 v Off VENTMIN to VENTMAX Closed On Off High 0 v Off 0 v Off VENTMIN to Full Open...

Page 37: ...O Y2 O OCCUPIED UNOCCUPIED None No Off Off Low 0 v Off 0 v Off MIN POS L Closed On Off Low 24 v On 0 v Off MIN POS L Closed On On High 24 v On 24 v On MIN POS H Closed Yes Off Off Low 0 v Off 0 v Off...

Page 38: ...y for differential enthalpy The high limit boundary is ES1 when there are no stages of mechanical cooling energized and HL high limit when a compressor stage is energized Table 21 Enthalpy Operation w...

Page 39: ...ly items that are configured are shown in the Checkout menu NOTE For information about menu navigation and use of the keypad see Interface Overview on page 29 To perform a Checkout test 1 Scroll to th...

Page 40: ...mpling inlet to the sampling tube on the basepan 2 SPEED INDOOR FAN MOTOR SYSTEM WITH VARI ABLE FREQUENCY DRIVE FACTORY INSTALLED OPTION For details on operating RHH 2 stage cooling units equipped wit...

Page 41: ...he belt span length by 1 64 For example if the belt span length is 32 inches 32 x 1 64 1 2 inch deflection BELT FORCE DEFLECTION METHOD Check the belt tension with a spring force belt force deflec tio...

Page 42: ...ners www hvacpartners com TORQUE ALL SHEAVE SET SCREWS TO 110 130 in lbs SET SCREW SET SCREW STRAIGHT EDGE BELT SPAN BELT DEFLECTION FORCE SEE TABLE 1 DEFLECTION BELT SPAN 64 TABLE 1 TABLE 2 BELT CROS...

Page 43: ...opeller for location in housing orifice and verify setscrew is tight Y N _____ Verify that fan sheaves are aligned and belts are properly tensioned Y N _____ Verify that scroll compressors are rotatin...

Page 44: ...L2 _____________ L3 _____________ TEMPERATURES Outdoor air Temperature _____________ F DB Dry Bulb Return air Temperature _____________ F DB _____________ F Wb Wet Bulb Cooling Supply Air Temperature...

Reviews: