32
Specifications subject to change without notice.
516 01 3604 04
STATUS
(cont)
ACTUATOR
N/A
OK/Alarm (on
Alarm menu)
Displays ERROR if voltage or torque is below actuator range.
EXH1 OUT
OFF
ON/OFF
EXHAUST STAGE 1 RELAY OUTPUT
Output of EXH1 terminal:
ON = relay closed
OFF = relay open
EXH2 OUT
OFF
ON/OFF
EXHAUST STAGE 2 RELAY OUTPUT
Output of AUX terminal; displays only if AUX = EXH2
ERV
OFF
ON/OFF
ENERGY RECOVERY VENTILATOR
Output of AUX terminal; displays only if AUX = ERV
MECH COOL ON
or
HEAT STAGES ON
0
0, 1, or 2
Displays stage of mechanical cooling that is active.
Displays the stage of heat pump heating that is active.
FAN SPEED
N/A
LOW or HIGH
SUPPLY FAN SPEED
Displays speed setting of fan on a 2-speed fan unit.
W (HEAT ON)
N/A
ON/OFF
HEAT DEMAND STATUS
Displays status of heat demand on a 2-speed fan unit.
SETPOINTS
MAT SET
53F
38°F to 65°F
(3°C to 18°C);
increment by 1°F
SUPPLY AIR SETPOINT
Setpoint determines where the economizer will modulate the OA
damper to maintain the mixed air temperature.
LOW T LOCK
32F
–45 to 80 F
(–43°C to 27°C);
increment by 1°F
COMPRESSOR LOW TEMPERATURE LOCKOUT
Setpoint determines outdoor temperature when the mechanical
cooling cannot be turned on. Commonly referred to as the
Compressor lockout.
DRYBLB SET
63F
48°F to 80°F
(9°C to 27°C);
increment by 1°F
OA DRY BULB TEMPERATURE CHANGEOVER SETPOINT
Setpoint determines where the economizer will assume outdoor air
temperature is good for free cooling; e.g.; at 63°F unit will economize
at 62°F and below and not economize at 64°F and above. There is a
2°F deadband.
ENTH CURVE
ES3
ES1,ES2,ES3,ES4,
or ES5
ENTHALPY CHANGEOVER CURVE
Enthalpy boundary “curves” for economizing using single enthalpy.
DCV SET
1100 ppm
500 to 2000ppm;
increment by 100
DEMAND CONTROLLED VENTILATION
Displays only if CO
2
sensor is connected. Setpoint for Demand
Controlled Ventilation of space. Above the setpoint, the OA dampers
will modulate open to bring in additional OA to maintain a space ppm
level below the setpoint.
MIN POS
2.8 V
2 to 10 Vdc
VENTILATION MINIMUM POSITION
Displays ONLY if a CO
2
sensor is NOT connected.
VENTMAX
With 2-speed fan units
VENTMAX L (low speed
fan) and VENTMAX H
(high speed fan)
settings are required
2.8 V
2 to 10 Vdc
DCV MAXIMUM DAMPER POSITION
Displays only if a CO
2
sensor is connected. Used for Vbz (ventilation
max cfm) setpoint. Displays 2 to 10 V if <3 sensors (RA,OA, and
MA). In AUTO mode dampers controlled by CFM.
100 to 9990 cfm;
increment
by 10
If OA, MA, RA, and CO
2
sensors are connected and DCV CAL
ENABLE is set to AUTO mode, the OA dampers are controlled by
CFM and displays from 100 to 9990 CFM.
2 to 10 Vdc
With 2-speed fan units VENT L (low speed fan) and MIN POS H (high
speed fan) settings are required. Default for VENTMAX L is 3.2V and
VENTMAX H is 2.8V
VENTMIN
With 2-speed
fan units VENTMIN L
(low
speed fan) and
VENTMIN
H (high speed fan) set
2.25 V
2 to 10 Vdc or 100
to 9990 cfm
increment by 10
DCV MINIMUM DAMPER POSITION
Displays only if a CO
2
sensor is connected. Used for Ba (ventilation
min cfm) setpoint. Displays 2 to 10 V if <3 sensors (RA, OA, and MA).
Va is only set if DCV is used. This is the ventilation for less than
maximum occupancy of the space. In AUTO mode dampers
controlled by CFM.
100 to 9990 cfm;
increment
by 10
If OA, MA, RA, and CO
2
sensors are connected and DCV CAL
ENABLE is set to AUTO mode, the OA dampers are controlled by
CFM and displays from 100 to 9990 CFM.
2 to 10 Vdc
With 2-speed fan units VENTMIN L (low speed fan) and MIN POS H
(high speed fan) settings are required. Default for VENTMIN L is 3.2V
and VENTMIN H is 2.8V
ERV OAT SP
††
32°F
0°F to 50°F
(–18°C to 10°C);
increment by 1°F
ENERGY RECOVERY VENTILATOR UNIT OUTDOOR AIR
TEMPERATURE SETPOINT
Only when AUX1 O = ERV
EXH1 SET
With 2-speed fan units
Exh1 L (low speed fan)
and Exh1 H (high speed
fan) settings are
required
50%
0 to 100%;
increment by 1
EXHAUST FAN STAGE 1 SETPOINT
Setpoint for OA damper position when exhaust fan 1 is powered by
the economizer.
With 2-speed fan units Exh1 L (low speed fan) and Exh1 H (high
speed fan) settings are required. Default for Exh1 L is 65% and Exh1
H is 50%
EXH2 SET
With 2-speed fan units
Exh2 L (low speed fan)
and Exh2 H (high speed
fan) settings are
required
75%
0 to 100%;
increment by 1
EXHAUST FAN STAGE 2 SETPOINT
Setpoint for OA damper position when exhaust fan 2 is powered by
the economizer. Only used when AUX1 O is set to EHX2.
With 2-speed fan units Exh2 L (low speed fan) and Exh2 H (high
speed fan) settings are required. Default for Exh2 L is 80% and Exh2
H is 75%
Table 12 —
Menu Structure* (cont)
MENU
PARAMETER
PARAMETER
DEFAULT
VALUE
PARAMETER
RANGE AND
INCREMENT
†
NOTES