background image

SERVICE AND TECHNICAL SUPPORT MANUAL

Gas Furnace: N9MSE

Specifications  subject to change without notice.

440 04 4401 03

11

(Read following caution before changing taps.)

UNIT DAMAGE HAZARD

To avoid operating outside the rise range and avoid

component damage:
Refer to the Air Delivery Tables to determine which airflows

and settings are allowed for proper heating airflow. DO NOT

use the highlighted settings for heating airflow. The

highlighted settings are to be used for Cooling and

Continuous Fan ONLY.

CAUTION

!

Change the blower speed taps as required to maintain proper

temperature rise for Heating and Cooling as described above.

To change blower motor speed selections for heating mode,

remove blower motor lead from control HEAT terminal(s). (See

Figure 4

) Select desired blower motor speed lead(s) from the

other motor leads and relocate it/them to HEAT (heating blower

tap) terminal(s). Reconnect original lead on SPARE terminal.

Adjust Blower Off Delay (Heat Mode)

If desired, the main blower off time delay period may be

lengthened or shortened when operating in the heating mode

to provide greater comfort. For position and location of jumpers

on control center. (See 

Figure 4

 and 

Figure 15

)

The blower off-delay has four adjustable settings from 90 sec to

180 sec. (See 

Table 4

) To change the blower off delay setting,

move the jumper from one set of pins on the control to the pins

used for the desired blower off delay. Factory blower off-delay

setting is 120 sec.

Table 4

Blower Off Delay Jumper Positions

PINS

1 AND 2

2 AND 3

3 AND 4

4 AND 5

Time (in sec.)

90

120

150

180

Adjust Cooling Airflow

The cooling airflow can be set from the remaining blower speed

taps. Refer to the Air Delivery Tables in these instructions.

FURNACE OVERHEATING HAZARD

Failure to follow this caution may result in reduced furnace

life.
Recheck temperature rise. It must be within limits specified

on the rating plate. Recommended operation is at the

mid--point of rise range or slightly above.

CAUTION

!

Adjust Thermostat Heat Anticipator

Mechanical thermostat:

 Set thermostat heat anticipator to

match the amp. draw of the electrical components in the R-W

circuit. Accurate amp. draw readings can be obtained at the

wires normally connected to thermostat sub-base terminals, R

and W. The thermostat anticipator should NOT be in the circuit

while measuring current.

1. Remove thermostat from sub-base or from wall.
2. Connect an amp. meter across the R and W sub-base

terminals or R and W wires at wall.

3. Record amp. draw across terminals when furnace is in

low heat and after blower starts.

4. Set heat anticipator on thermostat per thermostat

instructions and install on sub-base or wall.

5. Install blower access door.

Electronic thermostat:

 Set cycle rate for 3 cycles per hr.

Figure 5

Amp. Draw Check with Ammeter

A96316

R Y W G

10 TURNS

THERMOSTAT SUBBASE

TERMINALS WITH

THERMOSTAT REMOVED

(ANITICIPATOR, CLOCK, ETC.,

MUST BE OUT OF CIRCUIT.)

HOOK-AROUND

AMMETER

EXAMPLE: 5.0 AMPS ON AMMETER

10 TURNS AROUND JAWS

 

=  0.5 AMPS FOR THERMOSTAT

     ANTICIPATOR SETTING

FROM UNIT 24-V

CONTROL TERMINALS

Check Safety Controls

The flame sensor, gas valve, and pressure switch were all

checked in the Start

up procedure section as part of normal

operation.

1. Check Main Limit Switch 

This control shuts off combustion system and energizes

air

circulating blower motor, if furnace overheats. By

using this method to check the temperature limit control,

it can be established that the limit is functioning properly

and that the limit will operate if there is a restricted

return

air supply or motor failure. If the limit control does

not function during this test, the cause must be

determined and corrected.

a. Run furnace for at least 5 minutes.
b. Gradually block off return air with a piece of

cardboard or sheet metal until the limit trips.

c. Unblock return air to permit normal circulation.

d. Burners will re

light when furnace cools down.

2. Check Pressure Switch(es) 

This control proves operation of the draft inducer blower.
a. Turn off 115

v power to furnace.

b. Disconnect inducer motor lead wires from wire

harness.

c. Turn on 115

v power to furnace.

d. Set thermostat to “call for heat” and wait 1 minute.

When low pressure switch is functioning properly, hot

surface  igniter should 

NOT 

glow and control

diagnostic light flashes a status code 3. If hot surface

igniter glows when inducer motor is disconnected,

shut down furnace immediately.

e. Determine reason low pressure switch did not

function properly and correct condition.

f. Turn off 115

v power to furnace.

g. Reconnect inducer motor wires, replace  door, and

turn on 115

v power.

h. Blower will run for 90 seconds before beginning the

call for heat again.

i. Furnace should ignite normally.

Summary of Contents for N9MSE0401410A

Page 1: ...s and or pictures or product labels The signal word WARNING is used throughout this manual in the following manner Safety alert symbol When you see this symbol on the unit and in instructions or manua...

Page 2: ...eath WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE...

Page 3: ...am of Furnace Drip Leg Gas Valve turned ON Type of Gas Natural Propane Filter Type and Size Check in box the Blower OFF Delay Jumper Heating Position for Fan Time OFF Setting 1 and 2 2 and 3 3 and 4 5...

Page 4: ...structure through drain tube Vent gases contain carbon monoxide which is tasteless and odorless WARNING 1 Remove upper and middle collector box drain plugs opposite of the condensate trap See Figure...

Page 5: ...altitude from local gas supplier 2 Obtain average yearly gas specific gravity from local gas supplier 3 Find installation altitude range for your installation in the manifold pressure tables in Table...

Page 6: ...e is outside this range change main burner orifices h When correct input is obtained replace cap that conceal gas valve regulator adjustment screw Main burner flame should be clear blue almost transpa...

Page 7: ...S CONNECTOR TRANSFORMER 24 VAC CONNECTIONS P2 HOT SURFACE IGNITOR HSI INDUCER MOTOR IND CONNECTOR 115 VAC L1 LINE VOLTAGE CONNECTION SPARE1 COM BLUE 115 VAC L2 NEUTRAL CONNECTIONS 24 V THERMOSTAT TERM...

Page 8: ...300 21 171 343 857 62 58 116 290 22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 9...

Page 9: ...42 3 4 42 3 5 42 3 6 3001 800 43 3 8 42 3 2 42 3 3 42 3 4 915 825 43 3 6 43 3 7 43 3 8 42 3 2 850 44 3 8 43 3 5 43 3 6 43 3 7 875 44 3 6 44 3 7 43 3 4 43 3 5 4000 900 44 3 4 44 3 5 44 3 7 44 3 8 1219...

Page 10: ...ding Leaving blower door off will result in incorrect temperature measurements due to possible changes in duct static pressure and airflow FURNACE DAMAGE HAZARD Failure to follow this caution may resu...

Page 11: ...minals R and W The thermostat anticipator should NOT be in the circuit while measuring current 1 Remove thermostat from sub base or from wall 2 Connect an amp meter across the R and W sub base termina...

Page 12: ...1785 1685 1580 1455 Yellow 2100 2030 1960 1885 1805 1720 1635 1545 1440 1305 Orange 1840 1810 1765 1725 1665 1590 1515 1430 1335 1240 Blue 1705 1685 1660 1615 1570 1510 1445 1370 1280 1135 Red 1425 14...

Page 13: ...nt location accordingly Figure 6 Multipoise Orientations A93041 Electrical Controls and Wiring ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death There may...

Page 14: ...D 6 A component test sequence will follow 7 Reinstall the Main Control door Component Self Test NOTE The furnace control component test allows all components to run for a short time except the gas val...

Page 15: ...rvice as necessary 4 Inspect burner compartment before each heating season for rust corrosion soot or excessive dust If necessary have furnace and burner serviced by a qualified service agency 5 Inspe...

Page 16: ...t on blower wheel remove wheel from the blower housing and wash it with an appropriate degreaser To remove wheel a Mark blower wheel location on shaft before disassembly to ensure proper reassembly b...

Page 17: ...old or damaging the mounting to the burner assembly ELECTRICAL SHOCK AND FIRE HAZARD Failure to follow this warning could result in personal injury death and or property damage Turn off the gas and el...

Page 18: ...ontrol door when complete Servicing Hot Surface Igniter The igniter does NOT require annual inspection Check igniter resistance before removal Refer to Figure 9 Figure 10 and Figure 11 1 Turn off gas...

Page 19: ...r drain extension elbow to the condensate trap 7 Connect the leads of the condensate heat pad if used 8 Connect external drain piping to the condensate drain elbow or drain extension pipe 9 Turn gas o...

Page 20: ...ratures may be 32_ F 0_ C or lower freeze protection measures must be taken to prevent property or product damage CAUTION Since the furnace uses a condensing heat exchanger some water will accumulate...

Page 21: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace N9MSE Specifications subject to change without notice 440 04 4401 03 21 Figure 14 Service Label 338310 2 Rev F...

Page 22: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace N9MSE Specifications subject to change without notice 22 440 04 4401 03 Figure 15 Wiring Diagram 339241 2 Rev A...

Page 23: ...nce Gas valve and humidifier will not be turned on Inducer motor will start and remain on until the end of the blower test then off The following components are on for 10 15 seconds each individually...

Page 24: ...nt test Does the igniter glow orange white by the end of the 15 second warm up period Unplug igniter harness from control and repeat component test Check for 115V between connector P2 HSI and NEUTRAL...

Page 25: ...is energized Simultaneously the electronic air cleaner terminal EAC is energized and remains energized as long as the blower motor BLWM is energized f Heat Off Delay When the thermostat is satisfied t...

Page 26: ...dule when used Inducer motor capacitor when used Collector box Condensate trap Condensate trap elbow Gaskets WARNING FIRE EXPLOSION ELECTRICAL SHOCK AND CARBON MONOXIDE POISONING HAZARD Failure to fol...

Page 27: ...Two stage FEATURE B Base AFUE Efficiency E Extra AFUE Efficiency C Communicating D Dual Certified 2 pipe or 1 pipe R 2 pipe only S Single stage T Two stage N Standard L Low Nox FEATURE 040 40 000 BTU...

Reviews: