10
46201200402
Specifications are subject to change without notice.
Table 1—Physical Data Con’t
UNIT SIZE
48090
48115
48130
60090
60115
60130
NOMINAL CAPACITY (ton)
4
4
4
5
5
5
SHIPPING WEIGHT lb
SHIPPING WEIGHT kg
480
218
480
218
480
218
497
225
497
225
497
225
COMPRESSOR / QUANTITY
Scroll / 1
REFRIGERANT (R---410A)
Quantity lb
Quantity (kg.)
9.2
4.2
9.2
4.2
9.2
4.2
9.8
4.4
9.8
4.4
9.8
4.4
REFRIGERANT METERING DEVICE
Orifice
ORIFICE ID in./mm
.080 / 2.03
.084 / 2.14
OUTDOOR COIL
Rows...Fins/in.
Face Area (sq ft)
1...21
21.4
1...21
21.4
1...21
21.4
1...21
23.3
1...21
23.3
1...21
23.3
OUTDOOR FAN
Nominal Cfm
Diameter in.
Diameter (mm)
Motor Hp (Rpm)
3600
26
660.4
1/5 (810)
3600
26
660.4
1/5 (810)
3600
26
660.4
1/5 (810)
4200
26
660.4
1/5 (810)
4200
26
660.4
1/5 (810)
4200
26
660.4
1/5 (810)
INDOOR COIL
Rows...Fins/in.
Face Area (sq ft)
3...17
4.7
3...17
4.7
3...17
4.7
3...17
5.6
3...17
5.6
3...17
5.6
INDOOR BLOWER
Nominal Cooling Airflow (Cfm)
Size in.
Size (mm)
Motor HP (RPM)
1550
1550
1550
1750
1750
1750
1550
11x10
279.4x254
1.0 (1075)
1550
11x10
279.4x254
1.0 (1075)
1550
11x10
279.4x254
1.0 (1075)
1750
11x10
279.4x254
1.0 (1040)
1750
11x10
279.4x254
1.0 (1040)
1750
11x10
279.4x254
1.0 (1040)
FURNACE SECTION*
Burner Orifice No. (Qty...Drill Size)
1 & 3 Phase Natural Gas (Factory Installed)
1 & 3 Phase Propane Gas
3...38
3...53
3...33
3...51
3...31
3...49
3...38
3...53
3...33
3...51
3...31
3...49
HIGH---PRESSURE SWITCH
(psig) Cut---out Reset (Auto)
650 +/--- 15
420 +/--- 25
LOSS---OF CHARGE / LOW---PRESSURE
SWITCH (Liquid Line) (psig) cut---out Reset
(auto)
20 +/--- 5
45 +/--- 10
N/A
RETURN---AIR FILTERS Throwaway
†
}
in.
mm
1 each 24x14x1
610x356x25
24x15x1
610x406x25
1 each 24x16x1
610x406x25
24x18x1
610x457x25
*Based on altitude of 0 to 2000 ft (0---610 m).
{
Required filter sizes shown are based on the larger of the AHRI (Air Conditioning Heating and Refrigeration Institute) rated cooling airflow or the heating air-
flow velocity of 300 to 350 ft/minute for throwaway type. Air filter pressure drop for non---standard filters must not exceed 0.08 IN. W.C.
}
If using accessory filter rack refer to the filter rack installation instructions for correct filter sizes and quantity.
Table 2 – Maximum Gas Flow Capacity*
NOMINAL
IRON PIPE
SIZE (IN.)
INTERNAL
DIAMETER
(IN.)
LENGTH OF PIPE FT (m)†
10
(3)
20
(6)
30
(9)
40
(12)
50
(15)
60
(18)
70
(21)
80
(24)
90
(27)
100
(30)
125
(38)
150
(46)
175
(53)
200
(61)
1/2
.622
175
120
97
82
73
66
61
57
53
50
44
40
—
—
3/4
.824
360
250
200
170
151
138
125
118
110
103
93
84
77
72
1
1.049
680
465
375
320
285
260
240
220
205
195
175
160
145
135
1---1/4
1.380
1400
950
770
600
580
530
490
460
430
400
360
325
300
280
1---1/2
1.610
2100
1460
1180
990
900
810
750
690
650
620
550
500
460
430
*Capacity of pipe in cu ft of gas per hr for gas pressure of 0.5 psig or less. Pressure drop of 0.5---IN. W.C. (based on a 0.60 specific gravity gas). Refer to Table 2
and National Fuel Gas Code NFPA 54/ANSI Z223.1.
{
This length includes an ordinary number of fittings.
Step 6 — Connect Condensate Drain
NOTE
: When installing condensate drain connection be sure to
comply with local codes and restrictions.
This unit disposes of condensate water through a 3/4 in. NPT
fitting which exits through the base on the evaporator coil access
side. See Fig. 3--6 for location.
Condensate water can be drained directly onto the roof in rooftop
installations (where permitted) or onto a gravel apron in ground
level installations. Install a field--supplied 2--in. (51 mm)
condensate trap at the end of condensate connection to ensure
proper drainage. Make sure that the outlet of the trap is at least 1 in.
(25 mm) lower than the drain--pan condensate connection to
prevent the pan from overflowing (See Fig. 9). Prime the trap with
water. When using a gravel apron, make sure it slopes away from
the unit.
Connect a drain tube using a minimum of 3/4--in. PVC or 3/4--in.
copper pipe (all field--supplied) at the outlet end of the 2--in. (51
mm) trap. Do not undersize the tube. Pitch the drain tube
downward at a slope of at least 1--in. (25 mm) for every 10 ft (3.1
m) of horizontal run. Be sure to check the drain tube for leaks.
TRAP
OUTLET
1-in. (25 mm) min.
2-in. (51 mm) min.
A09052
Fig. 9 -- Condensate Trap
P
G
D4,
P
GS
4,
W
P
G4