AIRFLOW PERFORMANCE -- CFM at a given Speed and Static reading (continued)
Model (* = 2 or 4)
Measured Static Pressure, inlet to outlet (inches water column)
Blower Speed
Model (* = 2 or 4)
0.60
0.50
0.40
0.30
0.20
0.10
Blower Speed
FSM*X4800
FSU*X4800
High
1902
1824
1743
1659
1571
1479
Medium
1830
1763
1690
1611
1527
1436
Low
1625
1584
1531
1465
1387
1296
FEM*X6000
High
2057
2024
1989
1954
1916
1878
Medium
1799
1766
1731
1695
1658
1618
Low
1667
1633
1596
1558
1517
1475
FSM*X6000
FSU*X6000
High
2128
2050
1965
1875
1778
1674
Medium
1959
1898
1829
1750
1663
1566
Low
1748
1709
1659
1598
1525
1442
NOTES:
1. Airflow based on dry coil at 230V with factory approved filter and electric heater
(2 element heater for model sizes 1800 -- 3600, 3 element heater for model sizes 4200 -- 6000)
2. Not recommended for use above 0.60 inches water column external static pressure.
3. Shaded cells indicate airflow is greater than 450 CFM per ton.
STATIC PRESSURE CORRECTION FROM DRY TO WET COIL (inches of water column)
Airflow performance chart above was developed using fan coils with DRY coils.
When taking a static reading across a WET coil, adjust the static pressure numbers above by
adding
the values in
this table (for a given CFM, wet coil will have greater static pressure drop than dry coil).
Model Size
CFM
500
600
700
800
900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000
1800 (all)
.034 .049 .063
--
--
--
--
--
--
--
--
--
--
--
--
--
2400 (all)
.016 .027 .038 .049 .059
--
--
--
--
--
--
--
--
--
--
--
3000 (all)
--
--
--
.049 .059 .070 .080
--
--
--
--
--
--
--
--
--
3500 (FEM)
3600 (FSU)
--
--
--
--
--
.055 .064 .073 .081
--
--
--
--
--
--
--
3600 (FEM)
3600 (FSM)
--
--
--
--
--
.034 .042 .049 .056
--
--
--
--
--
--
--
4200 (all)
--
--
--
--
--
--
--
.049 .056 .063 .070
--
--
--
--
--
4800 (all)
--
--
--
--
--
--
--
--
--
.038 .043 .049 .054 .059
--
--
6000 (all)
--
--
--
--
--
--
--
--
--
--
--
.027 .031 .035 .039 .043
STATIC PRESSURE DROP ACROSS FILTER (inches of water column)
Model Size
CFM
400
600
800
1000
1200
1400
1600
1800
2000
1800
.020
.044
.075
--
--
--
--
--
--
2400
--
.044
.075
.110
--
--
--
--
--
3000
--
--
.048
.072
.100
--
--
--
--
3500 & 3600
--
--
--
.072
.100
.130
--
--
--
4200
--
--
--
--
.070
.092
.120
--
--
4800
--
--
--
--
--
.092
.120
.152
--
6000
--
--
--
--
--
--
.120
.152
.187