SERVICE MANUAL
R
−
410A Ductless Split System: DLF4(A/H), DLC4(A/H)
421 08 9204 00
25
ELECTRICAL DATA
Table 2
−
Accessory
Condensate Pump Kit Contents
Electrical Data Table
Unit
Size
System Voltage
Volts
−
Ph.
−
Freq.
Operating
Voltage
Compressor
Outdoor Fan
Indoor Fan
MCA
Max
Fuse/CB
Amps
(MOCP)
RLA
LRA
FLA
HP
Output
Watts
Volts
FLA
HP
Output
Watts
(Min/Max)
9K
115
−
1
−
60
103/127
16.03
33
0.17
0.054
30
115 V
−
AC
0.38
0.056
20
22
35
12K
115
−
1
−
60
103/127
17.53
33
0.17
0.058
30
115 V
−
AC
0.38
0.056
20
23
40
12K
208/230
−
1
−
60
187/253
6.47
13.8
0.14
0.058
30
208/230 V
−
AC
0.20
0.056
20
10
15
18K
208/230
−
1
−
60
187/253
9.70
13.8
0.32
0.156
60
208/230 V
−
AC
0.28
0.075
20
13
20
24K
208/230
−
1
−
60
187/253
11.04
18.5
1.10
0.224
90
176
−
375V
−
DC 0.24
0.068
60
16
25
30K
208/230
−
1
−
60
187/253
13.45
40
0.45
0.228
100
208/230 V
−
AC
0.40
0.106
40
20
30
36K
−
AC
208/230
−
1
−
60
187/253
16.92
67
0.73
0.268
170
208/230 V
−
AC
0.47
0.114
60
24
35
36K
−
HP
208/230
−
1
−
60
187/253
17.50
67
0.73
0.268
170
208/230 V
−
AC
0.47
0.114
60
24
40
LEGEND
FLA
−
Full Load Amps
LRA
−
Locked Rotor Amps
MCA
−
Minimum Circuit Amps
RLA
−
Rated Load Amps
MOCP
−
Maximum Over Current Protection
WIRING
The main power is supplied to the outdoor unit. The field
supplied connecting cable from the outdoor unit to indoor unit
consists of four wires and provides the power for the indoor unit
as well as the communication signal and ground between the
outdoor and indoor unit.
Two wires are high voltage AC power, one is low voltage DC
signal and one is a ground wire.
Consult local building codes, NEC (National Electrical Code) or
CEC (Canadian Electrical Code) for special requirements.
Voltage drop on the connecting cable should be kept to a
minimum. Use cable size and max length below:
18 AWG
50 ft. (16m)
16 AWG
100 ft. (33m)
CAUTION
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Use copper conductors only with a minimum 300 volt
rating and 2/64 inch thick insulation.
CAUTION
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Be sure to comply with local codes while running wire from
indoor unit to outdoor unit.
Every wire must be connected firmly. Loose wiring may
cause terminal to overheat or result in unit malfunction. A
fire hazard may also exist. Therefore, be sure all wiring is
tightly connected.
No wire should be allowed to touch refrigerant tubing,
compressor or any moving parts.
Disconnecting means must be provided and shall be
located within sight and readily accessible from the air
conditioner.
Connecting cable with conduit shall be routed through
hole in the conduit panel.