background image

SERVICE AND TECHNICAL SUPPORT MANUAL

Gas Furnace: (F/G)9MVE

Specifications  subject to change without notice.

440 04 4801 03

30

Sequence of Operation

NOTE

:  Furnace control must be grounded for proper operation

or else control will lock out. Control is grounded through

green/yellow wire routed to gas valve and burner box screw.
Using the schematic diagram in 

Figure 16

, follow the sequence

of operation through the different modes. Read and follow the

wiring diagram very carefully.

NOTE

:  If a power interruption occurs during a call for heat

(W/W1 or W/W1

and

W2), the control will start a 90

second

blower

only ON period two seconds after power is restored, if

the thermostat is still calling for gas heating. The amber LED
light will flash code 1+2 during the 90

second period, after

which the LED will flash a heartbeat (bright

dim), as long as no

faults are detected. After the 90

second period, the furnace will

respond to the thermostat normally.
The blower door must be installed for power to be conducted

through the blower door interlock switch ILK to the furnace

control CPU, transformer TRAN, inducer motor IDM, blower

motor BLWM, hot

surface igniter HSI, and gas valve GV.

1. Two

Stage Heating (Adaptive Mode) with

Single

Stage Thermostat

NOTE

:  The low

heat only switch SW1

2 selects either the

low

heat only operation mode when ON, (see item 2. below) or

the adaptive heating mode when OFF in response to a call for

heat. (See 

Figure 5

) When the W2 thermostat terminal is

energized it will always cause high

heat operation when the

R

to

W circuit is closed, regardless of the setting of the

low

heat only switch. This furnace can operate as a two

stage

furnace with a single

stage thermostat because the furnace

control CPU includes a programmed adaptive sequence of

controlled operation, which selects low

heat or high

heat

operation. This selection is based upon the stored history of the
length of previous gas

heating periods of the single

stage

thermostat.
The furnace will start up in either low

 or high

heat. If the

furnace starts up in low

heat, the control CPU determines the

low

heat on

time (from 0 to 16 minutes) which is permitted

before switching to high

heat.

If the power is interrupted, the stored history is erased and the

control CPU will select low

heat for up to 16 minutes and then

switch to high

heat, as long as the thermostat continues to call

for heat. Subsequent selection is based on stored history of the

thermostat cycle times.
The wall thermostat “calls for heat”, closing the R

to

W circuit.

The furnace control performs a self

check, verifies the

low

heat and high

heat pressure switch contacts LPS and

HPS are open, and starts the inducer motor IDM in

high

speed.

a.

Inducer Prepurge Period

(1.)  If the furnace control CPU selects low

heat

operation the inducer motor IDM comes up to

speed, the low

heat pressure switch LPS closes,

and the furnace control CPU begins a

15

second prepurge period. If the low

heat

pressure switch LPS fails to remain closed the

inducer motor IDM will remain running at

high

speed. After the low

heat pressure switch

re

closes the furnace control CPU will begin a

15

second prepurge period, and continue to run

the inducer motor IDM at high

speed.

(2.) If the furnace control CPU selects high

heat

operation, the inducer motor IDM remains

running at high

speed, and the high

heat

pressure switch relay HPSR is de

energized to

close the NC contact. When sufficient pressure is

available the high

heat pressure switch HPS

closes, and the high

heat gas valve solenoid

GV

HI is energized. The furnace control CPU

begins a 15

second prepurge period after the

low

heat pressure switch LPS closes. If the

high

heat pressure switch HPS fails to close and

the low

heat pressure switch LPS closes, the

furnace will operate at low

heat gas flow rate

until the high

heat pressure switch closes for a

maximum of 2 minutes after ignition.

b.

Igniter Warm

Up

 

At the end of the prepurge period,

the Hot

Surface Igniter HSI is energized for a

17

second igniter warm

up period.

c.

Trial

For

Ignition Sequence

 

When the igniter

warm

up period is completed the main gas valve

relay contact GVR closes to energize the gas valve

solenoid GV

M. The gas valve solenoid GV

M

permits gas flow to the burners where it is ignited by

the HSI. Five seconds after the GVR closes, a

2

second flame proving period begins. The HSI

igniter will remain energized until the flame is sensed

or until the 2

second flame proving period begins. If

the furnace control CPU selects high

heat operation,

the high

heat gas valve solenoid GV

HI is also

energized.

d.

Flame

Proving

 

 When the burner flame is proved

at the flame

proving sensor electrode FSE, the

inducer motor IDM switches to low

speed unless the

furnace is operating in high

heat, and the furnace

control CPU begins the blower

ON delay period and

continues to hold the gas valve GV

M open. If the

burner flame is not proved within two seconds, the

control CPU will close the gas valve GV

M, and the

control CPU will repeat the ignition sequence for up

to three more Trials

For

Ignition before going to

Ignition

Lockout. Lockout will be reset automatically

after three hours, or by momentarily interrupting 115

vac power to the furnace, or by interrupting 24 vac

power at SEC1 or SEC2 to the furnace control CPU

(not at W/W1, G, R, etc.). If flame is proved when

flame should not be present, the furnace control CPU

will lock out of Gas

Heating mode and operate the

inducer motor IDM on high speed until flame is no

longer proved.

e.

Blower

On delay

 

 If the burner flame is proven the

blower

ON delays for low

heat and high

heat are as

follows: 

Low

heat 

 45 seconds after the gas valve GV

M is

opened the blower motor BLWM is turned ON at

low

heat airflow. 

High

heat 

 25 seconds after the gas valve GV

M is

opened the BLWM is turned ON at high

heat airflow.

Simultaneously, the humidifier terminal HUM and

electronic air cleaner terminal EAC

1 are energized

and remain energized throughout the heating cycle.

f.

Switching from Low

 to High

Heat

 

 If the furnace

control CPU switches from low

heat to high

heat, the

furnace control CPU will switch the inducer motor

IDM speed from low to high. The high

heat pressure

switch relay HPSR is de

energized to close the NC

contact. When sufficient pressure is available the

high

heat pressure switch HPS closes, and the

high

heat gas valve solenoid GV

HI is energized.

The blower motor BLWM will transition to high

heat

airflow five seconds after the furnace control CPU

switches from low

heat to high

heat.

g.

Switching from High

 to Low

Heat

 

The furnace

control CPU will not switch from high

heat to

low

heat while the thermostat R

to

W circuit is

closed when using a single

stage thermostat.

h.

Blower

Off Delay

 

When the thermostat is satisfied,

the R to W circuit is opened, de

energizing the gas

Summary of Contents for A3 Series

Page 1: ...tures or product labels The signal word WARNING is used throughout this manual in the following manner Safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert...

Page 2: ...eath WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE...

Page 3: ...in Connected Condensate Drain Trapped Manual Gas Shut off Upstream of Furnace Drip Leg Gas Valve turned ON Type of Gas Natural Propane Filter Type and Size Shade in Final Furnace Settings Below O N O...

Page 4: ...l Setup Switches SW1 The furnace control has 8 setup switches that may be set to meet the application requirements To set these setup switches for the appropriate requirement 1 Remove blower door 2 Lo...

Page 5: ...soap solution made specifically for the detection of leaks to check all connections A fire or explosion may result causing property damage personal injury or loss of life WARNING Adjustments FIRE HAZ...

Page 6: ...0 Btu cu ft Specific gravity 0 62 Therefore Orifice No 44 Furnace is shipped with No 44 orifices In this example all main burner orifices are the correct size and do not need to be changed to obtain p...

Page 7: ...ease input rate Figure 3 Redundant Automatic Gas Control Valve 2 Stage without Tower Pressure Ports ON OFF Switch Regulator Seal Cap RegulatorAdjustment Regulator Seal Cap under Cap 1 2 NPT Outlet 1 8...

Page 8: ...s warning could result in personal injury death and or property damage Manifold pressure tap set screw must be tightened or 1 8 in NPT pipe plug must be installed to prevent gas leaks WARNING c Tighte...

Page 9: ...300 21 171 343 857 62 58 116 290 22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48...

Page 10: ...43 3 8 1 6 42 3 2 1 4 850 44 3 8 1 6 43 3 5 1 5 43 3 6 1 5 43 3 7 1 6 875 44 3 6 1 5 44 3 7 1 6 43 3 4 1 4 43 3 5 1 5 4000 900 44 3 4 1 4 44 3 5 1 5 44 3 7 1 5 44 3 8 1 6 1219 925 44 3 2 1 4 44 3 4 1...

Page 11: ...re and airflow FURNACE DAMAGE HAZARD Failure to follow this caution may result in S Overheating the heat exchangers or condensing flue gases in heat exchanger areas not designed for condensate S Short...

Page 12: ...r off delay See Table 4 and Figure 4 Figure 5 Table 4 Blower Speed Taps DESIRED HEATING MODE BLOWER OFF DELAY SEC SETUP SWITCH SW1 7 and 8 POSITION 90 OFF OFF 120 ON OFF 150 OFF ON 180 ON ON Adjust Co...

Page 13: ...r refer to unit wiring diagram TWN 1 CFM 2 3 4 5 6 7 8 SW2 CF AC SW2 1 Twining OFF Allows for selection of furnace Main OFF or Secondary ON when Twinned furnace setup is required See kit instructions...

Page 14: ...this method to check limit control it can be established that limit is functioning properly and will operate if there is a restricted return air supply or motor failure If limit control does not funct...

Page 15: ...FF OFF ON 605 565 510 455 420 See note 4 OFF ON OFF 785 750 705 675 630 585 See note 4 OFF ON ON 955 920 895 860 825 785 755 720 685 650 ON OFF OFF 1135 1110 1080 1055 1020 990 935 880 825 745 ON OFF...

Page 16: ...0 22 Clg Default OFF OFF OFF 2010 1960 1910 1850 1800 1750 1690 1645 1565 1480 Cooling SW2 OFF OFF ON 1015 805 645 550 480 See note 4 OFF ON OFF 1075 975 915 835 765 See note 4 OFF ON ON 1205 1135 105...

Page 17: ...itioned air is discharged upward Since this furnace can be installed in any of the 4 positions shown in Figure 7 you must revise your orientation to component location accordingly Figure 7 Multipoise...

Page 18: ...isconnecting the limit switch To retrieve Status Codes follow the procedure below 2 Turn Setup Switch SW1 1 ON 3 Manually close blower door switch 4 Control will flash up to 7 Status Codes 5 The last...

Page 19: ...eason Service as necessary 4 Inspect burner compartment before each heating season for rust corrosion soot or excessive dust If necessary have furnace and burner serviced by a qualified service agency...

Page 20: ...balance will be affected 7 If greasy residue is present on blower wheel remove wheel from the blower housing and wash it with an appropriate degreaser To remove wheel a Mark blower wheel location on s...

Page 21: ...following items must be performed by a qualified service technician If the burners develop an accumulation of light dirt or dust they may be cleaned by using the following procedure NOTE Use a back up...

Page 22: ...the Hot Surface Igniter NOTE Use propane resistant pipe dope to prevent leaks Do not use Teflon tape 13 Install the gas pipe to the gas valve Figure 12 Igniter Position Side View L12F041 2 in 2 5 mm...

Page 23: ...quired Verify a condensate trap gasket is included in the service kit or obtain one from your local distributor 1 Disconnect power at external disconnect fuse or circuit breaker 2 Turn off gas at exte...

Page 24: ...wiring diagram and reconnect wires to flame rollout switch gas valve igniter and flame sensor 10 Turn on gas and electrical supplies to furnace 11 Check furnace operation through two complete heat op...

Page 25: ...uart of anti freeze solution into the funnel tube Antifreeze should run through the collector box overfill condensate trap and flow to an open drain 8 Replace the rubber plug in the port on the collec...

Page 26: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace F G 9MVE Specifications subject to change without notice 440 04 4801 03 26 Figure 15 Service Label 340688 2 REV D...

Page 27: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace F G 9MVE Specifications subject to change without notice 27 440 04 4801 03 Figure 16 Wiring Diagram 340688 2 REV D...

Page 28: ...t flashes When done put setup switch SW1 1 in the OFF position Was there a previous status code other than the heartbeat Go to section below for the status code that was flashed Does the control respo...

Page 29: ...t check manifold pressure If OK check burner carryover and flame sensor location Clean flame sensor with fine steel wool and recheck current Nominal current is 4 0 to 6 0 microamps Is current near typ...

Page 30: ...t high speed and the high heat pressure switch relay HPSR is de energized to close the NC contact When sufficient pressure is available the high heat pressure switch HPS closes and the high heat gas v...

Page 31: ...tor BLWM will continue operating at cooling airflow for an additional 90 seconds Jumper Y Y2 to DHUM to reduce the cooling off delay to 5 seconds See Figure 4 b Two Stage Thermostat and Two Speed Cool...

Page 32: ...eat pump the furnace control automatically changes the timing sequence to avoid long blower off times during demand defrost cycles Whenever W W1 is energized along with Y1 or Y Y2 the furnace control...

Page 33: ...801 03 Figure 20 Variable Speed Furnace with Single Stage Heat Pump Dual Fuel L09F026 NOTE 9 Figure 21 Variable Speed Furnace with Two Stage Heat Pump Dual Fuel L09F028 NOTE 9 Figure 22 Variable Speed...

Page 34: ...stallation Instructions for additional information and setup procedure 4 When using a Humidity Sensing Thermostat set DEHUMIDIFY OPTIONS to H DE ENRGZD FOR DEHUM 5 Optional connection If wire is conne...

Page 35: ...ector box Condensate trap Condensate trap elbow Gaskets WARNING FIRE EXPLOSION ELECTRICAL SHOCK AND CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in dangerous operation...

Page 36: ...ed X ECM S Single stage T Two stage FEATURE B Base AFUE Efficiency E Extra AFUE Efficiency C Communicating D Dual Certified 2 pipe or 1 pipe R 2 pipe only S Single stage T Two stage N Standard L Low N...

Reviews: