![background image](http://html1.mh-extra.com/html/icp-das-usa/wf-2015/wf-2015_user-manual_3572603053.webp)
WF-2000 Series AIO
User’s Manual (RevB1.0, Oct./2016) ------------- 53
Table
5-8 (4xxxx) AO address
Begin Address
Points
Descriptions
Range
Access Type
40248
1
Reset System
1= Reset System
247= Restore to Factory
Default Settings
W
5.3.3
WF-2019 I/O Address Mapping
Table
5-9 (3xxxx) AI address
Begin Address
Points
Descriptions
Range
Access Type
30001
1~10
Analog Input
-32768 ~ +32767 (Bipolar)
0 ~ +65535 (Unipolar)
R
30011
1
CJC data
-300 ~ +1000
R
Table
5-10 (4xxxx) AO address
Begin Address
Points
Descriptions
Range
Access Type
40248
1
Reset System
1= Reset System
247= Restore to Factory
Default Settings
W
5.3.4
WF-2026 I/O Address Mapping
Table
5-11 (3xxxx) AI address
Begin Address
Points
Descriptions
Range
Access Type
30001
1~5
Analog Input
-32768 ~ +32767 (Bipolar)
0 ~ +65535 (Unipolar)
R
Table
5-12 (4xxxx) AO address
Begin Address
Points
Descriptions
Range
Access Type
40001
1~2
Analog Output
-32768 ~ +32767 (Bipolar)
0 ~ +65535 (Unipolar)
R/W