UA-5000 Series User Manual V.1.0.0 ICP DAS
8
1.4.
Software Specifications
Model
UA-5000 Series
OPC UA
OPC UA Server
OPC Unified Architecture: 1.02
Core Server Facet
Data Access Server Facet
Method Server Facet
Client Redundancy Facet
UA-TCP UA-SC UA Binary
User Token User Name Password & X509 Certificate
Security Policy
○
None
○
Basic128Rsa15
• Sign
• Sign & Encrypt
○
Basic256
• Sign
• Sign & Encrypt
Modbus Master
Modbus TCP
To read or control the devices that support standard Modbus TCP Slave
protocol. Recommend to keep the maximum number of devices within 100
connections.
Modbus RTU
A max. of 3 ports: ttyO2, ttyO4, ttyO5 to connect other Modbus RTU Slave
devices (e.g. M-7000). Recommend no more than 32 devices per port for
better communication quality.
MQTT
MQTT Client
Connect the MQTT Broker to read/control the devices supporting the
MQTT protocol.
MQTT Service
Connect the MQTT Broker to externally read/control the devices supporting
other protocols that linking with the UA-5000 series.
MQTT Broker
Compliance with MQTT v3.1.1 protocol. Support MQTT message
distribution management.
Recommend to keep the connection number of Client within 400.
Virtual Device
PID Function
Combine the remote I/O devices for the PID logic control system.
Summary of Contents for UA-5000 series
Page 9: ...UA 5000 Series User Manual V 1 0 0 ICP DAS 9 1 5 Appearance ...
Page 10: ...UA 5000 Series User Manual V 1 0 0 ICP DAS 10 ...
Page 23: ...UA 5000 Series User Manual V 1 0 0 ICP DAS 23 Step 7 Save all settings ...
Page 30: ...UA 5000 Series User Manual V 1 0 0 ICP DAS 30 Step 6 Save all settings ...
Page 35: ...UA 5000 Series User Manual V 1 0 0 ICP DAS 35 Step 9 Save all settings ...
Page 51: ...UA 5000 Series User Manual V 1 0 0 ICP DAS 51 3 Click Save to save the current settings ...
Page 58: ...UA 5000 Series User Manual V 1 0 0 ICP DAS 58 3 Click Save to save current settings ...