background image

 

tM-AD8C 8-channel Current Analog Input Module

- QuickStart (Jun/2016)  

ICP DAS USA, Inc.

 

www.icpdas-usa.com

 | 1-310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717

 

 

3. Block/ Wiring Diagram 

 

 

 

  Use 26-12 AWG wire for signal connections. 

  Strip the wire to a length of 7±0.5mm. 

  Use a crimp terminal for wiring. 

  Avoid high-voltage cables and power equipment as much as possible. 

  For RS-485 communication, use insulated and twisted pair 24 AWG wire, e.g. 

Belden 9841. 
 
 

4. Default Settings 

 

Default settings for the tM AD modules are as follows:  

 Protocol: Modbus RTU  

 Module Address: 01  

 Analog Input Type: type code 08, -10V to 10V  

 Baud Rate: 9600 bps 

 