background image

ICP DAS CO., LTD. 

         

Copyright © 2013 ICP DAS Co., Ltd. All Rights Reserved. 

 E-mail: [email protected] 

tM

-A

D

4

P

2

C

2

 Q

u

ic

k

 S

ta

rt

 G

u

id

e

 

11

 

Address 

Description 

Attribute 

00073 ~ 00074 

10073 ~ 10074 

High latched value of DO 

00097 ~ 00098 

10097 ~ 10098 

Low latched value of DI 

00105 ~ 00106 

10105 ~ 10106 

Low latched value of DO 

00225 ~ 00228 

10225 ~ 10228 

Over/under range status of analog input channel 0 to 3 

for 4 ~ 20mA or 0 ~ 20mA ranges 

00001 ~ 00002 

Digital output value of channel 0 to 1 

R/W 

00129 ~ 00130 

Safe value of digital output channel 0 to 1 

R/W 

00161 ~ 00162 

Power on value of digital output channel 0 to 1 

R/W 

00193 ~ 00194 

Counter update trigger edge of digital input channel 0 

to 1 

R/W 

00257 

Protocol, 0: DCON, 1: Modbus RTU 

R/W 

00258 

Protocol, 0: determined by 00257, 1: Modbus ASCII 

R/W 

00260 

Modbus host watchdog mode 

0: same as I-7000 

1: can use AO and DO command to clear host 

watchdog timeout status 

R/W 

00261 

1: enable, 0: disable host watchdog 

R/W 

00264 

Write 1 to clear latched DIO states 

00265 

DI active state 

R/W 

00266 

DO active state 

R/W 

00269 

Modbus data format, 0: hex, 1: engineering 

R/W 

00270 

Host watch dog timeout status, write 1 to clear host 

watch dog timeout status 

R/W 

00271 

1: enable, 0: disable fast mode 

R/W 

00273 

Reset status, 1: first read after powered on, 0: not the 

first read after powered on 

00289 ~ 00290 

Low alarm status of channel 0 to 1. Write 1 to clear low 

latched alarm of channel 0 to 1 

R/W 

00305 ~ 00306 

High alarm status of channel 0 to 1. Write 1 to clear 

high latched alarm of channel 0 to 1 

R/W 

00321 ~ 00322 

Enable/disable alarm of channel 0 to 1 

R/W 

00337 ~ 00338 

Alarm type, momentary or latched, of channel 0 to 1 

R/W 

00513 ~ 00514 

Write 1 to clear counter value of digital input channel 0 

to 1 

 

 

Summary of Contents for tM-AD4P2C2

Page 1: ...t Guide will provide information needed to get started with the tM AD4P2C2 Please also consult the User Manual for detailed information on the setup and use of the tM AD4P2C2 In addition to this guide...

Page 2: ...d E mail service icpdas com tM AD4P2C2 Quick Start Guide 2 1 Understanding the Hardware Specifications and Wiring Diagrams Before installing the hardware you should have a basic understanding of hardw...

Page 3: ...ICP DAS CO LTD Copyright 2013 ICP DAS Co Ltd All Rights Reserved E mail service icpdas com tM AD4P2C2 Quick Start Guide 3 I O Specifications...

Page 4: ...ICP DAS CO LTD Copyright 2013 ICP DAS Co Ltd All Rights Reserved E mail service icpdas com tM AD4P2C2 Quick Start Guide 4 Wire Connection Pin Assignment...

Page 5: ...t position 3 Connecting to the PC and the Power Supply The tM Series series is equipped with an RS 485 port for connection to a 232 USB converter to PC 2 Booting the tM AD4P2C2 in Init Mode Connect to...

Page 6: ...e the DCON Utility The DCON Utility can be obtained from the companion from the ICPDAS FTP site http www icpdas com download 7000 7000 htm Step 2 Follow the prompts to complete the installation After...

Page 7: ...Utility shortcut on your desktop Step 2 Use the COM1 port to communicate with the tM AD4P2C2 Click the COM Port option from the menu and a dialog box will be displayed that will allow you to set the c...

Page 8: ...earch for the tM AD4P2C2 module Click Start Search button from the toolbox to search for the tM AD4P2C2 module After the tM AD4P2C2 module is displayed in the list click Stop Search button Step 4 Conn...

Page 9: ...ox to 1 and then click Setting button to save the settings Make sure the INIT switch is placed in the Normal position 7 Starting the Module Operation After rebooting the tM AD4P2C2 module search for t...

Page 10: ...are version high word R 40483 Module name low word 0x4001 R 40484 Module name high word 0x0722 R 40485 Module address valid range 1 247 R W 40486 Bits 5 0 Baud rate 0x03 0x0A Code 0x03 0x04 0x05 0x06...

Page 11: ...Modbus ASCII R W 00260 Modbus host watchdog mode 0 same as I 7000 1 can use AO and DO command to clear host watchdog timeout status R W 00261 1 enable 0 disable host watchdog R W 00264 Write 1 to clea...