Address
Description
Attribute
00073 ~ 00074
10073 ~ 10074
High latched value of DO
R
00097 ~ 00098
10097 ~ 10098
Low latched value of DI
R
00105 ~ 00106
10105 ~ 10106
Low latched value of DO
R
00225 ~ 00228
10225 ~ 10228
Over/under range status of analog input channel 0 to 3
for 4 ~ 20mA or 0 ~ 20mA ranges
R
00001 ~ 00002
Digital output value of channel 0 to 1
R/W
00129 ~ 00130
Safe value of digital output channel 0 to 1
R/W
00161 ~ 00162
Power on value of digital output channel 0 to 1
R/W
00193 ~ 00194
Counter update trigger edge of digital input channel 0
to 1
R/W
00257
Protocol, 0: DCON, 1: Modbus RTU
R/W
00258
Protocol, 0: determined by 00257, 1: Modbus ASCII
R/W
00260
Modbus host watchdog mode
0: same as I-7000
1: can use AO and DO command to clear host
watchdog timeout status
R/W
00261
1: enable, 0: disable host watchdog
R/W
00264
Write 1 to clear latched DIO states
W
00265
DI active state
R/W
00266
DO active state
R/W
00269
Modbus data format, 0: hex, 1: engineering
R/W
00270
Host watch dog timeout status, write 1 to clear host
watch dog timeout status
R/W
00271
1: enable, 0: disable fast mode
R/W
00273
Reset status, 1: first read after powered on, 0: not the
first read after powered on
R
00289 ~ 00290
Low alarm status of channel 0 to 1. Write 1 to clear low
latched alarm of channel 0 to 1
R/W
00305 ~ 00306
High alarm status of channel 0 to 1. Write 1 to clear
high latched alarm of channel 0 to 1
R/W
00321 ~ 00322
Enable/disable alarm of channel 0 to 1
R/W
00337 ~ 00338
Alarm type, momentary or latched, of channel 0 to 1
R/W
00513 ~ 00514
Write 1 to clear counter value of digital input channel 0
to 1
W