the configuration dialog box. 

 

 

 

Address

 

Description

 

Attribute

 

30001 ~ 30002

 

40001 ~ 40002

 

Analog input value of channel 0 to 1

 

R

 

40257 ~ 40258

 

Analog input type code of channel 0 to 1

 

R/W

 

40481 

 

Firmware version (low word)

 

R

 

40482

 

Firmware version (high word)

 

R

 

40483

 

Module name (low word) , 0x2001

 

R

 

40484

 

Module name (high word) , 0x0700

 

R

 

40485

 

Module address, valid range: 1 ~ 247

 

R/W

 

40486

 

Bits 5:0 

 

Baud rate, 0x03 ~ 0x0A

 

Code

 

0x03

 

0x04

 

0x05

 

0x06

 

Baud

 

1200

 

2400

 

4800

 

9600

 

Code

 

0x07

 

0x08

 

0x09

 

0x0A

 

Baud

 

19200

 

38400

 

57600

 

115200

 

Bits 7:6

 

        00: no parity, 1 stop bit

 

        01: no parity, 2 stop bits

 

        10: even parity, 1 stop bit

 

        11: odd parity, 1 stop bit

 

R/W

 

40488

 

Modbus response delay time in ms, valid range: 0 ~ 30

 

R/W

 

40489

 

Host watchdog timeout value, 0 ~ 255, in 0.1s 

 

R/W

 

40490

 

Channel enable/disable, 00h ~ 03h

 

R/W

 

40492

 

Host watchdog timeout count, write 0 to clear

 

R/W

 

40494

 

4mA under range threshold in 0.1mA, 0 ~ 40

 

R/W

 

 

Address

 

Description

 

Attribute

 

10129 ~ 10130

 

00129 ~ 00130

 

Over/under range status of channel 0 to 1 for 4 ~ 20mA or 0 ~ 20mA ranges

 

R

 

00257

 

Protocol, 0: DCON, 1: Modbus RTU

 

R/W

 

00258

 

Protocol, 0: determined by 00257, 1: Modbus ASCII

 

R/W

 

00261

 

1: enable, 0: disable host watchdog

 

R/W

 

00269

 

Modbus data format, 0: hex, 1: engineering

 

R/W

 

00270

 

Host watch dog timeout status, write 1 to clear host watch dog timeout status

 

R/W

 

00271

 

1: enable, 0: disable fast mode

 

R/W

 

00273

 

Reset status, 1: first read after powered on, 0: not the first read after powered on

 

R

 

 

 

 

--------------------------------------------------------------------------------- 

Modbus Address Mapping

 

Summary of Contents for tM-AD2

Page 1: ...the most popular automation solution for remote monitoring and control applications This Quick Start Guide will provide information needed to get started with the tM AD2 Please also consult the User...

Page 2: ...E mail service icpdas com tM AD2 Quick Start 2 Understanding the Hardware Specifications and Wiring Diagrams Before installing the hardware you should have a basic understanding of hardware specificat...

Page 3: ...Copyright 2015 ICP DAS Co Ltd All Rights Reserved E mail service icpdas com tM AD2 Quick Start 3 I O Specifications Wire Connection Pin Assignment...

Page 4: ...Connecting to the PC and the Power Supply The tM Series series is equipped with an RS 485 port for connection to a 232 USB converter to PC 2 Booting the tM Series in Init Mode Connect to the PC using...

Page 5: ...ftp ftp icpdas com pub cd 8000cd napdos driver dcon_utility CD Napdos Driver DCON_Utility 5 Using the DCON Utility to Initialize the tM Series Module The tM Series is an I O module based on the DCON...

Page 6: ...earch Step 3 Search for the tM Series module Click Start Search button from the toolbox to search for the tM Series module After the tM Series module is displayed in the list click Stop Search button...

Page 7: ...eries module Set the Address field in the dialog box to 1 and then click Setting Module Configurations button to save the settings Make sure the INIT switch is placed in the Normal position 7 Starting...

Page 8: ...even parity 1 stop bit 11 odd parity 1 stop bit R W 40488 Modbus response delay time in ms valid range 0 30 R W 40489 Host watchdog timeout value 0 255 in 0 1s R W 40490 Channel enable disable 00h 03h...

Reviews: